For <strong>Moeller</strong> <strong>Electric</strong> Sales and S<strong>up</strong>port call KMparts.com (866) 595-9616<br />
<strong>Circuit</strong>-<strong>breakers</strong>, switch-disconnec<strong>to</strong>rs<br />
10/72<br />
Ordering<br />
Undervoltage release with screw terminal<br />
For use with Rated control voltage Part no.<br />
Article no. when<br />
ordered separately<br />
Undervoltage releases<br />
Without auxiliary contact<br />
Non-delayed disconnection of NZM circuit-<strong>breakers</strong> or N switch-disconnec<strong>to</strong>rs<br />
when the control voltage sinks below 35 – 70% U S .<br />
For use with Emergency-S<strong>to</strong>p devices in conjunction with Emergency-S<strong>to</strong>p but<strong>to</strong>n.<br />
D1<br />
U <<br />
D2<br />
D1<br />
U <<br />
D2<br />
<strong>NZM1</strong><br />
With clamp<br />
terminal on the<br />
left-hand switch<br />
side.<br />
With 3 m<br />
connection<br />
cable instead of<br />
screw<br />
termination.<br />
<strong>NZM1</strong>(-4),<br />
N(S)1(-4)<br />
<strong>NZM1</strong>(-4),<br />
N(S)1(-4)<br />
U s<br />
V<br />
24 V 50/60 Hz <strong>NZM1</strong>-XU24AC<br />
259434<br />
110 V – 130 V 50/60 Hz <strong>NZM1</strong>-XU110-130AC<br />
259440<br />
208 V 240 V 50/60 Hz <strong>NZM1</strong>-XU208-240AC<br />
259442<br />
380 V – 440 V 50/60 Hz <strong>NZM1</strong>-XU380-440AC<br />
259444<br />
480 V – 525 V 50/60 Hz <strong>NZM1</strong>-XU480-525AC<br />
259446<br />
600 V 50/60 Hz <strong>NZM1</strong>-XU600AC<br />
259448<br />
12 V DC <strong>NZM1</strong>-XU12DC<br />
259450<br />
24 V DC <strong>NZM1</strong>-XU24DC<br />
259452<br />
110 V – 130 V DC <strong>NZM1</strong>-XU110-130DC<br />
259458<br />
220 V – 250 V DC <strong>NZM1</strong>-XU220-250DC<br />
259460<br />
24 V 50/60 Hz <strong>NZM1</strong>-XUL24AC<br />
259462<br />
110 V – 130 V 50/60 Hz <strong>NZM1</strong>-XUL110-130AC<br />
259468<br />
208 V 240 V 50/60 Hz <strong>NZM1</strong>-XUL208-240AC<br />
259471<br />
380 V – 440 V 50/60 Hz <strong>NZM1</strong>-XUL380-440AC<br />
259473<br />
480 V – 525 V 50/60 Hz <strong>NZM1</strong>-XUL480-525AC<br />
259475<br />
600 V 50/60 Hz <strong>NZM1</strong>-XUL600AC<br />
259477<br />
12 V DC <strong>NZM1</strong>-XUL12DC<br />
259479<br />
24 V DC <strong>NZM1</strong>-XUL24DC<br />
259481<br />
110 V 130 V DC <strong>NZM1</strong>-XUL110-130DC<br />
259487<br />
220 V – 250 V DC <strong>NZM1</strong>-XUL220-250DC<br />
259489<br />
<strong>Moeller</strong> HPL0211-2007/2008<br />
Price<br />
see price<br />
list<br />
Std. pack<br />
Notes<br />
http://catalog.moeller.net<br />
1 off When the undervoltage<br />
release is de-energized,<br />
accidental contact with the<br />
main contacts of the switch<br />
during attempts <strong>to</strong> switch on,<br />
is safely prevented .<br />
1 off<br />
Undervoltage release cannot<br />
be installed simultaneously<br />
with NZM...-XHIV... earlymake<br />
auxiliary contact or<br />
NZM...-XA... shunt release.