12.11.2014 Views

Path Rating Catalog 2013 - Western Electricity Coordinating Council

Path Rating Catalog 2013 - Western Electricity Coordinating Council

Path Rating Catalog 2013 - Western Electricity Coordinating Council

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Revised February 1998<br />

58. Eldorado - Mead 230 kV Lines<br />

Accepted <strong>Rating</strong><br />

Existing <strong>Rating</strong><br />

Other<br />

Location:<br />

Near Boulder City in southern Nevada<br />

Definition: Flows on the Eldorado-Mead 230 kV transmission lines 1 and 2.<br />

Transfer Limit:<br />

Critical<br />

Disturbance<br />

that limits the<br />

transfer<br />

capability:<br />

1140 MW<br />

The 1140 MW rating is limited by the likely contingency (emergency)<br />

thermal rating of the conductor. The critical disturbance, for which the<br />

1140 MW rating is established, is outage of one of the two Eldorado-Mead<br />

230 kV lines.<br />

When: The 1140 MW rating was established in 1969.<br />

System<br />

Conditions:<br />

Study Criteria:<br />

Remedial<br />

Actions<br />

Required:<br />

Formal<br />

Operating<br />

Procedure:<br />

Power may flow westbound or eastbound in varying levels throughout the<br />

year primarily due to Mohave and Hoover power deliveries.<br />

WECC, SCE<br />

None<br />

None<br />

Allocation: Jointly owned by SCE (54.700%), NEVP (26.425%) and SRP (18.875%).<br />

Interaction None<br />

w/Other<br />

Transfer <strong>Path</strong>s:<br />

Contact Person: Steven E. Mavis<br />

Southern California Edison<br />

Three Innovation Way<br />

Pomona, CA 91768<br />

(909) 274-1587<br />

(909) 274-1601 - fax<br />

steven.mavis@sce.com<br />

PART VI Item 1-158