12.11.2014 Views

Path Rating Catalog 2013 - Western Electricity Coordinating Council

Path Rating Catalog 2013 - Western Electricity Coordinating Council

Path Rating Catalog 2013 - Western Electricity Coordinating Council

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Revised February 2007<br />

26. Northern - Southern California<br />

Accepted <strong>Rating</strong><br />

Existing <strong>Rating</strong><br />

Other<br />

Location:<br />

Definition:<br />

Between PG&E and Southern California Edison<br />

Midway-Vincent #1 500kV line metered at Midway<br />

Midway-Vincent #2 500kV line metered at Midway<br />

Midway-Whirlwind 500kV line metered at Midway<br />

Transfer Limit: North to South: 4000MW (Other <strong>Rating</strong>) 1<br />

South to North:<br />

3000 MW<br />

Transfer limits are affected by generation and load levels between <strong>Path</strong> 15<br />

and Midway. North to south seasonal limits can vary from 900 to 4000 MW<br />

and south to north from 1400 to 2400 MW.<br />

Critical<br />

Disturbance<br />

that limits the<br />

transfer<br />

capability:<br />

Midway-Vincent #1 and #2 500 kV double-line outage, or Midway-Vincent<br />

#1 and Midway-Whirlwind 500kV double-line outage can overload the<br />

remaining <strong>Path</strong> 26 500 kV line and/or cause voltage criteria violation.<br />

When: North to south rating of 4000 MW was approved by WECC on May 5, 2006.<br />

The existing <strong>Path</strong> 26 RAS was upgraded and released for operation on June<br />

19, 2006 to support the north to south rating. (SCE and PG&E are currently<br />

in the process of initiating a redefinition of the path and reestablishing the<br />

existing path rating with the approved modification of the existing RAS, as<br />

discussed above.)<br />

South to north rating of 3,000 MW was approved by WECC on September<br />

26, 2011. There is no existing <strong>Path</strong> 26 RAS for south-to-north transfer at<br />

3,000 MW.<br />

System<br />

Conditions:<br />

Study Criteria:<br />

Remedial<br />

Actions<br />

Required:<br />

Formal<br />

Operating<br />

Procedure:<br />

North to south transfer was based on heavy summer and light spring<br />

conditions.<br />

South to north transfer was based on light winter conditions.<br />

All facilities loaded within normal ratings under normal system conditions.<br />

All facilities loaded within emergency ratings under outage conditions.<br />

The system meets the post transient voltage criteria.<br />

Fully meets NERC/WECC Planning Standards.<br />

Based on the nomogram curve designed for north to south flow between 3000<br />

and 3550 MW, the <strong>Path</strong> 26 RAS would trip up to 1400 MW of Midway area<br />

generation for loss of any two of the South of Midway 500 kV lines<br />

(Midway-Vincent #1, Midway-Vincent #2, and Midway-Whirlwind). For<br />

north to south flow between 3550 and 4000 MW, the <strong>Path</strong> 26 RAS would trip<br />

1400 MW of Midway generation and up to 600 MW load at SCE’s Rio<br />

Honda and/or Walnut Substations for the same 500 kV double-line outage.<br />

California ISO T-103, T-118A, T-120 and T-122.<br />

1 The rating of 4000 MW included Midway –Vincent #3, which has been replaced. This new path definition is going through the Three-<br />

Phase Process..<br />

PART VI Item 1-73

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!