5/128 Technical d<strong>at</strong>a<br />

DILP contactors<br />

<strong>Moeller</strong> HPL0211-2004/2005<br />

DILP160 DILP250 DILP315 DILP500 DILP630 DILP800<br />

Contactors<br />

AC<br />

AC-1 oper<strong>at</strong>ion<br />

Component lifespan Oper<strong>at</strong>ions x 10 6 0.5 0.3 0.3 0.1 0.1 0.2<br />

Conventional free air thermal current q r<strong>at</strong>ed oper<strong>at</strong>ional<br />

current, 4-pole open up to 690 V<br />

Open <strong>at</strong> 40 °C A 160 250 315 500 630 800<br />

Open <strong>at</strong> 55 °C A 160 230 270 470 470 650<br />

1-pole open A 450 700 880 1400 1760 2240<br />

AC-3 oper<strong>at</strong>ion<br />

Component lifespan Oper<strong>at</strong>ions x 10 6 0.5 1 1 0.6 0.6 0.5<br />

AC-3 r<strong>at</strong>ed oper<strong>at</strong>ional current, open,<br />

50 – 60 Hz, 3-pole<br />

220/230/240 V I e A 120 145 210 400 400 550<br />

380/400/440 V I e A 120 145 210 400 400 550<br />

500 V 1) I e A 120 120 210 370 370 550<br />

660/690 V 1) I e A 120 120 210 370 370 550<br />

1000 V 1) I e A 64 80 113 155 155 175<br />

AC-3 motor load switch motor r<strong>at</strong>ing<br />

220/230/240 V P kW 30 45 59 110 110 160<br />

380/400/440 V P kW 55 75 110 200 200 280<br />

660/690 V 1) P kW 110 110 160 355 355 500<br />

1000 V 1) P kW 90 110 160 220 220 250<br />

DC<br />

Oper<strong>at</strong>ions 5/97 5/97 5/97 5/97 5/97 5/97<br />

R<strong>at</strong>ed oper<strong>at</strong>ional current, open<br />

DC-1 duty, L/R max. 1 ms<br />

60 V I e A 120 200 300 370 550 800<br />

110 V I e A 120 200 300 370 550 800<br />

220 V I e A 120 200 300 370 550 800<br />

440 V I e A 120 200 260 370 450 650<br />

DC-3 duty, L/R max. 2 ms<br />

60 V I e A 120 145 210 450 450 650<br />

110 V I e A 135 135 210 450 450 650<br />

220 V I e A 135 135 210 450 450 650<br />

440 V I e A 135 135 170 450 450 650<br />

DC-5 duty, L/R max. 7.5 ms<br />

60 V I e A 135 135 210 450 450 650<br />

110 V I e A 135 135 210 450 450 650<br />

220 V I e A 135 135 210 450 450 650<br />

440 V I e A 135 135 170 450 450 650<br />

Current he<strong>at</strong> loss (4-pole)<br />

With conventional free air thermal<br />

W 32 52 65 145 184 240<br />

current I th<br />

Magnet systems<br />

Pick-up and drop-out values<br />

AC oper<strong>at</strong>ed Pick-up x U c 0.85 – 1.1 0.85 – 1.1 0.85 – 1.1 0.85 – 1.1 0.85 – 1.1 0.85 – 1.1<br />

Power consumption of the coil <strong>at</strong> cold st<strong>at</strong>e and 1.0 x U c<br />

AC oper<strong>at</strong>ed Pick-up VA 800 800 1100 3500 3500 3500<br />

Dual-voltage coil 50 Hz Sealing VA 44 44 52 125 125 125<br />

Dual-voltage coil 50 Hz Sealing W 15 15 18 50 50 50<br />

Dual-voltage coil 60 Hz Sealing VA 52 52 65 140 140 140<br />

Dual-voltage coil 60 Hz Sealing W 18 18 22 60 60 60<br />

Duty factor % DF 100 100 100 100 100 100<br />

Switching times <strong>at</strong> 100 % U c (approxim<strong>at</strong>e values)<br />

AC oper<strong>at</strong>ed<br />

Closing delay ms 20 – 40 20 – 40 20 – 40 30 – 60 30 – 60 30 – 60<br />

Opening delay ms 7 – 15 7 – 15 7 – 15 10 – 20 10 – 20 10 – 20<br />

Notes<br />

1) Do not reverse directly<br />