Revised February 2005<br />

61. Lugo - Victorville 500 kV Line<br />

Accepted <strong>Rating</strong><br />

Existing <strong>Rating</strong><br />

Other<br />

Location:<br />

Definition:<br />

500 kV transmission line from Victorville substation in LDWP’s service area<br />

to Lugo substation in SCE’s service area<br />

Line is owned independently from the midpoint of the line to the respective<br />

service areas of SCE and LDWP. Metered at Victorville 500 kV substation.<br />

Transfer Limit: Victorville to Lugo: 2400 MW<br />

Lugo to Victorville: 900 MW<br />

Critical<br />

Disturbance<br />

that limits the<br />

transfer<br />

capability:<br />

When:<br />

System<br />

Conditions:<br />

Study Criteria:<br />

Remedial<br />

Actions<br />

Required:<br />

Formal<br />

Operating<br />

Procedure:<br />

Allocation:<br />

Interaction<br />

w/Other<br />

Transfer <strong>Path</strong>s:<br />

Contact Person:<br />

The 2400 MW rating is limited by the loss of the Mohave-Lugo or Eldorado-<br />

Lugo 500 kV lines in SCE’s service territory. The 900 MW rating is limited<br />

due to thermal limitations on Inyokern-Searles 115 kV line under N-0<br />

conditions.<br />

The Victorville-Lugo rating was established in 2001 and the Lugo-Victorville<br />

rating was established in 1995.<br />

Victorville to Lugo flows are high during high IPPDC and high EOR/WOR<br />

flows. Lugo to Victorville flows are high with low flows on EOR/WOR and<br />

low flows on the IPPDC.<br />

WECC Reliability Criteria<br />

None<br />

Flows on Victorville-Lugo may be limited depending on flows across the<br />

Sylmar auto-transformer banks. A dynamic nomogram has also been put inplace<br />

to monitor the actual flows on Eldorado-Lugo, Mohave-Lugo, Palo<br />

Verde-Devers and Palo Verde-N. Gila lines such that the outage of any one of<br />

these lines will not load the Victorville-Lugo line above the emergency rating<br />

of 2600 MVA.<br />

The flows are allocated between LDWP, SCE, Anaheim and Riverside.<br />

Flow on this path is dependent on internal generation in SCE, and flows on<br />

IPPDC, EOR/WOR, Midway-Vincent 500 kV lines and north of Lugo paths.<br />

Steven E. Mavis<br />

Southern California Edison<br />

Three Innovation Way<br />

Pomona, CA 91768<br />

(909) 274-1587<br />

(909) 274-1601 - fax<br />

steven.mavis@sce.com<br />

John Burnett<br />

Los Angeles Dept. Of Water &<br />

Power<br />

P. O. Box 111, Room 1246<br />

111 N. Hope Street<br />

Los Angeles, CA 90051<br />

(213) 367-1744<br />

(213) 367-5132<br />

john.burnett@ladwp.com<br />

PART VI Item 1-164