SIVACON is resistant<br />
to internal arcing faults<br />
10<br />
Testing of low voltage switchboards under internal<br />
arcing fault conditions is classified as a special<br />
test in accordance with IEC 61641 or VDE 0660<br />
Part 500, supplement 2.<br />
This test serves to gauge the dangers to which<br />
persons might be exposed in the event of an internal<br />
arcing fault.<br />
By way of the test under internal arcing fault<br />
conditions, SIVACON provides evidence of personnel<br />
safety in terms of the following assessment criteria<br />
as standard:<br />
Arc barrier<br />
Assessment criteria<br />
1. Doors, covers etc. must not<br />
open<br />
2. No parts may fly off<br />
3. No holes may be burnt into<br />
the enclosure<br />
4. Indicators must not ignite<br />
5. The protective conductor<br />
circuit for touchable parts<br />
of the enclosure must still<br />
be in working order<br />
Additional modules for limiting<br />
the effects of the arcing fault<br />
inside the switchboard<br />
• Restriction to one cubicle<br />
(Arc barrier)<br />
• Restriction to the function<br />
compartment or place of<br />
origin<br />
• Insulated main busbars<br />
(design without base)<br />
Arcing fault<br />
test<br />
Insulated<br />
main busbar<br />
Device compartment can<br />
be separated from<br />
interconnected busbars<br />