For <strong>Moeller</strong> <strong>Electric</strong> Sales and S<strong>up</strong>port call KMparts.com (866) 595-9616<br />

<strong>Circuit</strong>-<strong>breakers</strong>, switch-disconnec<strong>to</strong>rs<br />

10/72<br />

Ordering<br />

Undervoltage release with screw terminal<br />

For use with Rated control voltage Part no.<br />

Article no. when<br />

ordered separately<br />

Undervoltage releases<br />

Without auxiliary contact<br />

Non-delayed disconnection of NZM circuit-<strong>breakers</strong> or N switch-disconnec<strong>to</strong>rs<br />

when the control voltage sinks below 35 – 70% U S .<br />

For use with Emergency-S<strong>to</strong>p devices in conjunction with Emergency-S<strong>to</strong>p but<strong>to</strong>n.<br />

D1<br />

U <<br />

D2<br />

D1<br />

U <<br />

D2<br />

<strong>NZM1</strong><br />

With clamp<br />

terminal on the<br />

left-hand switch<br />

side.<br />

With 3 m<br />

connection<br />

cable instead of<br />

screw<br />

termination.<br />

<strong>NZM1</strong>(-4),<br />

N(S)1(-4)<br />

<strong>NZM1</strong>(-4),<br />

N(S)1(-4)<br />

U s<br />

V<br />

24 V 50/60 Hz <strong>NZM1</strong>-XU24AC<br />

259434<br />

110 V – 130 V 50/60 Hz <strong>NZM1</strong>-XU110-130AC<br />

259440<br />

208 V 240 V 50/60 Hz <strong>NZM1</strong>-XU208-240AC<br />

259442<br />

380 V – 440 V 50/60 Hz <strong>NZM1</strong>-XU380-440AC<br />

259444<br />

480 V – 525 V 50/60 Hz <strong>NZM1</strong>-XU480-525AC<br />

259446<br />

600 V 50/60 Hz <strong>NZM1</strong>-XU600AC<br />

259448<br />

12 V DC <strong>NZM1</strong>-XU12DC<br />

259450<br />

24 V DC <strong>NZM1</strong>-XU24DC<br />

259452<br />

110 V – 130 V DC <strong>NZM1</strong>-XU110-130DC<br />

259458<br />

220 V – 250 V DC <strong>NZM1</strong>-XU220-250DC<br />

259460<br />

24 V 50/60 Hz <strong>NZM1</strong>-XUL24AC<br />

259462<br />

110 V – 130 V 50/60 Hz <strong>NZM1</strong>-XUL110-130AC<br />

259468<br />

208 V 240 V 50/60 Hz <strong>NZM1</strong>-XUL208-240AC<br />

259471<br />

380 V – 440 V 50/60 Hz <strong>NZM1</strong>-XUL380-440AC<br />

259473<br />

480 V – 525 V 50/60 Hz <strong>NZM1</strong>-XUL480-525AC<br />

259475<br />

600 V 50/60 Hz <strong>NZM1</strong>-XUL600AC<br />

259477<br />

12 V DC <strong>NZM1</strong>-XUL12DC<br />

259479<br />

24 V DC <strong>NZM1</strong>-XUL24DC<br />

259481<br />

110 V 130 V DC <strong>NZM1</strong>-XUL110-130DC<br />

259487<br />

220 V – 250 V DC <strong>NZM1</strong>-XUL220-250DC<br />

259489<br />

<strong>Moeller</strong> HPL0211-2007/2008<br />

Price<br />

see price<br />

list<br />

Std. pack<br />

Notes<br />

http://catalog.moeller.net<br />

1 off When the undervoltage<br />

release is de-energized,<br />

accidental contact with the<br />

main contacts of the switch<br />

during attempts <strong>to</strong> switch on,<br />

is safely prevented .<br />

1 off<br />

Undervoltage release cannot<br />

be installed simultaneously<br />

with NZM...-XHIV... earlymake<br />

auxiliary contact or<br />

NZM...-XA... shunt release.