Parameter<br />

<strong>MT</strong>Manager description<br />

OUT_OFFEVT_* Off event 0<br />

Default<br />

value<br />

0<br />

1<br />

...<br />

16<br />

Range<br />

Analog inputs AN1, AN2 * - index from 1 to 2<br />

AN_NAME_* Name AN* max. 16 characters<br />

AN_MODE_* Input type 1<br />

1<br />

2<br />

3<br />

AN_FLR_* Filtering constant [s] 0<br />

0<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

AN_RANGE_* Signal range 1<br />

0<br />

1<br />

AN_LREF_*<br />

Low reference - internal units<br />

{0...5V}<br />

0 0...500<br />

AN_LREF_*<br />

Low reference - internal units<br />

{0...10V}<br />

0 0...1000<br />

AN_LREF_* Low reference - internal units 0 0...2000<br />

AN_HREF_*<br />

High reference - internal units<br />

{0...5V}<br />

1000 0...500<br />

AN_HREF_*<br />

High reference - internal units<br />

{0...10V}<br />

1000 0...1000<br />

AN_HREF_* High reference - internal units 1000 0...2000<br />

AN_LENG_*<br />

Low reference - engineering<br />

units<br />

0 -32757...32767<br />

AN_HENG_*<br />

High reference - engineering<br />

units<br />

1000 -32757...32767<br />

AN_ALM_HH_* Alarm HiHi - engineering units 32767 -32757...32767<br />

AN_NAME_* Name AN* max. 16 characters<br />

AN_ALM_HI_* Alarm Hi - engineering units 32767 -32757...32767<br />

AN_ALM_LO_* Alarm Lo - engineering units -32767 -32757...32767<br />

AN_ALM_LL_* Alarm LoLo - engineering units -32767 -32757...32767<br />

AN_ALM_HIST_<br />

*<br />

Alarm hysteresis - engineering<br />

units<br />

100 0...65535<br />

AN_DBD_* Deadband - engineering units 100 0...65535<br />

1-Wire inputs (1, 2) * - index from 1 to 2<br />

OW_NAME_* Name 1-WIRE* max. 16 characters<br />

OW_ACT_* Input mode 1<br />

OW_ALM_HH_* Alarm HiHi 125 -25...125<br />

OW_ALM_HI_* Alarm Hi 125 -25...125<br />

OW_ALM_LO_* Alarm Lo -25 -25...125<br />

OW_ALM_LL_* Alarm LoLo -25 -25...125<br />

OW_ALM_HIST_<br />

*<br />

Alarm hysteresis 2 0...50<br />

OW_DBD_* Deadband 2 0...50<br />

1<br />

2<br />

Definition<br />

None<br />

EVT1<br />

...<br />

EVT16<br />

(* - index from 1<br />

to 16)<br />

Voltage input<br />

Current input<br />

PT100 (AN1) or<br />

NTC (AN2)<br />

0<br />

0,05<br />

0,1<br />

0,25<br />

0,5<br />

1<br />

2<br />

4<br />

8<br />

0...5V<br />

0...10V<br />

Inactive<br />

Temperature<br />

measurement<br />

74