Technical d<strong>at</strong>a<br />

Auxiliary contacts<br />

5/125<br />

<strong>Moeller</strong> HPL0211-2004/2005<br />

Auxiliary contacts<br />

DIL00(A)(B)M-01,<br />

DIL00(A)(B)M-10<br />

...DILM DILM820-XHI... ...SDILM DILP800-XHI<br />

Auxiliary contacts<br />

Interlocked opposing contacts to ZH1/457<br />

within an auxiliary contact module<br />

Yes Yes Yes Yes –<br />

Break contact (not l<strong>at</strong>e-break contact) suitable as a mirror contact<br />

(to IEC/EN 60947-4-1 Annex F)<br />

DIL00(A)(B)M DIL00M –<br />

DIL2AM<br />

DIL0M –<br />

DIL3AM85<br />

DILM185 –<br />

DILM1000<br />

DIL0M –<br />

DIL2AM<br />

R<strong>at</strong>ed impulse withstand voltage U imp V AC 6000 6000 6000 6000 6000<br />

Overvoltage c<strong>at</strong>egory/pollution degree III/3 III/3 III/3 III/3 III/3<br />

–<br />

Contactors<br />

R<strong>at</strong>ed insul<strong>at</strong>ion voltage U i V AC 690 690 690 690 690<br />

R<strong>at</strong>ed oper<strong>at</strong>ional voltage U e V AC 500 500 500 500 690<br />

Safe isol<strong>at</strong>ion to VDE 0106 Part 101 and Part 101/A1<br />

between coil and auxiliary contacts V AC 440 440 440 440 1000<br />

Between the auxiliary contacts V AC 440 440 440 440 400<br />

R<strong>at</strong>ed oper<strong>at</strong>ional current<br />

AC–15<br />

230 V I e A 6 6 6 6 6<br />

380/415 V I e A 4 4 4 4 4<br />

500 V I e A 1.5 1.5 1.5 1.5 1<br />

DC-13 L/R F 15 ms 1)<br />

24 V I e A 10 10 10 10 6<br />

60 V I e A 6 6 6 6 4<br />

110 V I e A 3 3 3 3 1.8<br />

220 V I e A 1 1 1 1 0.6<br />

Conventional thermal free air current I th A 16 16 10 16 10<br />

Control circuit reliability (<strong>at</strong> U e = 24 V DC, U min Failure r<strong>at</strong>e l