Removing and Installing the DC-Input Power Supplies Chapter 4 Removal and Replacement Procedures Note For multiple DC input power supply, each DC input must be protected by dedicated circuit breaker or fuse. The circuit breaker or fuse should be sized according to the power supply input rating and local or national electrical code requirements. Step 10 Wire for 4500 W (right side of power supply bay) as follows: a. From the right side of the power supply, connect the ground wire to the ground (see Figure 4-52). Figure 4-52 DC-Input Wire Connections for 4000-W DC-Input Power Supply, Right Side of Power Bay Terminal block cover Input power module Power switch RUN INSTALL CISCO SYSTEMS, INC 1 2 3 4 INPUT OK FAN OK OUTPUT FAIL Power leads attached to terminal block ( - ) Negative (+) Positive ( - ) Negative (+) Positive ( - ) Negative (+) Positive Captive installation screw ( ) Ground 191291 b. \From the right side of the power supply, connect each of the DC-input wires to the right power supply terminal block (see Figure 4-47 and Figure 4-52) in this order: Negative (-) Positive (+) Note When you tighten the terminal nuts, make sure they are snug. Do not over tighten them. Recommended torque strength is 20 inch-pounds. Over tightening the terminal nuts can break the terminal block (Maximum torque: 36 inch-pounds). c. Secure outer block cover. 4-72 Catalyst 6500 Series Switches Installation Guide OL-5781-08
Chapter 4 Removal and Replacement Procedures Removing and Installing the DC-Input Power Supplies Note For proper 4500W DC-input redundant power configuration, three pairs of input wires for one 6000W DC-input power supply must come from the same battery system (A feed); three pairs of input wires for the other 6000W DC-input power supply must come from another battery system (B feed). Note For multiple DC input power supply, each DC input must be protected by dedicated circuit breaker or fuse. The circuit breaker or fuse should be sized according to the power supply input rating and local or national electrical code requirements. Step 11 Wire for 6000 W (right side of power supply bay) as follows: a. From the right side of the power supply, connect the ground wire to the ground (see Figure 4-53). Figure 4-53 DC-Input Wire Connections for 6000-W DC-Input Power Supply for Right Side of Power Bay Terminal block cover Input power module Power switch RUN INSTALL CISCO SYSTEMS, INC Captive installation screw 1 2 3 4 INPUT OK FAN OK OUTPUT FAIL ( ) Ground Power leads attached to terminal block ( - ) Negative (+) Positive ( - ) Negative (+) Positive ( - ) Negative (+) Positive ( - ) Negative (+) Positive 191293 OL-5781-08 Catalyst 6500 Series Switches Installation Guide 4-73
- Page 228 and 229: Removing and Installing the DC-Inpu
- Page 230 and 231: Removing and Installing the DC-Inpu
- Page 232 and 233: Removing and Installing the DC-Inpu
- Page 234 and 235: Removing and Installing the DC-Inpu
- Page 236 and 237: Removing and Installing the DC-Inpu
- Page 238 and 239: Removing and Installing the DC-Inpu
- Page 240 and 241: Removing and Installing the DC-Inpu
- Page 242 and 243: Removing and Installing the DC-Inpu
- Page 244 and 245: Removing and Installing the DC-Inpu
- Page 246 and 247: Removing and Installing the DC-Inpu
- Page 248 and 249: Removing and Installing the DC-Inpu
- Page 250 and 251: Removing and Installing the DC-Inpu
- Page 252 and 253: Removing and Installing the DC-Inpu
- Page 254 and 255: Removing and Installing the DC-Inpu
- Page 256 and 257: Removing and Installing the DC-Inpu
