71. South of Allston<br />

Revised January <strong>2013</strong><br />

Accepted <strong>Rating</strong><br />

Existing <strong>Rating</strong><br />

Other<br />

Location:<br />

Definition:<br />

Transfer Limit:<br />

Critical<br />

Disturbance<br />

that limits the<br />

transfer<br />

capability:<br />

When:<br />

System<br />

Conditions:<br />

Study Criteria:<br />

Remedial<br />

Actions<br />

Required:<br />

Formal<br />

Operating<br />

Procedure:<br />

Allocation:<br />

Interaction<br />

w/Other<br />

Transfer <strong>Path</strong>s:<br />

Southwestern Washington/Northwestern Oregon<br />

Sum of the flows on the following lines:<br />

Line Owner Metered End<br />

Clatsop 230/115 kV BPA Clatsop<br />

Allston-Keeler 500 kV BPA Allston<br />

Allston-Rainier 115 kV BPA Allston<br />

Astoria Tap-Seaside 115 kV PAC Astoria Tap<br />

Merwin-View 115 kV PAC Merwin<br />

Trojan-Rivergate 230 kV PGE Trojan<br />

Trojan-St Marys 230 kV PGE Trojan<br />

Woodland Tap-Ross 230 kV BPA Ross<br />

Currently, per DSO 309, the SOL in the north to south direction is a dynamic<br />

limit and varies between 2935 and 3980 MW.<br />

The SOL in the south to north direction is a dynamic limit that adjusts in real<br />

time and the limit is 1115 MW.<br />

Allston-Keeler 500 kV line<br />

Keeler-Pearl 500 kV line<br />

Trojan-Rivergate 230 kV and Trojan-St Marys 230 kV line<br />

Allston-Trojan #1 and #2 230 kV lines<br />

Trojan –St Marys 230 kV and St Marys-Keeler 230 kV lines<br />

The path is limited for outages that cause thermal overloads<br />

SOL studies are completed on an annual basis.<br />

Heavy summer loadings<br />

Canada - NW – high north to south flow<br />

California - Oregon Intertie – high north to south flow<br />

Pacific DC Intertie – high north to south flow<br />

Upper Columbia generation high<br />

Lower Columbia generation low<br />

I-5 Corridor generation high<br />

BPA, PGE, PAC and WECC/NERC<br />

Generation dropping on available I-5 corridor thermal generation (Chehalis,<br />

Big Hanaford, and Fredrickson. Grays Harbor, Mint Farm, and Beaver)<br />

Generation ramping on Lewis River (Swift and Yale)<br />

Generation dropping in B.C. Hydro<br />

Generation dropping on Upper Columbia (Coulee and Chief Joseph)<br />

BPA Dispatcher Standing Order No. 309 (updated seasonally)<br />

All of the Capacity is allocated to BPA, PAC and PGE.<br />

None<br />