12.11.2014 Views

Path Rating Catalog 2013 - Western Electricity Coordinating Council

Path Rating Catalog 2013 - Western Electricity Coordinating Council

Path Rating Catalog 2013 - Western Electricity Coordinating Council

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

System<br />

Conditions:<br />

The Accepted <strong>Rating</strong> for NE-SW transfer was studied under 2008 Heavy<br />

Summer conditions with all lines in service and would be applicable year<br />

round.<br />

The Existing <strong>Rating</strong> for SW-NE transfer is dependent on the AC ties to the<br />

Utah system. The Intermountain-Mona 345 kV line transfer limitation is<br />

1400 MW line thermal rating based on N-1 contingency, i.e., one of the<br />

Intermountain-Mona 345 kV lines being out.<br />

Study Criteria: • NERC/WECC Transmission Planning Reliability Criteria.<br />

Remedial<br />

Actions<br />

Required:<br />

The Intermountain Power Project (IPP) Contingency Arming System (CAS)<br />

has been implemented to mitigate IPPDC disturbances by monitoring realtime<br />

power flows and arming to trip the required amount of IPP generating<br />

units and Milford wind generation.<br />

Formal<br />

Operating<br />

Procedure:<br />

The IPP CAS consists of arming charts where real-time power output of the<br />

IPP generating units, the Milford wind generation along with the IPPDC line<br />

flows are used to select the no-unit, one-unit or two-unit tripping of the IPP<br />

generation units along with the tripping of Milford wind generation. The IPP<br />

CAS and associated operating procedures are included with the LDWP’s<br />

Energy Control Center Energy Management System (ECC-EMS) computers.<br />

Allocation: LADWP 59.5%<br />

Anaheim 17.7%<br />

Riverside 10.2%<br />

Pasadena 5.9%<br />

Burbank 4.5%<br />

Glendale 2.3%<br />

Interaction<br />

w/Other<br />

None.<br />

Transfer <strong>Path</strong>s:<br />

Contact Person:<br />

John Burnett<br />

Los Angeles Department of Water and Power<br />

P. O. Box 111, Room 1246<br />

111 North Hope Street<br />

Los Angeles, CA 90051<br />

(213) 367-1744<br />

(213) 367-3829 – fax<br />

john.burnett@ladwp.com<br />

PART VI Item 1-77

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!