PULMONARY MEDICINE SERVICE NOVEMBER 29, 2011<br />
Sleep Study Room (OPPF6)<br />
Room Data Sheet<br />
ARCHITECTURAL<br />
HEATING, VENTILATING AND AIR CONDITIONING<br />
Ceiling: AT Dry Bulb Temp Cooling: 75˚F (24˚C)<br />
Ceiling Height: 9’-0” Dry Bulb Temp Heating: 70˚F (21˚C)<br />
Wall Finish: GWB *1 Minimum % Outside Air: 2<br />
Base: PRB 100% Exhaust Air:<br />
Floor Finish: SVT Noise Criteria: NC 40<br />
Door: 19/20 X, CR Steam:<br />
Hardware: SH-3 Relative Humidity/Cooling: 60%<br />
Relative Humidity/Heating: 20%<br />
Minimum Air Changes/Hr.: 4<br />
Notes: Room Pressure: Neutral (0)<br />
*1. See <strong>Design</strong> and <strong>Construction</strong> Procedures PG-18-3,<br />
“Noise Transmission Control”<br />
AC Load Lights:<br />
As Required<br />
AC Load Equipment:<br />
As Required<br />
POWER Number <strong>of</strong> People: 1<br />
General: As Shown Special Equipment:<br />
Special:<br />
Emergency:<br />
PLUMBING AND MEDICAL GASES<br />
Notes: Cold Water: Yes<br />
Hot Water:<br />
Yes<br />
Domestic Water (HWH):<br />
Yes<br />
COMMUNICATIONS<br />
Laboratory Air:<br />
Patient Monitor: Laboratory Vacuum:<br />
Nurse Call: Yes Sanitary/Vent: Yes<br />
Security/Duress: Medical Air:<br />
CCTV: Yes Medical Vacuum:<br />
Telephone: Yes Oxygen:<br />
Pub. Address:<br />
Nitrogen Oxide:<br />
Radio:<br />
Nitrogen:<br />
Data: Yes Anesthesia Evac:<br />
Panic Call: Sprinkler: Yes<br />
Battery Operated Clock: Yes Tempered Water:<br />
Intercom: Yes Water Control:<br />
Staff/Duty Station:<br />
LIGHTING<br />
General:<br />
1. One (1) <strong>of</strong> 2’x4’ (600mm x 1200mm) Fluorescent<br />
Light Fixture, Acrylic, Prismatic Lens with F32T8<br />
Lamps, 3500˚K, CRI=70 (minimum)<br />
2. Four (4) Down Lights, Dimmable<br />
3. One (1) Table Lamp<br />
4. Provide Ballasts Per Fixture for Desired Switching<br />
Configuration<br />
5. Lighting Level: 30fc, dimmable to 0<br />
SPECIAL EQUIPMENT<br />
Polysomnography<br />
DESIGN STANDARDS<br />
SECTION 4 - PAGE 85