5/116<br />

Technical d<strong>at</strong>a<br />

DIL contactors<br />

Technical d<strong>at</strong>a<br />

DIL contactors<br />

5/117<br />

<strong>Moeller</strong> HPL0211-2004/2005<br />

<strong>Moeller</strong> HPL0211-2004/2005<br />

Contactors<br />

Contactors<br />

DILM185 DILM225 DILM300 DILM500 DILM580 DILM750 DILM1000 DILH1400<br />

DILM250 DILM400 DILM650 DILM820 DILH2000<br />

Contactors<br />

General<br />

Standards IEC/EN 60947, VDE 0660, UL, CSA IEC/EN 60947, VDE 0660, UL, CSA<br />

Lifespan, mechanical AC oper<strong>at</strong>ed Oper<strong>at</strong>ions x 10 6 10 10 7 7 5 5 5 5<br />

DC oper<strong>at</strong>ed Oper<strong>at</strong>ions x 10 6 10 10 7 7 5 5 5 5<br />

Oper<strong>at</strong>ing frequency, mechanical AC oper<strong>at</strong>ed Oper<strong>at</strong>ions/h 3000 3000 2000 2000 1000 1000 1000 1000<br />

DC oper<strong>at</strong>ed Oper<strong>at</strong>ions/h 3000 3000 2000 2000 1000 1000 1000 1000<br />

Maximum oper<strong>at</strong>ing frequency <strong>Electric</strong>al (contactor without overload relay) Page 5/96 Page 05/070<br />

Clim<strong>at</strong>ic proofing Damp he<strong>at</strong>, constant, to IEC 60068-2-78/<br />

Damp he<strong>at</strong>, cyclic, to IEC 60068-2-30<br />

Damp he<strong>at</strong>, constant, to IEC 60068-2-78/<br />

Damp he<strong>at</strong>, cyclic, to IEC 60068-2-30<br />

Ambient temper<strong>at</strong>ure Open °C -25/60 -25/60 -25/60 -25/60 -25/60 -25/60 -25/60 -25/60<br />

Enclosed °C -25/40 -25/40 -25/40 -25/40 -25/40 -25/40 -25/40 -25/40<br />

Storage °C -40/80 -40/80 -40/80 -40/80 -40/80 -40/80 -40/80 -40/80<br />

Mounting position<br />

30˚ 30˚<br />

30˚ 30˚<br />

Contactors<br />

90°<br />

90°<br />

90°<br />

90°<br />

180°<br />

Mechanical shock resistance (IEC/EN 60068-2-27)<br />

Half-sinusoidal shock 10 ms Main contacts Make<br />

g 10 10 10 10 10 10 10 10<br />

contact<br />

Auxiliary contacts Make<br />

g 10 10 10 10 10 10 10 10<br />

contact<br />

Break<br />

g 8 8 8 8 8 8 8 8<br />

contact<br />

Degree of protection IP00 IP00 IP00 IP00 IP00 IP00 IP00 IP00<br />

Protection against direct contact when actu<strong>at</strong>ed from front (IEC 536)<br />

finger and back-of-hand proof with terminal shroud or<br />

terminal block<br />

finger and back-of-hand proof with terminal shroud or terminal block<br />

Weight kg 6.5 6.5 8 8 15 15 15 15 32<br />

Main cable cross-section Flexible with cable lug mm 2 35 – 95 50 – 240 50 – 240 50 – 240 50 – 240 50 – 240 50 – 240 –<br />

Stranded with cable lug mm 2 50 – 120 70 – 240 70 – 240 70 – 240 70 – 240 70 – 240 70 – 240 –<br />

Solid or stranded AWG 1/0 – 250 MCM 2/0 – 500 MCM 2/0 – 500 MCM 2/0 – 500 MCM 2/0 – 500 MCM 2/0 – 500 MCM 2/0 – 500 MCM –<br />

Fl<strong>at</strong> conductor mm Fixing with fl<strong>at</strong> cable terminal or cable terminal blocks<br />

See terminal capacity for cable terminal blocks<br />

Fixing with fl<strong>at</strong> cable terminal or cable terminal blocks<br />

See terminal capacity for cable terminal blocks<br />

Busbar Width mm 20 20 25 25 30 50 60 60 80 100<br />

Main cable connection screw/bolt M10 M10 M10 M10 M10 M12 M12 M12<br />

Tightening torque Nm 24 24 24 24 24 35 35 35<br />

Control circuit cable<br />

cross-sections<br />

Solid mm 2 1 x (0.75 – 2.5)<br />

2 x (0.75 – 2.5)<br />

Flexible with ferrule mm 2 1 x (0.75 – 2.5)<br />

2 x (0.75 – 2.5)<br />

1 x (0.75 – 2.5)<br />

2 x (0.75 – 2.5)<br />

1 x (0.75 – 2.5)<br />

2 x (0.75 – 2.5)<br />

1 x (0.75 – 2.5)<br />

2 x (0.75 – 2.5)<br />

1 x (0.75 – 2.5)<br />

2 x (0.75 – 2.5)<br />

1 x (0.75 – 2.5)<br />

2 x (0.75 – 2.5)<br />

1 x (0.75 – 2.5)<br />

2 x (0.75 – 2.5)<br />

1 x (0.75 – 2.5)<br />

2 x (0.75 – 2.5)<br />

1 x (0.75 – 2.5)<br />

2 x (0.75 – 2.5)<br />

1 x (0.75 – 2.5)<br />

2 x (0.75 – 2.5)<br />

1 x (0.75 – 2.5)<br />

2 x (0.75 – 2.5)<br />

1 x (0.75 – 2.5)<br />

2 x (0.75 – 2.5)<br />

1 x (0.75 – 2.5)<br />

2 x (0.75 – 2.5)<br />

Solid or stranded AWG 2 x (18 – 12) 2 x (18 – 12) 2 x (18 – 12) 2 x (18 – 12) 2 x (18 – 12) 2 x (18 – 12) 2 x (18 – 12) 2 x (18 – 12)<br />

Control circuit cable connection screw/bolt M3.5 M3.5 M3.5 M3.5 M3.5 M3.5 M3.5 M3.5<br />

Tightening torque Nm 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2<br />

Tools Main cable Wrench mm 16 16 16 16 16 18 18 18<br />

1 x (0.75 – 2.5)<br />

2 x (0.75 – 2.5)<br />

1 x (0.75 – 2.5)<br />

2 x (0.75 – 2.5)<br />

Control circuit<br />

cable<br />

Pozidriv screwdriver Size 2 2 2 2 2 2 2 2 2 2 2 2 2<br />