Remedial<br />

Actions<br />

Required:<br />

Formal<br />

Operating<br />

Procedure:<br />

Allocation:<br />

A remedial action scheme is required to achieve the 2400 MW east to west<br />

rating. Multi-phase faults, SLG faults with delayed clearing, and multi-line<br />

outages on the Jim Bridger 345 kV lines require Jim Bridger unit(s) tripping.<br />

With all lines in service, Jim Bridger unit tripping is not required for SLG<br />

faults on the Jim Bridger 345 kV system. One of the Jim Bridger 345 kV<br />

shunt capacitors is normally on to reduce the reactive output of the Jim<br />

Bridger units so to increase reactive support during a disturbance. The Borah<br />

and Goshen shunt capacitors are normally off and held in reserve to be<br />

switched at the time of a disturbance for additional reactive support.<br />

Bridger West vs <strong>Path</strong> C South – North seasonal nomograms (Operating<br />

Procedure: PCC-005 <strong>Path</strong> C, South to North)<br />

The transfer capability of the path is allocated as follows:<br />

2400 MW East to West:<br />

Ownership Allocation<br />

IPC 800 MW (1/3) 774 MW<br />

PacifiCorp 1600 MW (2/3) 1626 MW (Remainder)<br />

Interaction<br />

w/Other<br />

Transfer <strong>Path</strong>s:<br />

Contact Person: Mark D. Hanson Craig Quist<br />

Idaho Power Company<br />

PacifiCorp<br />

P. O. Box 70 1407 West North Temple Suite 275<br />

Boise, ID 83707 Salt Lake City, UT 84116<br />

(208) 388-2253 (801) 220-4264<br />

(208) 388-6647 - fax (801) 220-2842- fax<br />

mhanson@idahopower.com craig.quist@pacificorp.com<br />