For <strong>Moeller</strong> <strong>Electric</strong> Sales and S<strong>up</strong>port call KMparts.com (866) 595-9616<br />

<strong>Circuit</strong>-<strong>breakers</strong>, switch-disconnec<strong>to</strong>rs,<br />

UL/CSA IEC<br />

10/40<br />

Ordering<br />

<strong>Circuit</strong>-<strong>breakers</strong> UL/CSA, IEC, electronic releases<br />

NZM…3, NZM…4<br />

Rated current =<br />

rated uninterr<strong>up</strong>ted<br />

current<br />

Setting range<br />

<strong>Moeller</strong> HPL0211-2007/2008<br />

Overload releases Short-circuit releases Part no.<br />

Non-delayed Delayed<br />

Article no.<br />

I n = I u I r I i I sd<br />

A A A A<br />

I<br />

I<br />

Systems, cable, transformer and genera<strong>to</strong>r protection<br />

3 pole<br />

Adjustable overload releases<br />

Terminal screws standard, terminals as accessories<br />

100 50…100 1200 100…1000 NZMN2-VE100-NA<br />

271148<br />

160 80…160 1920 160…1600 NZMN2-VE160-NA<br />

271149<br />

250 125…250 3000 250…2500 NZMN2-VE250-NA<br />

271150<br />

250 125…250 500…2750 250…2500 NZMN3-VE250-NA<br />

269332<br />

400 200…400 800…4400 400…4000 NZMN3-VE400-NA<br />

269333<br />

600 300…600 1200…4800 450…4200 NZMN3-VE600-NA<br />

269334<br />

800 400…800 1600…9600 800…8000 NZMN4-VE800-NA<br />

271154<br />

1000 500…1000 <strong>2000</strong>…1<strong>2000</strong> 1000…10000 NZMN4-VE1000-NA<br />

271155<br />

1200 630…1200 2400…14400 1260…1<strong>2000</strong> NZMN4-VE1200-NA<br />

271156<br />

http://catalog.moeller.net<br />

http://catalog.moeller.net<br />

Normal switching<br />

High switching capacity<br />

capacity<br />

150 kA 240 V 60 Hz<br />

85 kA 240 V 60 Hz<br />

100 kA 480 V 60 Hz 3)<br />

42 kA 480 V 60 Hz 1)<br />

50 kA 600 V 60 Hz 4)<br />

35 kA 600 V 60 Hz 2)<br />

Price<br />

see price list<br />

Part no.<br />

Article no.<br />

NZMH2-VE100-NA<br />

271151<br />

NZMH2-VE160-NA<br />

271152<br />

NZMH2-VE250-NA<br />

271153<br />

NZMH3-VE250-NA<br />

269335<br />

NZMH3-VE400-NA<br />

269336<br />

NZMH3-VE600-NA<br />

269337<br />

NZMH4-VE800-NA<br />

271157<br />

NZMH4-VE1000-NA<br />

271158<br />

NZMH4-VE1200-NA<br />

271159<br />

Price<br />

see price list<br />

<strong>Moeller</strong> HPL0211-2007/2008<br />

Std. pack<br />

1 off<br />

Notes<br />

Ordering<br />

<strong>Circuit</strong>-<strong>breakers</strong> UL/CSA, IEC, electronic releases<br />

Switches conform <strong>to</strong> UL/CSA as well as the IEC regulations.<br />

IEC switching performance values are contained on the rating plate.<br />

UL 489, CSA-C22.2-5.1, IEC/EN 60947-2<br />

Use in mo<strong>to</strong>r control circuits only in conjunction with a suitable contac<strong>to</strong>r.<br />

Adjustable overload releases I r<br />

• 0.5 – 1 x I n<br />

R.m.s. value measurement and “thermal memory”<br />

Adjustable time delay setting <strong>to</strong> overcome current peaks t r<br />

• 2 – 20 s with 6 x I r (ex-works 10 s)<br />

Adjustable delayed short-circuit releases I sd<br />

• 2 – 10 x I r (ex-works 6 x I r )<br />

– NZM...3-VE600-NA: 1.5 – 7 x I r (ex-works 6 x I r )<br />

Adjustable delay time t sd<br />

• Steps: 0, 20, 60, 100, 200, 300, 500, 750, 1000 ms (ex-works 0 ms)<br />

Adjustable non-delayed short-circuit releases I i<br />

• NZM2: fixed 12 x I n<br />

• NZM...3-VE250/400-NA: 2 – 11 x I n (ex-works 11 x I n )<br />

• NZM...3-VE600-NA: 2 – 8 x I n (ex-works 8 x I n )<br />

• NZM...4-VE...-NA: 2 – 12 x I n (ex-works 12 x I n )<br />

i 2 t constant function<br />

• NZM2 fixed OFF<br />

• NZM3, NZM4 switched (ex-works OFF)<br />

NZM…3, NZM…4<br />

10/41<br />

<strong>Circuit</strong>-<strong>breakers</strong>, switch-disconnec<strong>to</strong>rs,<br />

UL/CSA IEC<br />

1) Normal switching capacity for NZMN2-…-NA: 35 kA/480 V<br />

2) Normal switching capacity for NZMN2-…-NA: 25 kA/600 V<br />

3) High switching capacity for NZMH4-...-NA: 125 kA/240 V<br />

4) High switching capacity for NZMH4-...-NA: 85 kA/480 V<br />

Notes Notes for terminals a 10/55<br />

Rated current =<br />

rated uninterr<strong>up</strong>ted<br />

current<br />

I n = I u<br />

A<br />

Setting range<br />

Short-circuit releases<br />

I i<br />

A<br />

I<br />

Normal switching<br />

capacity<br />

240 V 60 Hz<br />

480 V 60 Hz<br />

600 V 60 Hz<br />

Part no.<br />

Article no.<br />

Price<br />

see price list<br />

Std. pack<br />

Notes<br />

Short-circuit protection<br />

Mo<strong>to</strong>r protection in conjunction with contac<strong>to</strong>r and overload relay<br />

• With short-circuit release<br />

• Without overload release<br />

3 pole<br />

Terminal screws standard, terminals as accessories<br />

90 180…1260 NZMN2-SE90-CNA<br />

271160<br />

140 280…1960 NZMN2-SE140-CNA<br />

271161<br />

220 440…3080 NZMN2-SE220-CNA<br />

271162<br />

220 440…3080 NZMN3-SE220-CNA<br />

269341<br />

350 700…4900 NZMN3-SE350-CNA<br />

269342<br />

450 900…6300 NZMN3-SE450-CNA<br />

284465<br />

1 off Switches conform <strong>to</strong> UL/CSA as well as the IEC regulations.<br />

IEC switching performance values are contained on the rating plate.<br />

UL 489, CSA-C22.2-5.1, IEC/EN 60947-2and IEC/EN 60947-4<br />

Adjustable short-circuit releases I i<br />

• 2 – 14 x I n (ex-works 12 x I n )<br />

Without overload release I r<br />

CNA: The device has components approved <strong>to</strong> UL, the conditions of approval must be observed during use. I.e. the device must be combined with a<br />

suitable contac<strong>to</strong>r and overload relay. A switching capacity is stated for the complete mo<strong>to</strong>r-starter combination.<br />

The device is approved as a CSA approved single device.<br />