13.11.2014 Views

Telemetry Module MT-021 User Manual

Telemetry Module MT-021 User Manual

Telemetry Module MT-021 User Manual

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Data type<br />

- number<br />

Range - 0...32767<br />

Default value - 100<br />

Comments<br />

- Setting hysteresis relevant for signal fluctuations prevents<br />

excessive activations of alarm flags.<br />

6.2.6.1.3.14. Deadband - engineering units<br />

Function<br />

- This parameter defines a minimal change of registered analog<br />

signal to react on.<br />

Data type<br />

- number<br />

Range - 0....32767<br />

Default value - 100<br />

Comments - When set to value 0, the flag will rise upon every detected<br />

signal change by minimum 1 engineering unit. Deadband flags<br />

are dedicated to continuous monitoring of analog signal<br />

changes.<br />

6.2.6.1.4. Inputs 1-WIRE1, 1-WIRE2<br />

<strong>MT</strong>-<strong>021</strong> module is equipped with two 1-WIRE inputs which allow connection of external<br />

transducers (e.g. temperature sensors).<br />

6.2.6.1.4.1. Name<br />

Function - Defines input's user friendly name<br />

Data type - Text<br />

Range - Letters and numerals, max. 16 characters<br />

Default value - Respectively (1-WIRE1, 1-WIRE2)<br />

Comments - Assigning friendly names facilitates discrimination of<br />

inputs destination and required settings.<br />

6.2.6.1.4.2. Input type<br />

Function<br />

- selection of 1-WIRE input mode<br />

Data type<br />

- selection list<br />

Range<br />

- Temperature measurement<br />

Temperature measurement by DS18B20 sensor<br />

Inactive<br />

Input switched off<br />

Default value - Inactive<br />

Comments - N/A<br />

6.2.6.1.4.2.1. Temperature measurement<br />

In this mode, the input module performs temperature reading from the DS18B20<br />

sensor connected to a 1-Wire bus. Configuration parameters associated with that<br />

operation mode allows to set alarm thresholds, hysteresis and deadband.<br />

47