Path Rating Catalog 2013 - Western Electricity Coordinating Council
Path Rating Catalog 2013 - Western Electricity Coordinating Council
Path Rating Catalog 2013 - Western Electricity Coordinating Council
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Revised February 2007<br />
26. Northern - Southern California<br />
Accepted <strong>Rating</strong><br />
Existing <strong>Rating</strong><br />
Other<br />
Location:<br />
Definition:<br />
Between PG&E and Southern California Edison<br />
Midway-Vincent #1 500kV line metered at Midway<br />
Midway-Vincent #2 500kV line metered at Midway<br />
Midway-Whirlwind 500kV line metered at Midway<br />
Transfer Limit: North to South: 4000MW (Other <strong>Rating</strong>) 1<br />
South to North:<br />
3000 MW<br />
Transfer limits are affected by generation and load levels between <strong>Path</strong> 15<br />
and Midway. North to south seasonal limits can vary from 900 to 4000 MW<br />
and south to north from 1400 to 2400 MW.<br />
Critical<br />
Disturbance<br />
that limits the<br />
transfer<br />
capability:<br />
Midway-Vincent #1 and #2 500 kV double-line outage, or Midway-Vincent<br />
#1 and Midway-Whirlwind 500kV double-line outage can overload the<br />
remaining <strong>Path</strong> 26 500 kV line and/or cause voltage criteria violation.<br />
When: North to south rating of 4000 MW was approved by WECC on May 5, 2006.<br />
The existing <strong>Path</strong> 26 RAS was upgraded and released for operation on June<br />
19, 2006 to support the north to south rating. (SCE and PG&E are currently<br />
in the process of initiating a redefinition of the path and reestablishing the<br />
existing path rating with the approved modification of the existing RAS, as<br />
discussed above.)<br />
South to north rating of 3,000 MW was approved by WECC on September<br />
26, 2011. There is no existing <strong>Path</strong> 26 RAS for south-to-north transfer at<br />
3,000 MW.<br />
System<br />
Conditions:<br />
Study Criteria:<br />
Remedial<br />
Actions<br />
Required:<br />
Formal<br />
Operating<br />
Procedure:<br />
North to south transfer was based on heavy summer and light spring<br />
conditions.<br />
South to north transfer was based on light winter conditions.<br />
All facilities loaded within normal ratings under normal system conditions.<br />
All facilities loaded within emergency ratings under outage conditions.<br />
The system meets the post transient voltage criteria.<br />
Fully meets NERC/WECC Planning Standards.<br />
Based on the nomogram curve designed for north to south flow between 3000<br />
and 3550 MW, the <strong>Path</strong> 26 RAS would trip up to 1400 MW of Midway area<br />
generation for loss of any two of the South of Midway 500 kV lines<br />
(Midway-Vincent #1, Midway-Vincent #2, and Midway-Whirlwind). For<br />
north to south flow between 3550 and 4000 MW, the <strong>Path</strong> 26 RAS would trip<br />
1400 MW of Midway generation and up to 600 MW load at SCE’s Rio<br />
Honda and/or Walnut Substations for the same 500 kV double-line outage.<br />
California ISO T-103, T-118A, T-120 and T-122.<br />
1 The rating of 4000 MW included Midway –Vincent #3, which has been replaced. This new path definition is going through the Three-<br />
Phase Process..<br />
PART VI Item 1-73