Chapter 4<br />

Removal and Replacement Procedures<br />

Removing and Installing the DC-Input Power Supplies<br />

When installing a 4000 W DC-input power supply, observe the following guidelines:<br />

• For proper 4000 W DC-input redundant power configuration, all source DC cables for one 4000 W<br />

DC-input power supply must come from the same battery system (A feed), and all source DC cables<br />

for the second 4000 W DC-input power supply must come from a different battery system (B feed).<br />

Note<br />

For multiple DC-input power supplies, each DC input must be protected by a dedicated<br />

circuit breaker or a fuse. The circuit breaker or fuse must be sized according to the power<br />

supply input rating and the local or national electrical code requirements.<br />

• The 4000 W DC-input power supply is designed to operate at either 2700 W or 4000 W. To operate<br />

the power supply at 2700 W, you can wire any two positive (+) negative (–) terminal pairs (VE-1<br />

and VE-2, VE-2 and VE-3, or VE-1 and VE-3). To operate the power supply at 4000 W, you must<br />

wire all three terminal pairs.<br />

Note<br />

The 4000 W DC-input power supply does not operate with only one pair of source DC cables<br />

connected.<br />

• For a single 4000 W DC-input power supply installation, install the power supply in the left-side<br />

power bay (POWER 1).<br />

Warning<br />

Before performing any of the following procedures, ensure that power is removed from the DC<br />

circuits. To ensure that all power is removed, locate the circuit breakers or fuses on the DC power<br />

lines that service the DC circuits. Turn OFF the DC power line circuit breakers and remove the DC<br />

power line fuses. Statement 322<br />

Warning<br />

Power supply captive installation screws must be tight to ensure protective grounding continuity.<br />

Statement 289<br />

Refer to Figure 4-26 for a front view of the power supply with the major features called out.<br />

Note<br />

Figure 4-26 shows the PWR-4000-DC power supply with an outer terminal block cover. An earlier<br />

version of this power supply does not have an outer terminal block cover. To order a retrofit kit<br />

containing this cover, use Cisco Systems part number CVR-4000DC-TERM=.<br />

OL-5781-08<br />