Revised November 2007<br />

29. Intermountain - Gonder 230 kV<br />

Accepted <strong>Rating</strong><br />

Existing <strong>Rating</strong><br />

Other<br />

Location:<br />

Definition:<br />

Transfer Limit:<br />

Critical<br />

Disturbance<br />

that limits the<br />

transfer<br />

capability:<br />

Transmission line from Intermountain Power Facility (IPF) at Delta, Utah to<br />

Gonder station in eastern central Nevada<br />

A 144-mile 230 kV transmission line from the 230 kV IPF station to the<br />

Mt. Wheeler Power Cooperative’s Gonder 230 kV station. The IPF 230 kV<br />

station is connected to the IPF 345 kV station through a 300 MVA regulating<br />

transformer. The IPF 345 and 230 kV stations are in the Los Angeles<br />

Department of Water and Power (LADWP) control area, while the Gonder<br />

230 kV station is in the Sierra Pacific Power Company’s control area.<br />

East to West: 200 MW (non-simultaneous)<br />

Studies to determine the simultaneous rating of this line with the Pavant-<br />

Gonder 230 kV line are presently on-going.<br />

The non-simultaneous rating is based on the rule-of-thumb criterion of<br />

30 degree power angle difference between the sending and the receiving end,<br />

and on N-0 load flow studies.<br />

When: The 200 MW bidirectional non-simultaneous rating was established in 1987,<br />

when the IPF was first put into service. This rating has been documented in<br />

the WECC Operations Committee’s Non-Simultaneous Transfer Capability<br />

Diagram as well as in the NERC Form OE-411, Item 5A reportings.<br />

System<br />

Conditions:<br />

Study Criteria:<br />

Remedial<br />

Actions<br />

Required:<br />

Formal<br />

Operating<br />

Procedure:<br />

Allocation:<br />

Interaction<br />

w/Other<br />

Transfer <strong>Path</strong>s:<br />

The non-simultaneous rating is based on the rule-of-thumb criterion of<br />

30 degree power angle difference between the sending and the receiving end,<br />

and on N-0 load flow studies.<br />

WECC Reliability Criteria for System Design. (The applicable WECC<br />

reliability criteria at that time.)<br />

For disturbances where both of the IPF-Mona 345 kV lines are tripped, a<br />

transfer trip protection trips the IPF-Gonder 230 kV line.<br />

There is an established energization/synchronization procedure for the line to<br />

control overvoltage conditions on the line. The IPF 230/345 kV regulating<br />

transformer (ULTC) is under the LADWP SCADA system.<br />

The following utilities have entitlements on this line:<br />

LDWP, Anaheim, Riverside, Pasadena, Burbank and Glendale.<br />

At the maximum flow conditions, the transfer capability of the line is<br />

sensitive to the flows on the Pavant-Gonder 230 kV line. Simultaneous flow<br />

capability of these two lines at the Gonder station cut-plane is presently under<br />

going a study.<br />

PART VI Item 1-82