Data type<br />
- number<br />
Range - 0...32767<br />
Default value - 100<br />
Comments<br />
- Setting hysteresis relevant for signal fluctuations prevents<br />
excessive activations of alarm flags.<br />
6.2.6.1.3.14. Deadband - engineering units<br />
Function<br />
- This parameter defines a minimal change of registered analog<br />
signal to react on.<br />
Data type<br />
- number<br />
Range - 0....32767<br />
Default value - 100<br />
Comments - When set to value 0, the flag will rise upon every detected<br />
signal change by minimum 1 engineering unit. Deadband flags<br />
are dedicated to continuous monitoring of analog signal<br />
changes.<br />
6.2.6.1.4. Inputs 1-WIRE1, 1-WIRE2<br />
<strong>MT</strong>-<strong>021</strong> module is equipped with two 1-WIRE inputs which allow connection of external<br />
transducers (e.g. temperature sensors).<br />
6.2.6.1.4.1. Name<br />
Function - Defines input's user friendly name<br />
Data type - Text<br />
Range - Letters and numerals, max. 16 characters<br />
Default value - Respectively (1-WIRE1, 1-WIRE2)<br />
Comments - Assigning friendly names facilitates discrimination of<br />
inputs destination and required settings.<br />
6.2.6.1.4.2. Input type<br />
Function<br />
- selection of 1-WIRE input mode<br />
Data type<br />
- selection list<br />
Range<br />
- Temperature measurement<br />
Temperature measurement by DS18B20 sensor<br />
Inactive<br />
Input switched off<br />
Default value - Inactive<br />
Comments - N/A<br />
6.2.6.1.4.2.1. Temperature measurement<br />
In this mode, the input module performs temperature reading from the DS18B20<br />
sensor connected to a 1-Wire bus. Configuration parameters associated with that<br />
operation mode allows to set alarm thresholds, hysteresis and deadband.<br />