sivacon
sivacon
sivacon
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Technical Data<br />
at a Glance<br />
Standards and specifications<br />
Type-tested low-voltage switchgear<br />
and controlgear assembly (TTA)<br />
Protection against electrical shock<br />
Testing of response to internal faults<br />
(arcing faults)<br />
Induced vibrations<br />
IEC 60439-1, DIN EN 60439-1<br />
(VDE 0660 Part 500)<br />
DIN VDE 0106 Part 100<br />
IEC 61641, VDE 0660 Part 500, Supplement 2<br />
IEC 68 Part 2, IEC 980<br />
Creepage distances<br />
and clearances<br />
Rated impulse withstand<br />
voltage (U imp )<br />
Overvoltage category<br />
Pollution degree<br />
8 kV<br />
III<br />
3<br />
Rated insulation<br />
voltage (U i )<br />
1000<br />
V<br />
Rated operational<br />
voltage (U e )<br />
up to<br />
690<br />
V<br />
Busbars<br />
(3 and 4-pole)<br />
Main horizontal<br />
busbars<br />
Rated current<br />
Rated peak withstand<br />
current (I pk )<br />
Rated short-time<br />
withstand current (I cw )<br />
up to 6300<br />
up to<br />
up to<br />
A<br />
250 kA<br />
100 kA<br />
Vertical busbars for<br />
circuit-breakers<br />
See main horizontal<br />
busbars<br />
for fixed-mounted design<br />
for in-line plug in design<br />
for In-line-type plug-in design 3NJ6<br />
Rated current<br />
Rated peak withstand<br />
current (I pk )<br />
Rated short-time<br />
withstand current (I cw )<br />
up to 2000<br />
up to<br />
up to<br />
A<br />
110 kA<br />
50 kA*<br />
for withdrawable unit design<br />
Rated current<br />
Rated peak withstand<br />
current (I pk )<br />
Rated short-time<br />
withstand current (I cw )<br />
up to 1000<br />
up to<br />
up to<br />
A<br />
143 kA<br />
65 kA*<br />
Device rated currents<br />
Circuit-breakers<br />
Cable feeders<br />
Motor feeders<br />
up to 6300<br />
up to 1600<br />
up to 630<br />
A<br />
A<br />
A<br />
Internal separation<br />
Form 1 to Form 4<br />
IEC 60439-1, Section 7.7<br />
DIN EN 60439-1<br />
Surface treatment<br />
Degree of protection<br />
(Paint finish to DIN 43656)<br />
Frame parts<br />
Enclosure<br />
Doors<br />
Colour of powder-coated parts<br />
(Coat thickness 80 µm)<br />
To IEC 60529, EN 60529<br />
Sendzimir galvanized<br />
Sendzimir galvanized/powder-coated<br />
Powder-coated<br />
RAL 7032, pebble grey<br />
IP 20 to IP 54<br />
Dimensions<br />
(Preferred dimensions to DIN 41488)<br />
Height:<br />
Width:<br />
Depth: Single front<br />
Double front<br />
Power centre<br />
2200<br />
400, 500, 600, 800, 1000<br />
400, 600<br />
1000<br />
1200<br />
mm<br />
mm<br />
mm<br />
mm<br />
mm<br />
* Rated conditional short-circuit current I CC up to 100 kA<br />
27