For <strong>Moeller</strong> <strong>Electric</strong> Sales and S<strong>up</strong>port call KMparts.com (866) 595-9616<br />

http://catalog.moeller.net<br />

<strong>Moeller</strong> HPL0211-2007/2008<br />

Technical data<br />

Residual-current relay<br />

PFR-003 PFR-03 PFR-5<br />

<strong>Electric</strong>al<br />

Standards IEC/EN 60947-2, IEC 755, IEC 1008, IEC 1009<br />

Sensitivity<br />

Pulse current sensitive, type A<br />

Rated control voltage U s V AC 230 g20 % (50/60 Hz)<br />

Mo<strong>to</strong>r rating P e W 3 3 3<br />

Rated fault currents I Dn mA 0.03 0.3 0.03, 0.1, 0.3, 0.5, 1, 3, 5<br />

Delay time v t s 0.02 (non-delayed) 0.02 (non-delayed) 0.02, 0.1, 0.3, 0.5, 1, 3, 5<br />

Relay contacts<br />

1 integrated changeover<br />

contact<br />

1 integrated changeover<br />

contact<br />

1 integrated changeover<br />

contact<br />

Rated voltage of the relay contact V AC/DC 250/100 250/100 250/100<br />

Rated current of the relay contact A 6 6 6<br />

Fault current warning Hz – – 0.5 = 25% – 50% I Dn<br />

1 = 50% – 75% I Dn<br />

2 = 75% – 100% I Dn<br />

Mechanical<br />

Standard front dimension mm 45 45 45<br />

Device height mm 85 85 85<br />

Device width mm 45 45 45<br />

Mounting Snap fixing, <strong>to</strong>p-hat rail DIN 46277, IEC/EN 60715<br />

Terminals <strong>to</strong>p and bot<strong>to</strong>m<br />

Box terminals<br />

Terminal protection Finger/back-of-hand proof <strong>to</strong> BGV A2, VDE 106 part 100<br />

Terminal capacities mm 2 2 x 0.75 – 2.5 solid, 2 x 0.75 – 1.5 flexible/with ferrules<br />

Sealability – yes<br />

PFR-…<br />

10/143<br />

<strong>Circuit</strong>-<strong>breakers</strong>, switch-disconnec<strong>to</strong>rs