12.11.2014 Views

Path Rating Catalog 2013 - Western Electricity Coordinating Council

Path Rating Catalog 2013 - Western Electricity Coordinating Council

Path Rating Catalog 2013 - Western Electricity Coordinating Council

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Revised January 2011<br />

27. Intermountain Power Project<br />

DC Line<br />

Accepted <strong>Rating</strong><br />

Existing <strong>Rating</strong><br />

Other<br />

Location:<br />

Definition:<br />

Transfer Limit:<br />

Critical<br />

Disturbance<br />

that limits the<br />

transfer<br />

capability:<br />

When:<br />

Line from Intermountain station in central Utah to Adelanto station in<br />

southern California (IPPDC)<br />

The IPPDC line is a ±500 kV DC bipole system. Power flow on the DC line<br />

is measured at the Intermountain end.<br />

Intermountain to Adelanto (NE-SW): 2400 MW<br />

Adelanto to Intermountain (SW-NE): 1400 MW<br />

Loss of the IPPDC bipole line.<br />

The non-simultaneous transfer rating was established by the Joint WECC<br />

Peer Review Group and <strong>Western</strong> Arizona Transmission Systems (WATS)<br />

Task Force. The WATS Task Force was comprised of members from the<br />

following companies:<br />

Arizona Public Service Company<br />

El Paso Electric Company<br />

DOE-<strong>Western</strong> Area Power Administration<br />

Imperial Irrigation District<br />

Los Angeles Department of Water and Power<br />

Nevada Power Company<br />

Public Service Company of New Mexico<br />

Salt River Project<br />

San Diego Gas and Electric Company<br />

Southern California Edison Company<br />

Southern California Public Power Authority<br />

Tucson Electric Power Company<br />

The Accepted <strong>Rating</strong> for NE-SW transfer of 2400MW was established in the<br />

LADWP sponsored <strong>Path</strong> 27 Project studies conducted within a WECC review<br />

Group that led to approval of the Accepted <strong>Rating</strong> Report. By the WECC<br />

PCC Chair’s letter dated October 03, 2007, <strong>Path</strong> 27 Upgrade <strong>Rating</strong> was<br />

granted Phase III status.<br />

The Existing <strong>Rating</strong> for SW-NE transfer of 1400MW was established in<br />

conjunction with the DOE Form IE-411 reporting in 1989. The SW-NE<br />

rating was established jointly by LADWP and PacifiCorp-Utah Power.<br />

Revised January 2011<br />

PART VI Item 1-76