Technical d<strong>at</strong>a<br />
DILP contactors<br />
5/127<br />
<strong>Moeller</strong> HPL0211-2004/2005<br />
DILP160 DILP250 DILP315 DILP500 DILP630 DILP800<br />
General<br />
Standards IEC/EN 60947, VDE 0660<br />
Lifespan, mechanical<br />
AC oper<strong>at</strong>ed Oper<strong>at</strong>ions x 10 6 10 10 10 5 5 5<br />
Maximum oper<strong>at</strong>ing frequency<br />
Mechanical, AC oper<strong>at</strong>ed Oper<strong>at</strong>ions/h 3600 3600 3600 3600 3600 3600<br />
<strong>Electric</strong>al Oper<strong>at</strong>ions/h 600 600 600 300 300 300<br />
Clim<strong>at</strong>ic proofing To LR test specific<strong>at</strong>ion No. 1 (ENV 1, 2, 3),<br />
based on IEC/EN 60068-2-30 and IEC/EN 60068-2-78<br />
Ambient temper<strong>at</strong>ure<br />
Open °C -40/70 -40/70 -40/70 -40/70 -40/70 -40/70<br />
Mounting position<br />
30˚<br />
30˚<br />
180°<br />
Contactors<br />
Mechanical shock resistance, half-sinusoidal shock 15 ms<br />
Main contacts Make<br />
g 10 10 10 10 10 10<br />
contact<br />
Degree of protection IP00 IP00 IP00 IP00 IP00 IP00<br />
Protection against direct contact when actu<strong>at</strong>ed from front finger and back-of-hand proof with terminal shroud<br />
(IEC 536)<br />
Weight kg 4.35 4.35 6.65 17.2 17.2 17.2<br />
Main cable cross-section<br />
Solid or stranded mm 2 10 – 70 35 – 120 35 – 120 1 x (70 – 300)<br />
2 x (35 – 185)<br />
1 x (70 – 300)<br />
2 x (35 – 185)<br />
1 x (70 – 300)<br />
2 x (35 – 185)<br />
Fl<strong>at</strong> conductor See box terminal set a 5/61<br />
Busbar connection max. mm 30 x 6 30 x 10 30 x 10 55 x 10 55 x 10 55 x 10<br />
Terminal screw M10 M10 M10 M10 M10 M10<br />
Tightening torque Nm 12 – 16 12 – 16 12 – 16 12 – 16 12 – 16 12 – 16<br />
Control circuit cable cross-sections<br />
Solid mm 2 2 x (0.5 – 2.5) 2 x (0.5 – 2.5) 2 x (0.5 – 2.5) 2 x (0.5 – 2.5) 2 x (0.5 – 2.5) 2 x (0.5 – 2.5)<br />
Terminal screw M3.5 M3.5 M3.5 M3.5 M3.5 M3.5<br />
Tightening torque Nm 1.2 1.2 1.2 1.2 1.2 1.2<br />
Main contacts<br />
R<strong>at</strong>ed impulse withstand voltage U imp V AC 8000 8000 8000 8000 8000 8000<br />
Overvoltage c<strong>at</strong>egory/pollution degree III/3 III/3 III/3 III/3 III/3 III/3<br />
R<strong>at</strong>ed insul<strong>at</strong>ion voltage U i V AC 1000 1000 1000 1000 1000 1000<br />
R<strong>at</strong>ed oper<strong>at</strong>ional voltage U e V AC 1000 1000 1000 1000 1000 1000<br />
Safe isol<strong>at</strong>ion to VDE 0106 Part 101 and Part 101/A1<br />
between coil and contacts V AC 1000 1000 1000 1000 1000 1000<br />
between the contacts V AC 690 690 690 690 690 690<br />
Making capacity (cos v to IEC/EN 60947) A 1700 1800 2300 5000 5000 5500<br />
Breaking capacity 230 V A 1400 1500 2000 5000 5000 5400<br />
380/400 V A 1400 1500 2000 5000 5000 5400<br />
500 V A 1100 1200 1700 5000 5000 5400<br />
660/690 V A 1100 1200 1700 5000 5000 5400<br />
Component lifespan Oper<strong>at</strong>ions Page 5/94<br />
Short-circuit r<strong>at</strong>ing<br />
Short-circuit protection r<strong>at</strong>ing maximum fuse<br />
Type “2” coordin<strong>at</strong>ion gG/gL A 200 200 315 630 630 630<br />
Type “1” coordin<strong>at</strong>ion gG/gL A 250 250 355 630 630 800<br />
Short-time withstand capability 10 s A 1700 1800 2300 5500 5500 5500<br />