5/88 Tripping characteristics<br />
DILM contactors<br />
<strong>Moeller</strong> HPL0211-2004/2005<br />
Contactors<br />
Normal switching duty<br />
R<strong>at</strong>ed output of three-phase motors 50–60 HZ<br />
kW<br />
30<br />
22<br />
18.5<br />
15<br />
11<br />
7.5<br />
5.5<br />
4<br />
3<br />
2.2<br />
R<strong>at</strong>ed oper<strong>at</strong>ional current I e 50 – 60 Hz<br />
A<br />
58<br />
43<br />
36<br />
30<br />
23<br />
16<br />
12<br />
8.8 DIL00M<br />
DILEM<br />
6.5 DILEEM<br />
5<br />
DIL2AM<br />
DIL2M<br />
DIL1AM<br />
DIL1M<br />
DIL0AM<br />
DIL0M<br />
DIL00BM<br />
DIL00AM<br />
DIL00BM<br />
AC-3/400 V<br />
Squirrel-cage motors<br />
Oper<strong>at</strong>ing characteristics<br />
Starting: from rest<br />
Stopping: after <strong>at</strong>taining full running speed<br />
<strong>Electric</strong>al characteristics<br />
Make: up to 6 r<strong>at</strong>ed motor current<br />
Break: up to 1 r<strong>at</strong>ed motor current<br />
Utiliz<strong>at</strong>ion c<strong>at</strong>egory<br />
100 % AC-3<br />
Typical applic<strong>at</strong>ions<br />
Compressors Lifts Mixers<br />
Pumps Escal<strong>at</strong>ors Agit<strong>at</strong>ors<br />
Fans Conveyor belts Centrifuges<br />
Hinged flaps Bucket-elev<strong>at</strong>ors Air-conditioning<br />
systems<br />
General drives in manufacturing and processing machines<br />
1.5<br />
3.5<br />
DILE(E)M-G<br />
DIL00M<br />
1.1<br />
0.8<br />
2.5<br />
2<br />
DILE(E)M<br />
0.55<br />
1.6<br />
0.01 0.02 0.04 0.06 0.1 0.2 0.4 0.6 0.75 1 2 3 4 5 6 8 10<br />
Component lifespan (millions of oper<strong>at</strong>ions)<br />
R<strong>at</strong>ed output of three-phase motors 50 – 60 Hz<br />
kW<br />
560<br />
450<br />
400<br />
355<br />
315<br />
250<br />
200<br />
160<br />
132<br />
110<br />
90<br />
75<br />
R<strong>at</strong>ed oper<strong>at</strong>ional current Ie 50 – 60 Hz<br />
A<br />
1000 DILM1000<br />
820<br />
750<br />
650<br />
580<br />
500<br />
400<br />
300<br />
250<br />
225<br />
185<br />
145<br />
DILM820<br />
DILM750<br />
DILM650<br />
DILM580<br />
DILM500<br />
DILM400<br />
DILM300<br />
DILM250<br />
DILM225<br />
DILM185<br />
DIL4AM145<br />
AC-3/400 V<br />
55<br />
104<br />
DIL4M115<br />
45<br />
37<br />
30<br />
85<br />
72<br />
58<br />
DIL3AM85<br />
DIL3M80<br />
22<br />
18.5<br />
15<br />
43<br />
36<br />
30<br />
11<br />
7.5<br />
23<br />
16<br />
0.01 0.02 0.04 0.06 0.1 0.2 0.4 0.6 0.75 1 2 3 4 5 6 8 10<br />
Component lifespan [millions of oper<strong>at</strong>ions]<br />
<strong>For</strong> <strong>Immedi<strong>at</strong>e</strong> <strong>Delivery</strong> <strong>call</strong> <strong>KM<strong>Parts</strong></strong>.<strong>com</strong> <strong>at</strong> (866) 595-9616