For <strong>Moeller</strong> <strong>Electric</strong> Sales and S<strong>up</strong>port call KMparts.com (866) 595-9616<br />

10/96<br />

Ordering<br />

Accessories<br />

Ordering<br />

Accessories<br />

10/97<br />

<strong>Circuit</strong>-<strong>breakers</strong>, switch-disconnec<strong>to</strong>rs<br />

NZM2, NZM3, NZM4<br />

<strong>Moeller</strong> HPL0211-2007/2008<br />

For use with Rated control voltage<br />

U s<br />

Part no.<br />

Article no. when ordered<br />

separately<br />

V<br />

Remote opera<strong>to</strong>r<br />

For remote switching of circuit-<strong>breakers</strong> and switch-disconnec<strong>to</strong>rs.<br />

ON and OFF switching and resetting by means of 2-wire or 3-wire control.<br />

Can be synchronized.<br />

Local switching by hand possible<br />

Lockable in the 0 position of the remote opera<strong>to</strong>r with <strong>up</strong> <strong>to</strong> 3 padlocks (hasp thickness: 4 – 8 mm)<br />

NZM2(-4)<br />

N(S)2(-4)<br />

NZM3(-4)<br />

N(S)3(-4)<br />

NZM4(-4)<br />

N(S)4(-4)<br />

110 – 130 V 50/60 Hz NZM2-XR110-130AC<br />

259830<br />

208 – 240 V 50/60 Hz NZM2-XR208-240AC<br />

259832<br />

380 – 440 V 50/60 Hz NZM2-XR380-440AC 1)<br />

259834<br />

24 – 30 V DC NZM2-XR24-30DC<br />

259836<br />

110 – 130 V DC NZM2-XR110-130DC<br />

259840<br />

220 – 250 V DC NZM2-XR220-250DC<br />

259842<br />

110 – 130 V 50/60 Hz NZM3-XR110-130AC<br />

259848<br />

208 – 240 V 50/60 Hz NZM3-XR208-240AC<br />

259850<br />

380 – 440 V 50/60 Hz NZM3-XR380-440AC 1)<br />

259852<br />

24 – 30 V DC NZM3-XR24-30DC<br />

259854<br />

110 – 130 V DC NZM3-XR110-130DC<br />

259858<br />

220 – 250 V DC NZM3-XR220-250DC<br />

259860<br />

110 – 130 V 50/60 Hz NZM4-XR110-130AC<br />

266684<br />

208 – 240 V 50/60 Hz NZM4-XR208-240AC<br />

266685<br />

380 – 440 V 50/60 Hz NZM4-XR380-440AC 1)<br />

266686<br />

24 – 30 V DC NZM4-XR24-30DC<br />

266691<br />

110 – 130 V DC NZM4-XR110-130DC<br />

266693<br />

220 – 250 V DC NZM4-XR220-250DC<br />

266694<br />

http://catalog.moeller.net<br />

Price<br />

see price list<br />

Std. pack<br />

1 off<br />

http://catalog.moeller.net<br />

Notes<br />

<strong>Moeller</strong> HPL0211-2007/2008<br />

Remote opera<strong>to</strong>r are combinable with NZM circuit-<strong>breakers</strong> and N switch-disconnec<strong>to</strong>rs but not with PN switch-disconnec<strong>to</strong>rs.<br />

A standard auxiliary contact (HIN) for the switch position detection is s<strong>up</strong>plied.<br />

When installing the NZM2-XR… and NZM3-XR… remote opera<strong>to</strong>rs on 4 pole switches, an additional 4 pole NZM2-XAVPR or NZM3-XAVPR shroud is necessary.<br />

3-wire control<br />

L1<br />

(L1+)<br />

N<br />

(L1–, L2)<br />

0 I<br />

70<br />

2-wire control<br />

L1<br />

(L1+)<br />

H1<br />

71 72<br />

75<br />

74<br />

S 0 I H1<br />

70 71 72<br />

75<br />

74<br />

0 I<br />

HIA H1<br />

70 71 72<br />

75<br />

74<br />

Terminal 70/71:<br />

Please note during engineering:<br />

Full current flows though the contact during make and break!<br />

RMQ series contact elements can be used for the NZM2(3,4)-XR… remote opera<strong>to</strong>rs.<br />

Terminal 75:<br />

Operational readiness signal when the cover is closed, and not locked.<br />

AC-15: 400 V; 2 A<br />

DC-13: 220 V; 0.2 A<br />

N<br />

(L1–, L2)<br />

Three-wire control with au<strong>to</strong>matic reset <strong>to</strong> the 0 position after the switch has tripped<br />

L1<br />

(L1+)<br />

N<br />

(L1–, L2)<br />

Switching cycle:<br />

NZM2-XR<br />

60 ms t > 3 s 60 ms<br />

r r r<br />

r<br />

OFF ON ON OFF<br />

OFF ON<br />

NZM2, NZM3, NZM4<br />

<strong>Circuit</strong>-<strong>breakers</strong>, switch-disconnec<strong>to</strong>rs<br />

Shroud for 4th pole<br />

Additional shroud for mounting the NZM2-XR... and NZM3-XR... on a 4-pole switch.<br />

NZM2-4<br />

N2-4<br />

NZM3-4<br />

N3-4<br />

Clamp terminal springloaded clamp<br />

Control circuit terminal springloaded terminals<br />

NZM...-XR...<br />

NZM2-XAVPR<br />

266677<br />

NZM3-XAVPR<br />

266678<br />

NZM-XRC<br />

266696<br />

1 off<br />

1 off<br />

1 off<br />

NZM3-XR<br />

80 ms t > 3 s 80 ms<br />

r r r<br />

r<br />

OFF ON ON OFF<br />

OFF ON<br />

NZM4-XR<br />

100 ms t > 3 s 100 ms<br />

r r r<br />

r<br />

OFF ON ON OFF<br />

OFF ON<br />

The time interval between OFF and ON is 3 seconds.<br />

On commands received during the time interval are ignored within the first 3 seconds after switch off.<br />

Protective cover for door cu<strong>to</strong>ut<br />

Transparent protective shroud <strong>to</strong> increase the degree of protection <strong>to</strong> IP54<br />

– RTR-<strong>NZM1</strong>0<br />

034825<br />

1 off <strong>Electric</strong>al remote switching and manual tripping (push <strong>to</strong> trip) are still possible.<br />

Notes<br />

1) Not UL/CSA approved.