SIVACON is resistant<br />

to internal arcing faults<br />

10<br />

Testing of low voltage switchboards under internal<br />

arcing fault conditions is classified as a special<br />

test in accordance with IEC 61641 or VDE 0660<br />

Part 500, supplement 2.<br />

This test serves to gauge the dangers to which<br />

persons might be exposed in the event of an internal<br />

arcing fault.<br />

By way of the test under internal arcing fault<br />

conditions, SIVACON provides evidence of personnel<br />

safety in terms of the following assessment criteria<br />

as standard:<br />

Arc barrier<br />

Assessment criteria<br />

1. Doors, covers etc. must not<br />

open<br />

2. No parts may fly off<br />

3. No holes may be burnt into<br />

the enclosure<br />

4. Indicators must not ignite<br />

5. The protective conductor<br />

circuit for touchable parts<br />

of the enclosure must still<br />

be in working order<br />

Additional modules for limiting<br />

the effects of the arcing fault<br />

inside the switchboard<br />

• Restriction to one cubicle<br />

(Arc barrier)<br />

• Restriction to the function<br />

compartment or place of<br />

origin<br />

• Insulated main busbars<br />

(design without base)<br />

Arcing fault<br />

test<br />

Insulated<br />

main busbar<br />

Device compartment can<br />

be separated from<br />

interconnected busbars<br />

25