Removing and Installing the DC-Input Power Supplies<br />

Chapter 4<br />

Removal and Replacement Procedures<br />

Installing a 950 W DC-Input Power Supply<br />

Warning<br />

Before performing any of the following procedures, ensure that power is removed from the DC<br />

circuits. To ensure that all power is removed, locate the circuit breakers or fuses on the DC power<br />

lines that service the DC circuits. Turn OFF the DC power line circuit breakers and remove the DC<br />

power line fuses. Statement 322<br />

To install a 950 W DC-input power supply, follow these steps:<br />

Step 1<br />

Ensure that the system (earth) ground connection has been made. For ground connection installation<br />

instructions, see the “Establishing the System Ground” section on page 3-52.<br />

Note<br />

The system (NEBS) ground serves as the primary safety ground for the <strong>Catalyst</strong> 6503 and<br />

<strong>Catalyst</strong> 6503-E chassis that are equipped with DC-input power supplies. The DC-input power<br />

supplies for these chassis do not have a separate ground. Make sure that the chassis you are<br />

working on has the system (NEBS) ground installed.<br />

Step 2<br />

Step 3<br />

Verify that power is off to the DC circuit connected to the DC PEM for the power supply that you are<br />

installing. As an added precaution, place the appropriate safety flag and lockout devices at the source<br />

power circuit breaker, or place a piece of adhesive tape over the circuit breaker handle to prevent<br />

accidental power restoration while you are working on the circuit.<br />

Grasp the power supply handle with one hand. Place your other hand underneath the power supply, as<br />

shown in Figure 4-10. Slide the power supply into the power supply bay. Make sure that the power<br />

supply is fully seated in the bay.<br />

Step 4 Tighten the power supply captive installation screws. (See Figure 4-9.)<br />

Caution<br />

Power supply captive installation screws must be tight to ensure protective grounding continuity.<br />

Caution<br />

Step 5<br />

Step 6<br />

Step 7<br />

In a system with dual power supplies, connect each power supply to a separate input line. In case of<br />

a line failure, the second source should still be available.<br />

Verify that all connections to the DC PEM are secure.<br />

Remove any safety flags, lockout devices, or tape from the circuit breaker switch handle, and restore<br />

power by moving the circuit breaker switch handle to the On (|) position.<br />

Verify the power supply operation by ensuring that the power supply front panel LEDs are in the<br />

following states:<br />

• INPUT OK LED is green<br />

• FAN OK LED is green<br />

• OUTPUT FAIL LED is not lit<br />

If the LEDs indicate a power problem, see the “Identifying Startup Problems” section on page E-3.<br />