Circuit-breakers NZM1, 2, 3, 4 up to 2000 A - Moeller Electric Parts
Circuit-breakers NZM1, 2, 3, 4 up to 2000 A - Moeller Electric Parts
Circuit-breakers NZM1, 2, 3, 4 up to 2000 A - Moeller Electric Parts
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
<strong>Circuit</strong>-<strong>breakers</strong>, switch-disconnec<strong>to</strong>rs,<br />
UL/CSA IEC<br />
10/30<br />
Ordering<br />
<strong>Circuit</strong>-breaker UL/CSA, IEC, thermomagnetic release<br />
NZM...1, NZM...2<br />
Rated current = rated<br />
uninterr<strong>up</strong>ted current<br />
Setting range<br />
Overload releases<br />
I n = I u I r I i<br />
A A A<br />
I<br />
Protection of systems and cables<br />
3 pole<br />
Fixed overload releases<br />
Terminal screws standard, terminals as accessories<br />
Short-circuit releases<br />
<strong>Moeller</strong> HPL0211-2007/2008<br />
http://catalog.moeller.net<br />
http://catalog.moeller.net<br />
Basic switching capacity<br />
35 kA 240 V 60 Hz<br />
25 kA 480 V 60 Hz 1)<br />
18 kA 600 V 60 Hz 2) Normal switching capacity<br />
85 kA 240 V 60 Hz<br />
35 kA 480 V 60 Hz 1)<br />
25 kA 600 V 60 Hz 2) High switching capacity<br />
150 kA 240 V 60 Hz<br />
100 kA 480 V 60 Hz<br />
50 kA 600 V 60 Hz<br />
Part no.<br />
Article no.<br />
Price<br />
see price list<br />
Part no.<br />
Article no.<br />
Price<br />
see price list<br />
Part no.<br />
Article no.<br />
Price<br />
see price list<br />
<strong>Moeller</strong> HPL0211-2007/2008<br />
Std. pack<br />
Ordering<br />
<strong>Circuit</strong>-breaker UL/CSA, IEC, thermomagnetic release<br />
Notes<br />
NZM...1, NZM...2<br />
10/31<br />
<strong>Circuit</strong>-<strong>breakers</strong>, switch-disconnec<strong>to</strong>rs,<br />
UL/CSA IEC<br />
125 125 750…1250 NZMB2-AF125-NA<br />
269166<br />
150 150 960…1600 NZMB2-AF150-NA<br />
269167<br />
175 175 1200…<strong>2000</strong> NZMB2-AF175-NA<br />
269168<br />
200 200 1200…<strong>2000</strong> NZMB2-AF200-NA<br />
269169<br />
225 225 1500…2500 NZMB2-AF225-NA<br />
271089<br />
250 250 1500…2500 NZMB2-AF250-NA<br />
271100<br />
NZMN2-AF125-NA<br />
269184<br />
NZMN2-AF150-NA<br />
269185<br />
NZMN2-AF175-NA<br />
269186<br />
NZMN2-AF200-NA<br />
269187<br />
NZMN2-AF225-NA<br />
271101<br />
NZMN2-AF250-NA<br />
271102<br />
NZMH2-AF125-NA<br />
269202<br />
NZMH2-AF150-NA<br />
269203<br />
NZMH2-AF175-NA<br />
269204<br />
NZMH2-AF200-NA<br />
269205<br />
NZMH2-AF225-NA<br />
271103<br />
NZMH2-AF250-NA<br />
271104<br />
1 off Switches conform <strong>to</strong> UL/CSA as well as the IEC regulations.<br />
IEC switching performance values are contained on the rating plate.<br />
UL 489, CSA-C22.2-5.1, IEC/EN 60947-2<br />
Fixed overload releases I r<br />
Adjustable short-circuit releases I i<br />
• ca. 6 – 10 x I n (ex-works 6 x I n )<br />
– NZM...-AF35/40-NA: approx. 8 – 10 x I n<br />
Fixed short-circuit releases I i<br />
• 350 A at I n = 15 – 30 A<br />
2) Basic switching capacity 18 kA 600 V and Normal switching capacity 25 kA 600 V for NZM2.<br />
Adjustable overload releases<br />
Terminals standard, terminal screws as accessories<br />
20 15…20 350 NZMB1-A20-NA<br />
281559<br />
25 20…25 350 NZMB1-A25-NA<br />
281560<br />
32 25…32 350 NZMB1-A32-NA<br />
281561<br />
40 32…40 320…400 NZMB1-A40-NA<br />
272253<br />
