6.2.6.1.3.9. Alarm HiHi - engineering units<br />

Function<br />

- Defines HiHi alarm level for analog signal value in engineering<br />

units.<br />

Data type<br />

- number<br />

Range - -32767...32767<br />

Default value - 32 767<br />

Comments - Upon exceeding the preset value by analog signal the HiHi<br />

alarm flag is risen. The resetting level of the flag depends on<br />

Alarm hysteresis setting.<br />

6.2.6.1.3.10. Alarm Hi - engineering units<br />

Function<br />

- Defines Hi alarm level for analog signal value in engineering<br />

units.<br />

Data type<br />

- number<br />

Range - -32767...32767<br />

Default value - 32 767<br />

Comments - Upon exceeding the preset value by analog signal the Hi alarm<br />

flag is risen. The resetting level of the flag depends on Alarm<br />

hysteresis setting.<br />

6.2.6.1.3.11. Alarm Lo - engineering units<br />

Function<br />

- Defines Lo alarm level for analog signal value in engineering<br />

units.<br />

Data type<br />

- number<br />

Range - -32767...32767<br />

Default value - -32767<br />

Comments - Upon exceeding the preset value by analog signal the Lo alarm<br />

flag is risen. The resetting level of the flag depends on Alarm<br />

hysteresis setting.<br />

6.2.6.1.3.12. Alarm LoLo - engineering units<br />

Function<br />

- Defines LoLo alarm level for analog signal value in<br />

engineering units.<br />

Data type<br />

- number<br />

Range - -32767...32767<br />

Default value - -32767<br />

Comments - Upon exceeding the preset value by analog signal the LoLo<br />

alarm flag is risen. The resetting level of the flag depends on<br />

Alarm hysteresis setting.<br />

6.2.6.1.3.13. Alarm hysteresis - engineering units<br />

Function<br />

- Defines hysteresis value for analog signal thresholds. The<br />

value is set in engineering units.<br />