Removing and Installing the DC-Input Power Supplies<br />

Chapter 4<br />

Removal and Replacement Procedures<br />

Installing a 6000 W DC-Input Power Supply<br />

Note<br />

With the PWR-6000-DC power supply, you have the option of installing an Input Power Module (IPM)<br />

(previously removed) with the DC-input wires and the ground wires still connected. You can then install<br />

your power supply and insert the fully-wired IPM. Read through this procedure carefully before<br />

installing your power supply.<br />

Warning<br />

Before performing any of the following procedures, ensure that power is removed from the DC<br />

circuits. To ensure that all power is removed, locate the circuit breakers or fuses on the DC power<br />

lines that service the DC circuits. Turn OFF the DC power line circuit breakers and remove the DC<br />

power line fuses. Statement 322<br />

Note<br />

For proper 6000W DC-input redundant power configuration, all input wires (two pairs for 2800W<br />

DC-input, three pairs for 4500W DC-input, and four pairs for 6000W DC-input) for one 6000W<br />

DC-input power supply must come from the same battery system (A feed); all input wires (two pairs for<br />

2800W DC-input, three pairs for 4500W DC-input, and four pairs for 6000W DC-input) for the other<br />

6000W DC-input power supply must come from another battery system (B feed).<br />

Note<br />

For multiple DC input power supply, each DC input must be protected by dedicated circuit breaker or<br />

fuse. The circuit breaker or fuse should be sized according to the power supply input rating and local or<br />

national electrical code requirements.<br />

Warning<br />

When installing or replacing the unit, the ground connection must always be made first and<br />

disconnected last. Statement 1046<br />

Note<br />

The 6000 W DC-input power supply provides power of 2800 W, 4500 W, or 6000 W. Select 2800 W by<br />

wiring any two positive (+)/negative (-) terminal pairs in any sequence. Select 4500 W by wiring any<br />

three positive (+)/negative (-) terminal pairs in any sequence. Select 6000 W by wiring all four positive<br />

(+)/negative (-) terminal pairs. The Cisco IOS software detects the wired inputs and sets the proper<br />

system power.<br />

Note<br />

The 6000 W DC-input power supply ground provides the system ground connection when the<br />

PWR-6000-DC power supply is installed in a <strong>Catalyst</strong> <strong>6500</strong> series chassis. Install the ground as<br />

described in this procedure.<br />

Note<br />

For redundant power supplies, you must connect the 6000 W DC-input power supply ground for both<br />

power supplies.<br />

4-64<br />

<strong>Catalyst</strong> <strong>6500</strong> <strong>Series</strong> <strong>Switches</strong> <strong>Installation</strong> <strong>Guide</strong><br />

OL-5781-08