PULMONARY MEDICINE SERVICE NOVEMBER 29, 2011<br />

Testing Lab, Extended <strong>Pulmonary</strong> Function (OPPF2)<br />

Room Data Sheet<br />

ARCHITECTURAL<br />

HEATING, VENTILATING AND AIR CONDITIONING<br />

Ceiling: AT Dry Bulb Temp Cooling: 75˚F (24˚C)<br />

Ceiling Height: 9’-0” Dry Bulb Temp Heating: 70˚F (21˚C)<br />

Wall Finish: GWB Minimum % Outside Air: 2<br />

Base: RB 100% Exhaust Air:<br />

Floor Finish: SVT Noise Criteria: NC 35<br />

Door: 1/2 X-T Steam:<br />

Hardware: 4G Relative Humidity/Cooling: 60%<br />

Relative Humidity/Heating: 20%<br />

Minimum Air Changes/Hr.: 8<br />

Notes: Room Pressure: Neutral (0)<br />

AC Load Lights:<br />

As Required<br />

AC Load Equipment:<br />

As Required<br />

POWER Number <strong>of</strong> People: 3<br />

General: As Shown Special Equipment:<br />

Special:<br />

Special Voltage as Required<br />

Emergency:<br />

PLUMBING AND MEDICAL GASES<br />

Notes: Dedicated Power Required Cold Water: Yes<br />

Hot Water:<br />

Yes<br />

Domestic Water (HWH):<br />

Yes<br />

COMMUNICATIONS<br />

Laboratory Air:<br />

Patient Monitor: Laboratory Vacuum:<br />

Nurse Call: Yes Sanitary/Vent: Yes<br />

Security/Duress:<br />

Medical Air:<br />

CCTV:<br />

Medical Vacuum:<br />

Telephone: Yes Oxygen:<br />

Pub. Address:<br />

Nitrogen Oxide:<br />

Radio:<br />

Nitrogen:<br />

Data: Yes Anesthesia Evac:<br />

Panic Call: Sprinkler: Yes<br />

Battery Operated Clock: Yes Tempered Water:<br />

Intercom: Water Control: Infrared<br />

Staff/Duty Station:<br />

LIGHTING<br />

General:<br />

1. Two (2) <strong>of</strong> 2’x4’ (600mm x 1200mm) Fluorescent<br />

Light Fixture, Acrylic, Prismatic Lens with F32T8<br />

Lamps, 3500˚K, CRI=70 (minimum)<br />

2. Provide Ballasts Per Fixture for Desired Switching<br />

Configuration<br />

3. Lighting Level: 50fc<br />

4. Under Cabinet Light<br />

5. Ceiling Mounted Occupancy Sensors<br />

SPECIAL EQUIPMENT<br />

None<br />

DESIGN STANDARDS<br />

SECTION 4 - PAGE 55