Ordering<br />

Undervoltage releases, off-delayed<br />

10/77<br />

http://catalog.moeller.net<br />

<strong>Moeller</strong> HPL0211-2007/2008<br />

For use with<br />

Undervoltage releases, off-delayed<br />

Combination of separate delay unit and special tripping device.<br />

Not UL/CSA approved.<br />

Delay unit<br />

Voltage dips of less than the setting between 0.06 – 16 s do not<br />

cause disconnection of the NZM circuit-breaker or N switchdisconnec<strong>to</strong>r.<br />

<strong>NZM1</strong>(-4), 2(-4), 3(-4), 4(-4)<br />

N(S)1(-4), 2(-4), 3(-4), 4(-4)<br />

50/60 Hz<br />

220 V – 240 V<br />

380 V – 440 V<br />

480 V – 550 V<br />

DC/AC<br />

24 V<br />

Part no.<br />

Article no. when<br />

ordered separately<br />

UVU-NZM<br />

260154<br />

Price<br />

see price<br />

list<br />

Std. pack<br />

<strong>NZM1</strong>, NZM2/3..., NZM4<br />

Notes<br />

1 off Adjustable delay time 70 ms – 4 s.<br />

With additional capaci<strong>to</strong>r <strong>up</strong> <strong>to</strong> 16 s.<br />

A special tripping device is required.<br />

Cannot be installed simultaneously with<br />

NZM...-XHIV... or NZM...-XA... shunt release.<br />

Delay unit for separate installation (Fixing: <strong>to</strong>phat<br />

rail or screws).<br />

For other operating voltages use control<br />

transformer.<br />

<strong>Circuit</strong>-<strong>breakers</strong>, switch-disconnec<strong>to</strong>rs<br />

Special tripping device<br />

For combination with separate delay unit<br />

Without auxiliary contacts<br />

<strong>NZM1</strong> with 3 m separate connection cables instead of screw<br />

terminal, NZM2, 3 , 4 with screw terminal<br />

U<br />

D1<br />

D2<br />

<strong>NZM1</strong>(-4)<br />

N(S)1(-4)<br />

NZM2(-4), N(S)2(-4)<br />

NZM3(-4), N(S)3(-4)<br />

<strong>NZM1</strong>-XUVL<br />

271607<br />

NZM2/3-XUV<br />

259527<br />

1 off UVU-NZM delay unit is additionally required.<br />

Cannot be installed simultaneously with<br />

separate NZM...-XHIV early-make auxiliary<br />

contact or NZM...-XA... shunt release.<br />

NZM4(-4)<br />

N(S)4(-4)<br />

NZM4-XUV<br />

266588<br />

With 2 early-make auxiliary contacts<br />

<strong>NZM1</strong> with 3 m separate connection cables instead of screw<br />

terminal, NZM2, 3 , 4 with screw terminal<br />

U<br />

D1 3.13<br />

D2<br />

3.14<br />

<strong>NZM1</strong>(-4)<br />

N(S)1(-4)<br />

NZM2(-4), N(S)2(-4)<br />

NZM3(-4), N(S)3(-4)<br />

NZM4(-4)<br />

N(S)4(-4)<br />

<strong>NZM1</strong>-XUVHIVL<br />

271608<br />

NZM2/3-XUVHIV<br />

259684<br />

NZM4-XUVHIV<br />

266596<br />

1 off Cannot be used in conjunction with NZM...-<br />

XR... remote opera<strong>to</strong>r.<br />

UVU-NZM delay unit is additionally required.<br />

Cannot be installed simultaneously with<br />

separate NZM...-XHIV early-make auxiliary<br />

contact or NZM...-XA... shunt release.<br />

<strong>NZM1</strong>, 2, 3: Early-make of the auxiliary<br />

contacts with on and off switching (manual<br />

operation): approx. 20 ms.<br />

NZM4: Early-make of the auxiliary contacts<br />

with switch on (manual operation):<br />

approx. 90 ms.<br />

With 2 separately operating early-make auxiliary contacts<br />

<strong>NZM1</strong> with 3 m separate connection cables instead of screw<br />

terminal, NZM2, 3, 4 with screw terminal, contact 3.23 and 3.24<br />

with 3 m separate connection cables.<br />

D1<br />

D2<br />

3.13<br />

3.14<br />

3.23<br />

3.24<br />

<strong>NZM1</strong>(-4)<br />

N(S)1(-4)<br />

NZM2(-4), N(S)2(-4)<br />

NZM3(-4), N(S)3(-4)<br />

NZM4(-4)<br />

N(S)4(-4)<br />

<strong>NZM1</strong>-XUVHIV20L<br />

271609<br />

NZM2/3-XUVHIV20<br />

259688<br />

NZM4-XUVHIV20<br />

266604<br />

1 off Cannot be used in conjunction with NZM...-<br />

XR... remote opera<strong>to</strong>r.<br />

UVU-NZM delay unit is additionally required.<br />

Cannot be installed simultaneously with<br />

separate NZM...-XHIV early-make auxiliary<br />

contact or NZM...-XA... shunt release.<br />

<strong>NZM1</strong>, 2, 3: Early-make of the auxiliary<br />

contacts with on and off switching (manual<br />

operation): approx. 20 ms.<br />

NZM4: Early-make of the auxiliary contacts<br />

with switch on (manual operation):<br />

approx. 90 ms.<br />

For <strong>Moeller</strong> <strong>Electric</strong> Sales and S<strong>up</strong>port call KMparts.com (866) 595-9616