4000 W AC-Input and DC-Input Power Supplies<br />

Appendix A<br />

Power Supply Specifications<br />

Table A-29<br />

4000 W DC-Input Power Supply Specifications<br />

Specification<br />

Description<br />

DC-input voltage • –48 VDC @ 37 A for nominal –48 V battery backup system<br />

(operating range: –40.5 VDC to –56 VDC)<br />

DC-input current<br />

Power supply output<br />

capacity<br />

• –60 VDC @ 29 A for nominal –60 V battery backup system<br />

(operating range: –55 VDC to –72 VDC)<br />

Note The 4000 W DC-input power supply requires two source<br />

DC-inputs to be connected; it cannot operate with only one<br />

positive (+)/negative (-) source DC terminal pair installed.<br />

40 A per each DC input (three inputs)<br />

Note For multiple DC input power supplies, each DC input must be<br />

protected by a dedicated circuit breaker or a fuse. The circuit<br />

breaker or the fuse must be sized according to the power supply<br />

input power rating and any local or national electrical code<br />

requirements.<br />

• 4000 W with three inputs active<br />

• 2700 W with two inputs active<br />

Note The 4000 W power supply cannot operate with only one source<br />

DC-input connected.<br />

Power supply output • 15 A @ + 3.3 VDC<br />

DC input terminal block<br />

Output holdup time<br />

kVA rating 1<br />

Heat dissipation<br />

Weight<br />

• 5 A @ + 5 VDC<br />

• 12 A @ +12 VDC<br />

• 90.63 A (three inputs) or 59.68 A (two inputs)<br />

@ +42 VDC<br />

Note The 4000 W power supply cannot operate with only one source<br />

DC-input connected.<br />

Accepts 4 AWG copper conductors. Actual size of the wire needed is<br />

determined by the installer or local electrician.<br />

8 ms<br />

5.4 kVA maximum<br />

17,730 BTU/hour (approx.)<br />

30.8 lb (14.0 kg)<br />

1. The kVA rating listed for the power supply should be used as the sizing criteria for both UPS outputs as well as standard<br />

circuits and transformers to power a switch.<br />

Table A-30 lists the power supply LEDs and their meanings.<br />

A-44<br />

<strong>Catalyst</strong> <strong>6500</strong> <strong>Series</strong> <strong>Switches</strong> <strong>Installation</strong> <strong>Guide</strong><br />

OL-5781-08