61. Lugo - Victorville 500 kV Line<br />
Accepted <strong>Rating</strong><br />
Existing <strong>Rating</strong><br />
Other<br />
Location:<br />
Definition:<br />
500 kV transmission line from Victorville substation in LDWP’s service area<br />
to Lugo substation in SCE’s service area<br />
Line is owned independently from the midpoint of the line to the respective<br />
service areas of SCE and LDWP. Metered at Victorville 500 kV substation.<br />
Transfer Limit: Victorville to Lugo: 2400 MW<br />
Lugo to Victorville: 900 MW<br />
Critical<br />
Disturbance<br />
that limits the<br />
transfer<br />
capability:<br />
When:<br />
System<br />
Conditions:<br />
Study Criteria:<br />
Remedial<br />
Actions<br />
Required:<br />
Formal<br />
Operating<br />
Procedure:<br />
Allocation:<br />
Interaction<br />
w/Other<br />
Transfer <strong>Path</strong>s:<br />
Contact Person:<br />
The 2400 MW rating is limited by the loss of the Mohave-Lugo or Eldorado-<br />
Lugo 500 kV lines in SCE’s service territory. The 900 MW rating is limited<br />
due to thermal limitations on Inyokern-Searles 115 kV line under N-0<br />
conditions.<br />
The Victorville-Lugo rating was established in 2001 and the Lugo-Victorville<br />
rating was established in 1995.<br />
Victorville to Lugo flows are high during high IPPDC and high EOR/WOR<br />
flows. Lugo to Victorville flows are high with low flows on EOR/WOR and<br />
low flows on the IPPDC.<br />
WECC Reliability Criteria<br />
None<br />
Flows on Victorville-Lugo may be limited depending on flows across the<br />
Sylmar auto-transformer banks. A dynamic nomogram has also been put inplace<br />
to monitor the actual flows on Eldorado-Lugo, Mohave-Lugo, Palo<br />
Verde-Devers and Palo Verde-N. Gila lines such that the outage of any one of<br />
these lines will not load the Victorville-Lugo line above the emergency rating<br />
of 2600 MVA.<br />
The flows are allocated between LDWP, SCE, Anaheim and Riverside.<br />
Flow on this path is dependent on internal generation in SCE, and flows on<br />
IPPDC, EOR/WOR, Midway-Vincent 500 kV lines and north of Lugo paths.<br />
Steven E. Mavis<br />
Southern California Edison<br />
Three Innovation Way<br />
Pomona, CA 91768<br />
(909) 274-1587<br />
(909) 274-1601 - fax<br />
steven.mavis@sce.com<br />
John Burnett<br />
Los Angeles Dept. Of Water &<br />
Power<br />
P. O. Box 111, Room 1246<br />
111 N. Hope Street<br />
Los Angeles, CA 90051<br />
(213) 367-1744<br />
(213) 367-5132<br />
john.burnett@ladwp.com<br />
PART VI Item 1-164