Circuit-breakers NZM1, 2, 3, 4 up to 2000 A - Moeller Electric Parts
Circuit-breakers NZM1, 2, 3, 4 up to 2000 A - Moeller Electric Parts
Circuit-breakers NZM1, 2, 3, 4 up to 2000 A - Moeller Electric Parts
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
For <strong>Moeller</strong> <strong>Electric</strong> Sales and S<strong>up</strong>port call KMparts.com (866) 595-9616<br />
10/56<br />
Ordering<br />
Connection types<br />
Ordering<br />
Connection types<br />
10/57<br />
<strong>Circuit</strong>-<strong>breakers</strong>. switch-disconnec<strong>to</strong>rs<br />
NZM3<br />
Max. cable<br />
connection area<br />
<strong>Moeller</strong> HPL0211-2007/2008<br />
http://catalog.moeller.net<br />
http://catalog.moeller.net<br />
<strong>Moeller</strong> HPL0211-2007/2008<br />
Rated For use with Terminal capacities Terminal capacities Part no.<br />
current 1) Article no. when<br />
For use with For use with Type of<br />
conduc<strong>to</strong>r<br />
Terminal<br />
capacities<br />
AWG/kcmil<br />
Cu strip (number of<br />
segments x width x<br />
Copper<br />
busbar width<br />
I n<br />
A<br />
segment thickness) x thickness<br />
mm 2 mm mm<br />
ordered with<br />
basic unit<br />
Part no.<br />
Article no. when<br />
ordered<br />
separately<br />
Terminals for connection width extension<br />
max. 500 NZM3, PN3, N(S)3 3 pole Cu cable 1 x 120 – 300 NZM3-XK300<br />
100782<br />
NZM3(-4), PN3(-4),<br />
N3(-4)<br />
4 pole NZM3-4-XK300<br />
100783<br />
not UL/CSA approved 630 NZM3, PN3, N(S)3 3 pole (2 x) 11 x 21 x 1.0 NZM3-XK22X21<br />
100784<br />
NZM3(-4), PN3(-4),<br />
N3(-4)<br />
4 pole (2 x) 11 x 21 x 1.0 NZM3-4-<br />
XK22X21<br />
100785<br />
Std.<br />
pack<br />
Notes<br />
NZM3<br />
1 off Type contains parts for a terminal located at <strong>to</strong>p or<br />
bot<strong>to</strong>m for 3 or 4-pole circuit-<strong>breakers</strong>.<br />
1 off Only in conjunction with connection width<br />
extension NZM3(-4)-XKV70.<br />
Use with flexible and highly flexible conduc<strong>to</strong>rs<br />
1 off ferrules.<br />
Standard with control circuit terminal for 1 x 0.75<br />
1 off – 2.5 mm 2 or 2 x 0.75 – 1.5 mm 2 copper<br />
conduc<strong>to</strong>rs.<br />
<strong>Circuit</strong>-<strong>breakers</strong>. switch-disconnec<strong>to</strong>rs<br />
Tunnel terminal<br />
– max. 350 NZM3(-4), PN3(-4),<br />
N(S)3(-4)<br />
20.5<br />
Three- and fourpole<br />
Copper<br />
conduc<strong>to</strong>rs<br />
Cu cable<br />
Al<br />
conduc<strong>to</strong>rs<br />
Al cable<br />
– max. 630 1 x 50 – 240<br />
2 x 50 – 240<br />
1 x 16 – 185 2) 1 x 6 – 350<br />
–<br />
1 x 0 – 500<br />
2 x 0 – 500<br />
NZM3-XKA1<br />
271459<br />
NZM3-4-XKA1<br />
271460<br />
NZM3-XKA2<br />
271461<br />
NZM3-4-XKA2<br />
271462<br />
1 off Type contains parts for a terminal located at <strong>to</strong>p or<br />
bot<strong>to</strong>m for 3 or 4-pole circuit-<strong>breakers</strong>.<br />
1 off A standard with control circuit terminal for 1 x<br />
0.75 – 2.5 mm 2 (18 – 14 AWG) or 2 x 0.75 – 1.5<br />
mm 2 (18 – 16 AWG) copper conduc<strong>to</strong>rs.<br />
Fitted outside the switch housing<br />
Use with flexible and highly flexible conduc<strong>to</strong>rs<br />
ferrules. Maximum specified cross-section can only<br />
be connected when stranded and without ferrules.<br />
1 off Mounting of the cover NZM3(-4)-XKSA obliga<strong>to</strong>ry<br />
(s<strong>up</strong>plied).<br />
1 off<br />
22.5<br />
Connection on rear<br />
not UL/CSA approved<br />
max. 630<br />
NZM3(-4), PN3(-4),<br />
N3(-4)<br />
Three- and fourpole<br />
Copper<br />
cables<br />
Cu cable<br />
1 x 16 – 240<br />
2 x 16 – 240<br />
max. 500 – – 1 x 10 – 120<br />
2 x 10 – 120<br />
min.6 x 16 x 0.8<br />
Max. 10 x 32 x 1.0<br />
Min. 20 x 5<br />
Max. 30 x 10<br />
+NZM3-XKRO<br />
266790<br />
+NZM3-XKRU<br />
266791<br />
+NZM3-4-XKRO<br />
266793<br />
+NZM3-4-XKRU<br />
266794<br />
NZM3-XKR<br />
266792<br />
NZM3-4-XKR<br />
266795<br />
1 off Type suffix and type contain parts for a circuitbreaker<br />
side at <strong>to</strong>p or bot<strong>to</strong>m for 3 or 4-pole circuit<strong>breakers</strong>.<br />
1 off<br />
O = for fitting at the <strong>to</strong>p<br />
U = for fitting at the bot<strong>to</strong>m<br />
Control circuit terminal<br />
– NZM3(-4), PN3,<br />
N(S)3(-4)<br />
– NZM3(-4), PN3,<br />
N(S)3(-4)<br />
Three- and fourpole<br />
Screw<br />
connection<br />
Box<br />
terminal<br />
1 x 0.75 – 2.5<br />
2 x 0.75 – 1.5<br />
1 x 18 – 14<br />
2 x 18 – 16<br />
NZM3/4-XSTS<br />
266797<br />
NZM-XSTK<br />
266739<br />
1 off Type contains parts for two terminal locations<br />
located at <strong>to</strong>p or bot<strong>to</strong>m for 3 or 4 pole circuit<strong>breakers</strong>.<br />
Included as standard with tunnel terminal<br />
Degree of protection IP1X<br />
1 off Height or thickness of the control circuit terminals<br />
NZM-XSTS = 2 mm<br />
Notes<br />
1) The following applies for the rated current: The values have been determined conform <strong>to</strong><br />
IEC/EN 60947 (switchgear standard) and generally relate <strong>to</strong> the max. defined cross-sections<br />
and are intended for the purpose of orientation.<br />
The engineering standards which apply in each case must be observed.