1Type-Tested Switchgear and<br />

1Controlgear Assembly (TTA)<br />

SIVACON is a type-tested switchgear and<br />

controlgear assembly (TTA) whose physical<br />

characteristics were designed in the test<br />

laboratory both for normal operating conditions<br />

and for fault situations. Conclusive<br />

type tests assure a maximum of reliability<br />

and safety. SIVACON has passed the<br />

following verification tests as detailed in<br />

IEC 60439-1 and DIN EN 60439-1<br />

(VDE 0660 Part 500):<br />

• Verification of temperaturerise<br />

limits by test<br />

• Verification of dielectric<br />

properties by test<br />

• Verification of the shortcircuit<br />

withstand strength<br />

by test<br />

• Verification of the effective<br />

connection between the<br />

exposed conductive parts<br />

of the assembly and the<br />

protective circuit by<br />

inspection or by resistance<br />

measurement<br />

• Verification of the shortcircuit<br />

withstand strength of<br />

the protective circuit by test<br />

• Verification of clearances<br />

and creepage distances<br />

• Verification of mechanical<br />

operation<br />

• Verification of the degree of<br />

protection<br />

Every SIVACON switchboard<br />

assembly undergoes routine<br />

testing before delivery:<br />

• Inspection of the assembly<br />

including inspection of<br />

wiring and, if necessary,<br />

electrical operation test<br />

• Dielectric test<br />

• Checking of protective<br />

measures and of the<br />

electrical continuity of the<br />

protective circuits<br />

These safety requirements<br />

are met by a series of details<br />

in SIVACON, for example:<br />

• With the use of the<br />

withdrawable design,<br />

operating errors are ruled<br />

out by exactly shaped<br />

mechanical guides and<br />

interlocks<br />

• Use is made of only a few,<br />

exclusively high-grade<br />

insulating materials<br />

(e.g. for rail mounts and<br />

reinforcements, etc.)<br />

• Use of reliable Siemens<br />

switchgear reduces the risk<br />

of premature failures<br />

• Reliable disconnection after<br />

70 to 100 ms even in the<br />

event of long delay times by<br />

3WN circuit-breakers with<br />

short-time grading control<br />

• Computer-assisted project<br />

planning assures error-free<br />

selection and placement of<br />

items<br />

• Arcing fault-tested<br />

• Quality management<br />

system to DIN EN ISO 9001<br />

• Environmental management<br />

system to<br />

DIN EN ISO 14001<br />

26