12.11.2014 Views

Path Rating Catalog 2013 - Western Electricity Coordinating Council

Path Rating Catalog 2013 - Western Electricity Coordinating Council

Path Rating Catalog 2013 - Western Electricity Coordinating Council

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

25. PacifiCorp/PG&E<br />

115 kV Interconnection<br />

Revised January <strong>2013</strong><br />

Accepted <strong>Rating</strong><br />

Existing <strong>Rating</strong><br />

Other<br />

Location: Southern Oregon/Northern California (Line 14)<br />

Definition:<br />

Sum of flow on Line 14, measured at Cascade.<br />

Transfer Limit: Winter Summer<br />

North to South: 100 MW * 80 MW<br />

South to North: 45 MW ** 45 MW **<br />

The thermal rating of this 115 kV line is 100/149 MVA Summer/Winter<br />

(397.5 ACSR conductor).<br />

Critical<br />

Disturbance<br />

that limits the<br />

transfer<br />

capability:<br />

When:<br />

System<br />

Conditions:<br />

Study Criteria<br />

* Due to load growth in the area, there are periods when the winter transfer<br />

limit may be reduced below 100 MW, sometimes as low as 80 MW.<br />

** The south to north non-simultaneous rating listed in the WECC Transfer<br />

Capability Diagram is 45 MW. This capability is rated under tie-line open<br />

south of phase shifter and is equivalent to the magnitude of PacifiCorp’s local<br />

area load.<br />

<strong>Path</strong> rating was established on April 19, 1984 with the publishing of the<br />

WECC progress report, by project owners.<br />

The powerflow and stability studies deriving the path rating, above, were<br />

conducted by PacifiCorp and PG&E.<br />

This interconnection operates in parallel with the California-Oregon Intertie<br />

(COI). In order to direct flow of the 100 MW south on Line 14, a<br />

75/100/125 MVA, 118 kV 0-60 degrees compensated phase shifter is<br />

installed at PacifiCorp’s Weed Junction substation, Weed Junction,<br />

California. This phase-shifting transformer regulates the flow of power,<br />

preventing power scheduled over it from flowing on the COI.<br />

The following stability simulations were made:<br />

A. Islanding Without the Line 14, 115 kV Tie<br />

This simulation assumes 3200 MW on the COI as well as 4163 MW on<br />

the Arizona to southern California path and indicates that minimum<br />

standards for stable operation can be achieved, complying with WECC<br />

criteria. Stability plot of the Devers 500 kV bus shows oscillations of<br />

increasing amplitude through the first 7-8 seconds, with decreasing<br />

amplitude thereafter.<br />

The minimum transient swing voltage was at the Devers 230 kV bus with<br />

81.7%. Use of the SDG&E’s Damping Coefficient Method demonstrates<br />

a 7.6% damping on this bus. Frequencies drop to 58.84 Hz minimum in<br />

California causing some under-frequency load shedding.<br />

PART VI Item 1-70

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!