Technical d<strong>at</strong>a<br />

DIL contactors<br />

5/115<br />

<strong>Moeller</strong> HPL0211-2004/2005<br />

DIL00M DIL0M DIL1M DIL2M DIL3M80 DIL4M115<br />

DIL00AM DIL0AM DIL1AM DIL2AM DIL3AM85 DIL4AM145<br />

DIL00BM<br />

Magnet systems<br />

Pick-up and drop-out values<br />

AC oper<strong>at</strong>ed Pick-up x U c 0.8 – 1.1 0.8 – 1.1 0.8 – 1.1 0.8 – 1.1 0.8 – 1.1 0.8 – 1.1<br />

AC oper<strong>at</strong>ed, 50/60 Hz Pick-up x U c 0.85 – 1.1 0.85 – 1.1 0.85 – 1.1 0.85 – 1.1 0.85 – 1.1 0.85 – 1.1<br />

coil<br />

DC oper<strong>at</strong>ed 1) Pick-up x U c 0.85 – 1.1 0.85 – 1.1 0.85 – 1.1 0.85 – 1.1 0.8 – 1.1 0.8 – 1.1<br />

Contactors<br />

Power consumption of the coil <strong>at</strong> cold st<strong>at</strong>e and<br />

1.0 x U c<br />

AC oper<strong>at</strong>ed Pick-up VA 67 100 136 185 320 550<br />

AC oper<strong>at</strong>ed Pick-up W 52 72 88 106 150 220<br />

Single-voltage coil Sealing VA 8.5 10 14 16 24 38<br />

50 Hz<br />

Single-voltage coil Sealing W 2.5 3 3.5 4.5 5.5 10<br />

50 Hz<br />

Dual-voltage coil Sealing VA 8.6 10 15 16.5 26 40<br />

50 Hz, 60 Hz<br />

Dual-voltage coil Sealing W 2.5 3 4 5.8 7 10<br />

50 Hz, 60 Hz<br />

Dual-frequency coil Sealing VA 10 14 21 25 28 43<br />

50/60 Hz <strong>at</strong> 50 Hz<br />

Dual-frequency coil Sealing W 3 4 5 7.5 8 11<br />

50/60 Hz <strong>at</strong> 50 Hz<br />

Dual-frequency coil Sealing VA 8.5 10 15 20 23 37<br />

50/60 Hz <strong>at</strong> 60 Hz<br />

Dual-frequency coil Sealing W 2.5 3 4 6 6 10<br />

50/60 Hz <strong>at</strong> 60 Hz<br />

DC oper<strong>at</strong>ed Pick-up W 9.5 10 14.5 16 230 360<br />

DC oper<strong>at</strong>ed Sealing W 9.5 10 14.5 16 5 5.7<br />

Duty factor % DF 100 100 100 100 100 100<br />

Switching times <strong>at</strong> 100 % U c (approxim<strong>at</strong>e values)<br />

Main contacts<br />

AC oper<strong>at</strong>ed<br />

Closing delay ms 14 – 22 9 – 19 11 – 19 14 – 22 20 – 24 18 – 28<br />

Opening delay ms 5 – 14 5 – 13 6 – 13 5 – 15 8 – 13 7 – 11<br />

DC oper<strong>at</strong>ed<br />

Closing delay ms 35 – 40 40 – 55 68 – 75 75 – 90 27 – 29 28 – 30<br />

Opening delay ms 5 – 10 6 – 10 10 – 15 12 – 18 12 – 23 13 – 16<br />

Reversing contactors<br />

Changeover time <strong>at</strong> 100 % U c ms 13 – 21 2) 13 – 19 2) 12 – 16 2) 13 – 19 2) 21 – 30 23 – 30<br />

Arcing time ms F 10 < 20 < 20 < 20 10 - 20 10 - 25<br />

Lifespan, mechanical; Coil<br />

50/60 Hz<br />

<strong>at</strong> 50 Hz<br />

Mechanical lifespan <strong>at</strong> 50 Hz approx. 30% less than under “General”<br />

Notes<br />

1) Smoothed DC voltage or three-phase current bridge rectifier, <strong>at</strong> least two-pulse bridge rectifier<br />

2) At 660/690 V, a current free pause of f 25 ms is necessary with reversal<br />