Path Rating Catalog 2013 - Western Electricity Coordinating Council

Path Rating Catalog 2013 - Western Electricity Coordinating Council

Path Rating Catalog 2013 - Western Electricity Coordinating Council

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

24. PG&E - Sierra<br />

Revised February 2001<br />

Accepted <strong>Rating</strong><br />

Existing <strong>Rating</strong><br />

Other<br />

Location:<br />

Definition:<br />

Transfer Limit:<br />

Critical<br />

Disturbance<br />

that limits the<br />

transfer<br />

capability:<br />

When:<br />

System<br />

Conditions:<br />

Study Criteria:<br />

Remedial<br />

Actions<br />

Required:<br />

Formal<br />

Operating<br />

Procedure:<br />

Allocation:<br />

Interaction<br />

w/Other<br />

Transfer <strong>Path</strong>s:<br />

Between Northern California and Nevada<br />

Drum-Summit (2-115 kV lines)<br />

Spaulding-Summit (1-60 kV line)<br />

Sum of the flows on the following transmission lines:<br />

Line<br />

Metered Point<br />

Drum-Summit 1 115 kV<br />

Summit 1 115 kV bus<br />

Drum-Summit 2 115 kV<br />

Summit 2 115 kV bus<br />

Drum-Summit 60 kV<br />

Summit 60 kV bus<br />

160 MW West to East<br />

150 MW East to West<br />

Transfer limit may vary from 0-160 MW depending on generation and load in<br />

the Drum-Rio Oso-Goldhill area. East to west limit based on N. Tahoe loads<br />

and Cal Sub phase shifter.<br />

Loss of the Drum Powerhouse<br />

Loss of Drum-Rio Oso #1 (115 kV)<br />

Loss of Drum-Summit 1&2<br />

Goldhill-Placer #2 (115 kV)<br />

Halsey Jct-Newark #1 & #2 (between Drum and Placer)<br />

Heavy Summer<br />

Heavy Winter<br />

All facilities loaded within normal ratings under normal system conditions.<br />

All facilities loaded within emergency ratings under outage conditions.<br />

Fully meets WECC Reliability Criteria in effect at time rating was<br />

established.<br />

Open Drum-Summit lines.<br />

For NE/SE separation, opening of the PG&E-Sierra tie lines is required.<br />

Open Drum-Atlantic 60 kV line at Weimer.<br />

Sierra, PG&E<br />

Affected by flow at California-Oregon border.<br />

The flow on the Midpoint-Humboldt line affects the scheduling capability of<br />

this path.<br />

PART VI Item 1-67