Removing and Installing the DC-Input Power Supplies<br />

Chapter 4<br />

Removal and Replacement Procedures<br />

Step 8<br />

Connect the source DC cable lugs to the 2700 W power supply terminal block posts (Figure 4-23) in this<br />

order:<br />

• Ground cable lug to the ground terminal posts<br />

• Negative (–) source DC cable lug to terminal post –VE-1<br />

• Positive (+) source DC cable lug to terminal post +VE-1<br />

Note<br />

If you are only going to install one pair of source DC cables (1350 W operation), you can attach<br />

the source DC cables to either the VE-1 or VE-2 pair of terminal posts. Also notice that there is<br />

only one ground connection on the power supply faceplate.<br />

Caution<br />

When you tighten the terminal nuts, make sure that they are snug. Do not overtighten them.<br />

Overtightening the terminal nuts can damage the terminal block. The recommended torque values for<br />

tightening the terminal nuts are 15 inch-pounds (1.7 newton-meters) (minimum) and 20 inch-pounds<br />

(2.2 newton-meters) (maximum).<br />

Figure 4-23<br />

Attaching the Source DC Cables and the Ground Cable<br />

PWR-2700-DC/4<br />

-VE-1<br />

-VE-1<br />

INPUT1 INPUT2 FAN OUTPUT<br />

OK OK OK FAIL<br />

48V-60V 48V-60V<br />

=40A =40A<br />

-VE-2<br />

-VE-2<br />

ALL FASTENERS MUST BE FULLY ENGAGED<br />

PRIOR TO OPERATING THE POWER SUPPLY<br />

270853<br />

Position the source DC cables in the fixed cable guide. Place the top half of the fixed cable guide over<br />

the source DC cables and secure the top half of the cable guide to the bottom half with two screws.<br />

Figure 4-24 shows how the source DC cables are routed from the left side of the power supply.<br />

Warning When installing the unit, always make the ground connection first and disconnect it last. Statement 42<br />

Step 9<br />

Step 10<br />

Route and secure the ground cable to the fixed cable guide loops with the two cable-ties supplied with<br />

the power supply. (See Figure 4-24.)<br />

Position the clear plastic terminal block cover over the terminal block and secure it to the power supply<br />

using the four supplied screws. (See Figure 4-24.)<br />