Ordering<br />
Undervoltage releases, off-delayed<br />
10/77<br />
http://catalog.moeller.net<br />
<strong>Moeller</strong> HPL0211-2007/2008<br />
For use with<br />
Undervoltage releases, off-delayed<br />
Combination of separate delay unit and special tripping device.<br />
Not UL/CSA approved.<br />
Delay unit<br />
Voltage dips of less than the setting between 0.06 – 16 s do not<br />
cause disconnection of the NZM circuit-breaker or N switchdisconnec<strong>to</strong>r.<br />
<strong>NZM1</strong>(-4), 2(-4), 3(-4), 4(-4)<br />
N(S)1(-4), 2(-4), 3(-4), 4(-4)<br />
50/60 Hz<br />
220 V – 240 V<br />
380 V – 440 V<br />
480 V – 550 V<br />
DC/AC<br />
24 V<br />
Part no.<br />
Article no. when<br />
ordered separately<br />
UVU-NZM<br />
260154<br />
Price<br />
see price<br />
list<br />
Std. pack<br />
<strong>NZM1</strong>, NZM2/3..., NZM4<br />
Notes<br />
1 off Adjustable delay time 70 ms – 4 s.<br />
With additional capaci<strong>to</strong>r <strong>up</strong> <strong>to</strong> 16 s.<br />
A special tripping device is required.<br />
Cannot be installed simultaneously with<br />
NZM...-XHIV... or NZM...-XA... shunt release.<br />
Delay unit for separate installation (Fixing: <strong>to</strong>phat<br />
rail or screws).<br />
For other operating voltages use control<br />
transformer.<br />
<strong>Circuit</strong>-<strong>breakers</strong>, switch-disconnec<strong>to</strong>rs<br />
Special tripping device<br />
For combination with separate delay unit<br />
Without auxiliary contacts<br />
<strong>NZM1</strong> with 3 m separate connection cables instead of screw<br />
terminal, NZM2, 3 , 4 with screw terminal<br />
U<br />
D1<br />
D2<br />
<strong>NZM1</strong>(-4)<br />
N(S)1(-4)<br />
NZM2(-4), N(S)2(-4)<br />
NZM3(-4), N(S)3(-4)<br />
<strong>NZM1</strong>-XUVL<br />
271607<br />
NZM2/3-XUV<br />
259527<br />
1 off UVU-NZM delay unit is additionally required.<br />
Cannot be installed simultaneously with<br />
separate NZM...-XHIV early-make auxiliary<br />
contact or NZM...-XA... shunt release.<br />
NZM4(-4)<br />
N(S)4(-4)<br />
NZM4-XUV<br />
266588<br />
With 2 early-make auxiliary contacts<br />
<strong>NZM1</strong> with 3 m separate connection cables instead of screw<br />
terminal, NZM2, 3 , 4 with screw terminal<br />
U<br />
D1 3.13<br />
D2<br />
3.14<br />
<strong>NZM1</strong>(-4)<br />
N(S)1(-4)<br />
NZM2(-4), N(S)2(-4)<br />
NZM3(-4), N(S)3(-4)<br />
NZM4(-4)<br />
N(S)4(-4)<br />
<strong>NZM1</strong>-XUVHIVL<br />
271608<br />
NZM2/3-XUVHIV<br />
259684<br />
NZM4-XUVHIV<br />
266596<br />
1 off Cannot be used in conjunction with NZM...-<br />
XR... remote opera<strong>to</strong>r.<br />
UVU-NZM delay unit is additionally required.<br />
Cannot be installed simultaneously with<br />
separate NZM...-XHIV early-make auxiliary<br />
contact or NZM...-XA... shunt release.<br />
<strong>NZM1</strong>, 2, 3: Early-make of the auxiliary<br />
contacts with on and off switching (manual<br />
operation): approx. 20 ms.<br />
NZM4: Early-make of the auxiliary contacts<br />
with switch on (manual operation):<br />
approx. 90 ms.<br />
With 2 separately operating early-make auxiliary contacts<br />
<strong>NZM1</strong> with 3 m separate connection cables instead of screw<br />
terminal, NZM2, 3, 4 with screw terminal, contact 3.23 and 3.24<br />
with 3 m separate connection cables.<br />
D1<br />
D2<br />
3.13<br />
3.14<br />
3.23<br />
3.24<br />
<strong>NZM1</strong>(-4)<br />
N(S)1(-4)<br />
NZM2(-4), N(S)2(-4)<br />
NZM3(-4), N(S)3(-4)<br />
NZM4(-4)<br />
N(S)4(-4)<br />
<strong>NZM1</strong>-XUVHIV20L<br />
271609<br />
NZM2/3-XUVHIV20<br />
259688<br />
NZM4-XUVHIV20<br />
266604<br />
1 off Cannot be used in conjunction with NZM...-<br />
XR... remote opera<strong>to</strong>r.<br />
UVU-NZM delay unit is additionally required.<br />
Cannot be installed simultaneously with<br />
separate NZM...-XHIV early-make auxiliary<br />
contact or NZM...-XA... shunt release.<br />
<strong>NZM1</strong>, 2, 3: Early-make of the auxiliary<br />
contacts with on and off switching (manual<br />
operation): approx. 20 ms.<br />
NZM4: Early-make of the auxiliary contacts<br />
with switch on (manual operation):<br />
approx. 90 ms.<br />