- Page 258 and 259: Removing and Installing the DC-Inpu
- Page 260 and 261: Removing and Installing the DC-Inpu
- Page 262 and 263: Removing and Installing the DC-Inpu
- Page 264 and 265: Removing and Installing the DC-Inpu
- Page 266 and 267: CISCO SYSTEMS, INC Removing and Ins
- Page 268 and 269: CISCO SYSTEMS, INC 1 2 3 4 INPUT OK
- Page 270 and 271: Removing and Installing the DC-Inpu
- Page 272 and 273: CISCO SYSTEMS, INC Removing and Ins
- Page 274 and 275: Removing and Installing the DC-Inpu
- Page 276 and 277: Removing and Installing the DC-Inpu
- Page 280 and 281: CISCO SYSTEMS, INC 1 2 3 4 INPUT OK
- Page 282 and 283: Removing and Installing PEMs Chapte
- Page 284 and 285: Removing and Installing PEMs Chapte
- Page 286 and 287: OSM-4OC12 POS-SI 1 2 1 2 1 1 2 2 3
- Page 288 and 289: Removing and Installing the Fan Tra
- Page 290 and 291: WS-X6K-SUP2-2GE OSM-4OC12 POS-SI OS
- Page 292 and 293: WS-X6K-SUP2-2GE SUPERVISOR2 WS-X6K-
- Page 294 and 295: WS-C6500-SFM SWITCH FABRIC MDL WS-C
- Page 296 and 297: WS-X6K-SUP2-2GE SUPERVISOR2 WS-X6K-
- Page 298 and 299: Removing and Installing the Fan Tra
- Page 300 and 301: ACTIVE TX RX RX TX ACTIVE TX RX RX
- Page 302 and 303: Installing the Air Filter Assembly
- Page 304 and 305: Installing the Remote Power Cycling
- Page 306 and 307: Installing the Remote Power Cycling
- Page 308 and 309: Installing the Remote Power Cycling
- Page 310 and 311: Power Supply Compatibility Matrix A
- Page 312 and 313: Power Supply Compatibility Matrix A
- Page 314 and 315: 950 W AC-Input and DC-Input Power S
- Page 316 and 317: 950 W AC-Input and DC-Input Power S
- Page 318 and 319: 1000 W AC-Input Power Supply Append
- Page 320 and 321: 1000 W AC-Input Power Supply Append
- Page 322 and 323: 1300 W AC-Input and DC-Input Power
- Page 324 and 325: 1300 W AC-Input and DC-Input Power
- Page 326 and 327: 1400 W AC-Input Power Supply Append
Removing and Installing the DC-Input Power Supplies<br />
Chapter 4<br />
Removal and Replacement Procedures<br />
Note<br />
For multiple DC input power supply, each DC input must be protected by dedicated circuit<br />
breaker or fuse. The circuit breaker or fuse should be sized according to the power supply input<br />
rating and local or national electrical code requirements.<br />
Step 10<br />
Wire for 4500 W (right side of power supply bay) as follows:<br />
a. From the right side of the power supply, connect the ground wire to the ground (see Figure 4-52).<br />
Figure 4-52<br />
DC-Input Wire Connections for 4000-W DC-Input Power Supply, Right Side of Power<br />
Bay<br />
Terminal<br />
block cover<br />
Input power<br />
module<br />
Power<br />
switch<br />
RUN<br />
INSTALL<br />
CISCO SYSTEMS, INC<br />
1 2 3 4<br />
INPUT OK<br />
FAN<br />
OK<br />
OUTPUT<br />
FAIL<br />
Power leads<br />
attached to<br />
terminal block<br />
( - ) Negative<br />
(+) Positive<br />
( - ) Negative<br />
(+) Positive<br />
( - ) Negative<br />
(+) Positive<br />
Captive<br />
installation<br />
screw<br />
( ) Ground<br />
191291<br />
b. \From the right side of the power supply, connect each of the DC-input wires to the right power<br />
supply terminal block (see Figure 4-47 and Figure 4-52) in this order:<br />
Negative (-)<br />
Positive (+)<br />
Note<br />
When you tighten the terminal nuts, make sure they are snug. Do not over tighten them.<br />
Recommended torque strength is 20 inch-pounds. Over tightening the terminal nuts can<br />
break the terminal block (Maximum torque: 36 inch-pounds).<br />
c. Secure outer block cover.<br />