Appendix A<br />

Power Supply Specifications<br />

2700 W AC-Input and DC-Input Power Supplies<br />

Table A-22<br />

2700 W DC-Input Power Supply Specifications (continued)<br />

Specification<br />

Power supply output • One DC input operation (1350 W operation)<br />

DC input terminal block<br />

Output holdup time<br />

kVA rating 1<br />

Heat dissipation<br />

Weight<br />

Description<br />

– 15 A @ +1.5 VDC<br />

– 5 A @ +3.3 VDC<br />

– 27.49 A @ +50 VDC<br />

• Two DC inputs operation (2700 W operation<br />

– 15 A @ +1.5 VDC<br />

– 5 A @ +3.3 VDC<br />

– 55.61 A @ +50 VDC<br />

Accepts 2–14 AWG copper conductors. Actual size of the wire needed<br />

is determined by the installer or local electrician. Terminal block<br />

material rated at 150°C.<br />

4 ms<br />

3.5 KW<br />

11,968 BTU/hour (approx.)<br />

21.0 lb (9.5 kg)<br />

1. The kVA rating listed for the power supply should be used as the sizing criteria for both UPS outputs as well as standard<br />

circuits and transformers to power a switch.<br />

Table A-23 lists the power supply LEDs and their meanings.<br />

OL-5781-08<br />

<strong>Catalyst</strong> <strong>6500</strong> <strong>Series</strong> <strong>Switches</strong> <strong>Installation</strong> <strong>Guide</strong><br />