PULMONARY MEDICINE SERVICE NOVEMBER 29, 2011 DESIGN STANDARDS SECTION 4 - PAGE 74

PULMONARY MEDICINE SERVICE NOVEMBER 29, 2011 Procedure Room, Bronchoscopy (TRPE2) Room Data Sheet ARCHITECTURAL HEATING, VENTILATING AND AIR CONDITIONING Ceiling: GWB(SC) Dry Bulb Temp Cooling: 75˚F (24˚C) Ceiling Height: 9’-0” Dry Bulb Temp Heating: 70˚F (21˚C) Wall Finish: GWB(SC) *1 Minimum % Outside Air: Base: WSF 100% Exhaust Air: Yes Floor Finish: WSF Noise Criteria: NC 35 Door: 19/20 X-T Steam: Hardware: 4P Relative Humidity/Cooling: 60% Relative Humidity/Heating: 20% Minimum Air Changes/Hr.: 12 Notes: Room Pressure: Negative (-) *1. See Design and Construction Procedures PG-18-3, AC Load Lights: As Required “Noise Transmission Control” AC Load Equipment: As Required POWER Number of People: 6 General: As Shown Special Equipment: Special: As Shown Emergency: PLUMBING AND MEDICAL GASES Notes: Dedicated Power Required Cold Water: Yes Hot Water: Yes Domestic Water (HWH): Yes COMMUNICATIONS Laboratory Air: Patient Monitor: Yes Laboratory Vacuum: Nurse Call: Yes Sanitary/Vent: Yes Security/Duress: Medical Air: 1 Outlet CCTV: Medical Vacuum: 1 Outlet Telephone: Yes Oxygen: 1 Outlet Pub. Address: Nitrogen Oxide: 1 Outlet Radio: Nitrogen: As Required Data: Yes Anesthesia Evac: 1 Outlet Panic Call: Sprinkler: Yes Battery Operated Clock: Yes Tempered Water: Intercom: Water Control: Infrared Staff/Duty Station: LIGHTING General: 1. Four (4) of 2’x4’ (600mm x 1200mm) Fluorescent Light Fixture, Acrylic, Prismatic Lens with F32T8 Lamps, 3500˚K, CRI=70 (minimum) 2. One (1) of 2’x2’ (600mm x 600mm) Fluorescent Light Fixture, Acrylic, Prismatic Lens with F32T8 Lamps, 3500˚K, CRI=70 (minimum) 2. Provide Ballasts Per Fixture for Desired Switching Configuration 3. Lighting Level: 50fc / 10fc 4. Boom Mounted Surgical Lamp 5. Four (4) Downlights, Dimmable SPECIAL EQUIPMENT None DESIGN STANDARDS SECTION 4 - PAGE 75

PULMONARY MEDICINE SERVICE NOVEMBER 29, 2011<br />

Procedure Room, Bronchoscopy (TRPE2)<br />

Room Data Sheet<br />

ARCHITECTURAL<br />

HEATING, VENTILATING AND AIR CONDITIONING<br />

Ceiling: GWB(SC) Dry Bulb Temp Cooling: 75˚F (24˚C)<br />

Ceiling Height: 9’-0” Dry Bulb Temp Heating: 70˚F (21˚C)<br />

Wall Finish: GWB(SC) *1 Minimum % Outside Air:<br />

Base: WSF 100% Exhaust Air: Yes<br />

Floor Finish: WSF Noise Criteria: NC 35<br />

Door: 19/20 X-T Steam:<br />

Hardware: 4P Relative Humidity/Cooling: 60%<br />

Relative Humidity/Heating: 20%<br />

Minimum Air Changes/Hr.: 12<br />

Notes: Room Pressure: Negative (-)<br />

*1. See <strong>Design</strong> and <strong>Construction</strong> Procedures PG-18-3, AC Load Lights:<br />

As Required<br />

“Noise Transmission Control”<br />

AC Load Equipment:<br />

As Required<br />

POWER Number <strong>of</strong> People: 6<br />

General: As Shown Special Equipment:<br />

Special:<br />

As Shown<br />

Emergency:<br />

PLUMBING AND MEDICAL GASES<br />

Notes: Dedicated Power Required Cold Water: Yes<br />

Hot Water:<br />

Yes<br />

Domestic Water (HWH):<br />

Yes<br />

COMMUNICATIONS<br />

Laboratory Air:<br />

Patient Monitor: Yes Laboratory Vacuum:<br />

Nurse Call: Yes Sanitary/Vent: Yes<br />

Security/Duress: Medical Air: 1 Outlet<br />

CCTV: Medical Vacuum: 1 Outlet<br />

Telephone: Yes Oxygen: 1 Outlet<br />

Pub. Address: Nitrogen Oxide: 1 Outlet<br />

Radio: Nitrogen: As Required<br />

Data: Yes Anesthesia Evac: 1 Outlet<br />

Panic Call: Sprinkler: Yes<br />

Battery Operated Clock: Yes Tempered Water:<br />

Intercom: Water Control: Infrared<br />

Staff/Duty Station:<br />

LIGHTING<br />

General:<br />

1. Four (4) <strong>of</strong> 2’x4’ (600mm x 1200mm) Fluorescent<br />

Light Fixture, Acrylic, Prismatic Lens with F32T8<br />

Lamps, 3500˚K, CRI=70 (minimum)<br />

2. One (1) <strong>of</strong> 2’x2’ (600mm x 600mm) Fluorescent Light<br />

Fixture, Acrylic, Prismatic Lens with F32T8 Lamps,<br />

3500˚K, CRI=70 (minimum)<br />

2. Provide Ballasts Per Fixture for Desired Switching<br />

Configuration<br />

3. Lighting Level: 50fc / 10fc<br />

4. Boom Mounted Surgical Lamp<br />

5. Four (4) Downlights, Dimmable<br />

SPECIAL EQUIPMENT<br />

None<br />

DESIGN STANDARDS<br />

SECTION 4 - PAGE 75