For <strong>Moeller</strong> <strong>Electric</strong> Sales and S<strong>up</strong>port call KMparts.com (866) 595-9616<br />

<strong>Circuit</strong>-<strong>breakers</strong>, switch-disconnec<strong>to</strong>rs<br />

10/98<br />

Ordering<br />

Diagnostics, communication<br />

Description<br />

Diagnostics and parameterization software (in situ)<br />

PC software for direct connection <strong>to</strong> all new NZM circuit<strong>breakers</strong><br />

with electronic releases (IEC and UL/CSA<br />

devices) or for direct connection <strong>to</strong> the DMI module,<br />

including the required connectionn cable.<br />

Protection parameter: online display and curve display,<br />

expoet option <strong>to</strong> curve programme “<strong>Moeller</strong><br />

CurveSelect”<br />

Warning and release messages: reading of diagnostic<br />

memory also in volt-free state.<br />

Load currents: display and trend indication<br />

Recording and export options <strong>to</strong> Excel for load currents<br />

and diagnostic messages.<br />

Configuration of the DMI: mo<strong>to</strong>r starter, remote<br />

opera<strong>to</strong>r, assignment of the DMI inputs and outputs and<br />

displays.<br />

Data Management Interface (DMI Module)<br />

Query of diagnostics and operational data, display of<br />

currents, mo<strong>to</strong>r starter function, parameterisation and<br />

control of the circuit-breaker with electronic release<br />

Comprehensive remote diagnostic options and remote<br />

operation via fieldbus in combination with a field Bus<br />

connection.<br />

Inclusive NZM-XDMI-CAB connection cable between<br />

NZM and DMI (length: 2 m).<br />

DEL ALT<br />

ESC OK<br />

NZM, easy<br />

Expansion unit, networking<br />

Interfacing <strong>to</strong> the DMI module for transfer of phase currents, parameter data, status<br />

data and diagnostics data as well as the circuit-breaker position (wiring of<br />

auxiliary contacts <strong>to</strong> DMI inputs).<br />

DMI configuration via field bus.<br />

Actuation of the DMI mo<strong>to</strong>r starter functions and the NZM remote opera<strong>to</strong>r (via<br />

DMI outputs wiring).<br />

Detection of digital inputs and actuation of the outputs via field Bus<br />

Fieldbus interface: <strong>to</strong> PROFIBUS-DPV1 slave.<br />

Can be operated with class 1 and class 2 masters.<br />

Addresses available: 1 <strong>to</strong> 126<br />

Fieldbus connection <strong>to</strong> CANopen<br />

Addresses available: 1 <strong>to</strong> 127<br />

Fieldbus connection <strong>to</strong> DeviceNet<br />

Addresses available: 0 <strong>to</strong> 63<br />

Switched-mode power s<strong>up</strong>ply unit<br />

For DMI module<br />

• Rated input voltage: 50/60 HZ: 115/230 V AC<br />

• Rated output voltage (residual ripple): 24 V DC (g 3 %)<br />

• Rated output current: 1.25 A<br />

Telescopic adapter<br />

For DMI module<br />

For equalization of the mounting depth of rear mounting devices in CI enclosures<br />

and cabinets<br />

With 35 mm <strong>to</strong>p-hat rail IEC/EN 60715, adjustable from<br />

75 – 115 mm. Screw-on and snap fitting.<br />

Part no.<br />

Article no.<br />

NZM-XPC-KIT<br />

265631<br />

NZM-XDMI612<br />

260217<br />

NZM-XDMI-DPV1<br />

270333<br />

EASY221-CO<br />

233539<br />

EASY222-DN<br />

233540<br />

EASY400-POW<br />

212319<br />

M22-TA<br />

226161<br />

<strong>Moeller</strong> HPL0211-2007/2008<br />

Price<br />

see price list<br />

Std. pack<br />

Notes<br />

http://catalog.moeller.net<br />

1 off Only suitable for use in conjunction<br />

with circuit-<strong>breakers</strong> having<br />

electronic releases.<br />

Free-of-charge download of the<br />

manual AWB1230-1459 and a<br />

demo software at<br />

www.moeller.net.<br />

1 off Only suitable for use in conjunction<br />

with circuit-<strong>breakers</strong> having<br />

electronic releases.<br />

Free download of manual<br />

AWB1230-1441 at<br />

www.moeller.net.<br />

1 off Connected <strong>to</strong> the DMI module and<br />

has the same con<strong>to</strong>ur appearance.<br />

Replaces the DPV0 interface<br />

1 off EASY204-DP.<br />

1 off<br />

1 off<br />

1 off