5/122<br />
Technical d<strong>at</strong>a<br />
DIL contactors<br />
Technical d<strong>at</strong>a<br />
DIL contactors<br />
5/123<br />
<strong>Moeller</strong> HPL0211-2004/2005<br />
<strong>Moeller</strong> HPL0211-2004/2005<br />
Contactors<br />
Contactors<br />
DILM185 DILM225 DILM300 DILM500 DILM580 DILM750 DILM1000 DILH1400<br />
DILM250 DILM400 DILM650 DILM820 DILH2000<br />
Contactors<br />
Magnet systems<br />
Duty factor % DF 100 100 100 100 100 100 100 100<br />
Switching times <strong>at</strong> 100 %<br />
U c (approxim<strong>at</strong>e values)<br />
Reaction in threshold and<br />
transition range<br />
(<strong>com</strong>fort series)<br />
Main contacts<br />
Sealing st<strong>at</strong>e<br />
DILM... <strong>com</strong>fort<br />
series<br />
DILM...-S<br />
standard series<br />
Voltage<br />
interruptions<br />
Closing delay ms < 100 < 100 < 80 < 80 < 70 < 70 < 70 < 70<br />
Opening delay ms < 80 < 80 < 80 < 80 < 70 < 70 < 70 < 40<br />
Closing delay ms < 50 < 50 < 50 < 50 – – – –<br />
Opening delay ms < 40 < 40 < 40 < 40 – – – –<br />
(0 – 0.2 x U c min ) F 10 ms Time is bridged successfully Time is bridged successfully<br />
(0 – 0.2 x U c min ) > 10 ms Drop-out of the contactor Drop-out of the contactor<br />
Voltage dips (0.2 – 0.6 x U c min ) F 12 ms Time is bridged successfully Time is bridged successfully<br />
(0.2 – 0.6 x U c min ) > 12 ms Drop-out of the contactor Drop-out of the contactor<br />
(0.6 – 0.7 x U c min ) Contactor remains switched on Contactor remains switched on<br />
Excess voltage (1.15 – 1.3 x U c max ) Contactor remains switched on Contactor remains switched on<br />
(> 1.3 x U c max ) F 3 s Contactor remains switched on Contactor remains switched on<br />
(> 1.3 x U c max ) > 3 s Drop-out of the contactor Drop-out of the contactor<br />
Pick-up phase (0 – 0.7 x U c min ) Contactor does not switch on Contactor does not switch on<br />
(0.7 x U c min – 1.15 x U c max ) Contactor switches on with certainty Contactor switches on with certainty<br />
(> 1.15 x U c max ) Contactor switches on with certainty Contactor switches on with certainty<br />
Permissible contact resistance (of the external <strong>com</strong>mand device with actu<strong>at</strong>ion of A11) mO F500 F500 F500 F500 F500 F500 F500 F500<br />
Contactors<br />
Permissible residual current (with actu<strong>at</strong>ion of A11 by the electronics with 0 signal) mA F1 F1 F1 F1 F1 F1 F1 F1<br />
SPS signal level (A3 - A4) to IEC/EN 61131-2 (type 2) High V 15 15 15 15 15 15 15 15<br />
Low V 5 5 5 5 5 5 5 5<br />
Electromagnetic <strong>com</strong>p<strong>at</strong>ibility (EMC)<br />
Electromagnetic <strong>com</strong>p<strong>at</strong>ibility<br />
This product is designed for oper<strong>at</strong>ion in industrial<br />
environments (environment 2). Usage in domestic areas<br />
(environment 1) can cause radio frequency interference (RFI)<br />
so th<strong>at</strong> additional interference so noise suppression measures<br />
must be provided.<br />
This product is designed for oper<strong>at</strong>ion in industrial environments<br />
(environment 2). Usage in domestic areas<br />
(environment 1) can cause radio frequency interference (RFI)<br />
so th<strong>at</strong> additional interference so noise suppression measures must be provided.<br />