Removing and Installing the DC-Input Power Supplies<br />

Chapter 4<br />

Removal and Replacement Procedures<br />

Warning<br />

When installing or replacing the unit, the ground connection must always be made first and<br />

disconnected last. Statement 1046<br />

Caution<br />

Step 18<br />

Step 19<br />

To prevent a short circuit or shock hazard after wiring the DC-input power supply, reinstall the terminal<br />

block covers.<br />

After you confirm that all installation steps are completed correctly, remove any safety flags, lockout<br />

devices, or adhesive tape from the source DC circuit breakers, and energize the source DC circuits to the<br />

power supplies.<br />

Turn the power switch to the On (|) position on the power supply. Turning on the power switch also<br />

engages a pawl that locks the power supply in the chassis.<br />

Verify the power supply operation by ensuring that the power supply front panel LEDs are in the<br />

following states:<br />

• INPUT OK 1 LED—If you have source DC cables attached to the VE-1 pair of power supply inputs,<br />

verify that the LED is green. If source DC cables are attached and the LED is not lit, source DC<br />

might not be on or the source DC voltage is less than or equal to –33 VDC. If the source DC voltage<br />

is between –33 VDC and –40.5 VDC, the LED can be either on, off, or flashing.<br />

• INPUT OK 2 LED—If you have source DC cables attached to the VE-2 pair of power supply inputs,<br />

verify that the LED is green. If source DC cables are attached and the LED is not lit, source DC<br />

might not be on or the source DC voltage is less than or equal to –33 VDC. If the source DC voltage<br />

is between –33 VDC and –40.5 VDC, the LED can be either on, off, or flashing.<br />

• INPUT OK 3 LED—If you have source DC cables attached to the VE-3 pair of power supply inputs,<br />

verify that the LED is green. If source DC cables are attached and the LED is not lit, source DC<br />

might not be on or the source DC voltage is less than or equal to –33 VDC. If the source DC voltage<br />

is between –33 VDC and –40.5 VDC, the LED can be either on, off, or flashing.<br />

• FAN OK LED is green.<br />

• OUTPUT FAIL LED is not lit.<br />

If the LEDs indicate a power problem, see the “Identifying Startup Problems” section on page E-3.<br />

Removing and Installing a 6000 W DC-Input Power Supply<br />

This section covers the power supply removal and installation procedures for the 6000 W DC-input<br />

power supply (PWR-6000-DC) and is divided into the following topics:<br />

• Required Tools, page 4-59<br />

• Removing a 6000 W DC-Input Power Supply, page 4-59<br />

• Installing a 6000 W DC-Input Power Supply, page 4-64<br />

Note<br />

For proper 6000 W DC-input redundant power configurations, all of the source DC for one 6000 W<br />

DC-input power supply must come from the same battery system (A feed); all of the source DC for the<br />

other 6000 W DC-input power supply must come from another battery system (B feed).<br />