6.2.3.7.2. Symbolic name<br />
Function - Defines user friendly name<br />
Data type - Text<br />
Range - 0..50 characters<br />
Default value - IREG0...IREG15<br />
Comments - N/A<br />
6.2.3.7.3. Space<br />
Function - Selection of register address space assigned to symbolic<br />
name.<br />
Data type - selection list<br />
Range - HReg<br />
IReg<br />
HB<br />
IB<br />
Default value - IReg<br />
Comments - N/A<br />
Internal registers address space (registers<br />
readout)<br />
Analog input address space (registers readout)<br />
Internal register address space (bits readout)<br />
Analog register address space (bits readout)<br />
6.2.3.7.4. Register/bit number<br />
Function - This parameter, together with the parameter Space<br />
defines the register address or bit assigned to symbolic<br />
name.<br />
Data type - number<br />
Range - 0...65535<br />
Default value - 0...15<br />
Comments - N/A<br />
6.2.3.8. Macros<br />
Macros group contains up to 16 use-defined macros. Macro may contain ASCII signs,<br />
symbolic names, SMS commands and other macros that will be put in SMS text.<br />
In order to use a symbolic name in SMS put it name preceded by '*' sign in SMS text<br />
send from mobile phone or defined in Rules/SMS sending or other macro.<br />
Using macros makes composing complex SMS texts and queries much more convenient<br />
and user friendly.<br />
6.2.3.8.1. Number of macros<br />
Function - declares number of user defined macros.<br />
Data type - number<br />
Range - 1..16<br />