6.2.6.1.1.2.1.2. Counting range (32bits)<br />

Function - defines max. value assumed by the counter<br />

Data type - number<br />

Range - 0....2 147 483 647<br />

Default value - 0<br />

Comments - N/A<br />

6.2.6.1.1.2.1.3. Triggering slope<br />

Function - selects counting direction<br />

Data type - selection list<br />

Range - Bi 0->1<br />

The change of counter state occurs upon signal change<br />

from 0 > 1<br />

Bi 1->0<br />

The change of counter state occurs upon signal change<br />

from 1 > 0<br />

Bi 0->1 | 1->0<br />

The change of counter state occurs upon any change of<br />

signal<br />

Default value - Bi 0->1<br />

Comments - N/A<br />

6.2.6.1.1.3. Filtering constant [s]<br />

Function - Defines (in seconds) value of minimum duration of<br />

altered state on input in order to consider state to be<br />

stable.<br />

Data type - number<br />

Range - 0....163,83 [s]<br />

Default value - 0,10 [s]<br />

Comments - Setting value appropriate to contact characteristics<br />

eliminates disturbance caused by contact bounce thus<br />

preventing multiple registration of what is in reality one<br />

pulse.<br />

6.2.6.1.2. Outputs Q1 ... Q4<br />

The <strong>MT</strong>-<strong>021</strong> module is equipped in four relay outputs Q1...Q4. Outputs can operate in<br />

one of two functional modes:<br />

monostable<br />

bistable<br />

Each mode has a set of specific configuration parameters.<br />