50 40…50 300…500 NZMB1-A50-NA<br />
272254<br />
63 50…63 380…630 NZMB1-A63-NA<br />
272255<br />
80 63…80 480…800 NZMB1-A80-NA<br />
272256<br />
100 80…100 600…1000 NZMB1-A100-NA<br />
272258<br />
125 100…125 750…1250 NZMB1-A125-NA<br />
281562<br />
NZMN1-A20-NA<br />
281570<br />
NZMN1-A25-NA<br />
281571<br />
NZMN1-A32-NA<br />
281572<br />
NZMN1-A40-NA<br />
274237<br />
NZMN1-A50-NA<br />
274239<br />
NZMN1-A63-NA<br />
274240<br />
NZMN1-A80-NA<br />
274241<br />
NZMN1-A100-NA<br />
274242<br />
NZMN1-A125-NA<br />
281573<br />
1 off Switches conform <strong>to</strong> UL/CSA as well as the IEC regulations.<br />
IEC switching performance values are contained on the rating plate.<br />
UL 489, CSA-C22.2-5.1, IEC/EN 60947-2<br />
Adjustable overload releases I r<br />
• 0.8 – 1 x I n (ex-works 0.8 x I n )<br />
Adjustable short-circuit releases I i<br />
• 6 – 10 x I n (ex-works 6 x I n )<br />
– NZM...-A40-NA: 8 – 10 x I n<br />
Fixed short-circuit releases I i<br />
• 350 A at I n = 20 – 32 A<br />
1) Basic switching capacity 25 kA 480 V and normal switching capacity 35 kA 480 V for NZM…1-…-NA:<br />
480 Y/277 V AC from 60 A.<br />
Adjustable overload releases<br />
Terminal screws standard, terminals as accessories<br />
Notes<br />
20 15…20 350 NZMB2-A20-NA<br />
269206<br />
25 20…25 350 NZMB2-A25-NA<br />
269207<br />
32 25…32 350 NZMB2-A32-NA<br />
269208<br />
40 32…40 320…400 NZMB2-A40-NA<br />
269209<br />
50 40…50 300…500 NZMB2-A50-NA<br />
269210<br />
63 50…63 380…630 NZMB2-A63-NA<br />
269211<br />
80 63…80 480…800 NZMB2-A80-NA<br />
269212<br />
100 80…100 600…1000 NZMB2-A100-NA<br />
269213<br />
125 100…125 750…1250 NZMB2-A125-NA<br />
269214<br />
160 125…160 960…1600 NZMB2-A160-NA<br />
269215<br />
200 160…200 1200…<strong>2000</strong> NZMB2-A200-NA<br />
269216<br />
250 200…250 1500…2500 NZMB2-A250-NA<br />
271105<br />
NZMN2-A20-NA<br />
269217<br />
NZMN2-A25-NA<br />
269218<br />
NZMN2-A32-NA<br />
269219<br />
NZMN2-A40-NA<br />
269220<br />
NZMN2-A50-NA<br />
269221<br />
NZMN2-A63-NA<br />
269222<br />
NZMN2-A80-NA<br />
269223<br />
NZMN2-A100-NA<br />
269224<br />
NZMN2-A125-NA<br />
269225<br />
NZMN2-A160-NA<br />
269226<br />
NZMN2-A200-NA<br />
269227<br />
NZMN2-A250-NA<br />
271106<br />
NZMH2-A20-NA<br />
269228<br />
NZMH2-A25-NA<br />
269229<br />
NZMH2-A32-NA<br />
269230<br />
NZMH2-A40-NA<br />
269231<br />
NZMH2-A50-NA<br />
269232<br />
NZMH2-A63-NA<br />
269233<br />
NZMH2-A80-NA<br />
269234<br />
NZMH2-A100-NA<br />
269235<br />
NZMH2-A125-NA<br />
269236<br />
NZMH2-A160-NA<br />
269237<br />
NZMH2-A200-NA<br />
269238<br />
NZMH2-A250-NA<br />
271107<br />
1 off Switches conform <strong>to</strong> UL/CSA as well as the IEC regulations.<br />
IEC switching performance values are contained on the rating plate.<br />
UL 489, CSA-C22.2-5.1, IEC/EN 60947-2<br />
Adjustable overload releases I r<br />
• 0.8 – 1 x I n (ex-works 0.8 x I n )<br />
Adjustable short-circuit releases I i<br />
• 6 – 10 x I n (ex-works 6 x I n )<br />
– NZM...-A40-NA: 8 – 10 x I n<br />
Fixed short-circuit releases I i<br />
• 350 A at I n = 20 – 32 A<br />
For <strong>Moeller</strong> <strong>Electric</strong> Sales and S<strong>up</strong>port call KMparts.com (866) 595-9616<br />
2) Basic switching capacity 18 kA 600 V and normal switching capacity 25 kA 600 V for NZM2.