6.2.6.1.2.1. Name<br />
Function - Defines output's user friendly name<br />
Data type - Text<br />
Range - Letters and numerals, max 16 characters<br />
Default value - Respectively (Q1...Q4)<br />
Comments - Assigning friendly names facilitates discrimination of<br />
outputs destination and required settings.<br />
6.2.6.1.2.2. Output mode<br />
Function - selection of binary output mode<br />
Data type - selection list<br />
Range - Monostable<br />
binary output is set for time given by Pulse<br />
duration parameter<br />
Bistable<br />
state of output is defined by user<br />
Default value - Monostable<br />
Comments - N/A<br />
6.2.6.1.2.3. Pulse duration [s]<br />
Function - defines length (in seconds) of impulse on binary output in<br />
monostable output mode<br />
Data type - number<br />
Range - 0.1 ... 214748364.7<br />
Default value - 0.1<br />
Comments - N/A<br />
6.2.6.1.2.4. On event<br />
Function - Allows selection of predefined event from the event list,<br />
which is to be used to turn on output.<br />
Data type - selection list<br />
Range - None or names of event from the Events table<br />
Default value - None<br />
Comments - N/A<br />
6.2.6.1.2.5. Off event<br />
Function - Allows selection of predefined event from the event list,<br />
which is to be used to turn off output.<br />
Data type - selection list<br />
Range - None or names of event from the Events table<br />
Default value - None<br />
Comments - Parameter is only available when Output mode is set to<br />
Bistable.<br />
43