5/112 Technical d<strong>at</strong>a<br />
DIL contactors<br />
<strong>Moeller</strong> HPL0211-2004/2005<br />
DIL00M DIL0M DIL1M DIL2M DIL3M80 DIL4M115<br />
DIL00AM DIL0AM DIL1AM DIL2AM DIL3AM85 DIL4AM145<br />
DIL00BM<br />
Contactors<br />
General<br />
Main cable connection screw/bolt M3.5 M4 M6 M6 M8 M10<br />
Tightening torque Nm 1.2 1.8 4 4 6 10<br />
Control circuit cable cross-sections<br />
Solid mm 2 1 x (0.75 – 4)<br />
2 x (0.75 – 4)<br />
Flexible with ferrule mm 2 1 x (0.75 – 2.5)<br />
2 x (0.75 – 2.5)<br />
1 x (0.75 – 4)<br />
2 x (0.75 – 4)<br />
1 x (0.75 – 2.5)<br />
2 x (0.75 – 2.5)<br />
1 x (0.75 – 4)<br />
2 x (0.75 – 4)<br />
1 x (0.75 – 2.5)<br />
2 x (0.75 – 2.5)<br />
1 x (0.75 – 4)<br />
2 x (0.75 – 4)<br />
1 x (0.75 – 2.5)<br />
2 x (0.75 – 2.5)<br />
1 x (0.75 – 4)<br />
2 x (0.75 – 4)<br />
1 x (0.75 – 2.5)<br />
2 x (0.75 – 2.5)<br />
1 x (0.75 – 4)<br />
2 x (0.75 – 4)<br />
1 x (0.75 – 2.5)<br />
2 x (0.75 – 2.5)<br />
Solid or stranded AWG 18 – 12 18 – 12 18 – 12 18 – 12 2 x (18 – 12) 2 x (18 – 12)<br />
Control circuit cable connection screw/bolt M3.5 M3.5 M3.5 M3.5 M3.5 M3.5<br />
Tightening torque Nm 1.2 1.2 1.2 1.2 1.2 1.2<br />
Tools<br />
Main cable<br />
Pozidriv screwdriver Size 2 2 2 2 – –<br />
Inbus – – – – 4 5<br />
Control circuit cable<br />
Pozidriv screwdriver Size 2 2 2 2 2 2<br />
Terminal capacity of springloaded main<br />
terminals<br />
Solid mm 2 1 x (1 – 2.5) – – – – –<br />
2 x (1 – 2.5)<br />
Flexible mm 2 1 x (1 – 2.5) – – – – –<br />
2 x (1 – 2.5)<br />
Flexible with ferrule mm 2 1 x (1 – 2.5) – – – – –<br />
2 x (1 – 2.5)<br />
Tools<br />
Standard screwdriver 0.6 x 3.5 – – – – –<br />
Main contacts<br />
R<strong>at</strong>ed impulse U imp V AC 8000 8000 8000 8000 8000 8000<br />
withstand voltage<br />
Overvoltage c<strong>at</strong>egory/pollution degree III/3 III/3 III/3 III/3 III/3 III/3<br />
R<strong>at</strong>ed insul<strong>at</strong>ion U i V AC 690 690 690 690 1000 1000<br />
voltage<br />
R<strong>at</strong>ed oper<strong>at</strong>ional U e V AC 690 690 690 690 1000 1000<br />
voltage<br />
Safe isol<strong>at</strong>ion to VDE 0106 Part 101 and<br />
Part 101/A1<br />
between coil and contacts V AC 440 440 440 440 500 500<br />
between the contacts V AC 440 440 440 440 500 500<br />
Making capacity<br />
A 200 200 250 270 730 950 1300 1800<br />
(cos v to IEC/EN 60947)<br />
Breaking capacity<br />
220/230 V A 130 130 160 230 380 750 1100 1800<br />
380/400 V A 120 120 160 230 380 600 1100 1800<br />
500 V A 120 120 160 230 355 600 1100 1800<br />
660/690 V A 100 100 125 210 255 545 650 1200<br />
1000 V A – – – – – – 330 630<br />
Component lifespan<br />
AC-3/AC-4/AC-1<br />
a Characteristic curves<br />
Short-circuit r<strong>at</strong>ing<br />
Short-circuit protection r<strong>at</strong>ing maximum fuse<br />
Type “2” coordin<strong>at</strong>ion<br />
400 V gG/gL 500 V A 20 35 63 100 160 250<br />
690 V gG/gL 690 V A – – – – 125 160<br />
1000 V gG/gL 1000 V A – – – – 80 100<br />
Type “1” coordin<strong>at</strong>ion<br />
400 V gG/gL 500 V A 25 50 100 125 250 315<br />
690 V gG/gL 690 V A – – – – 200 224<br />
1000 V gG/gL 1000 V A – – – – 100 160<br />