Created on 8/10/10 TABLE 1-1A: TOT3 SYSTEM INTACT LIMITS<br />

Home 2010-11 Heavy Winter<br />

2010-11 TOT3 Winter CPP: 66 MW<br />

System Intact<br />

DC TIES<br />

300 MW East to West 0 MW 300 MW West to East<br />

LRS 1140 MW (Net) a1 Stress 34 a2 Stress 37 a3 Stress 44<br />

Paw nee 777 MW (Net) TOT3 = 1609 MW TOT3 = 1507 MW TOT3 = 1376 MW<br />

(Outage Lar.Rivr-Story 345-kV line loaded (Outage Lar.Rivr-Story 345-kV line loaded (Outage Lar.Rivr-Story 345-kV line loaded<br />

Lar.Rivr-Ault 345-kV line to Lar.Rivr-Ault 345-kV line to Lar.Rivr-Ault 345-kV line to<br />

100% of its 956 MVA rating.) 100% of its 956 MVA rating.) 100% of its 956 MVA rating.)<br />

LRS 570 MW (Net) b1 Stress 41 b2 Stress 35 b3 Stress 33<br />

Paw nee 777 MW (Net) TOT3 = 1412 MW TOT3 = 1165 MW TOT3 = 854MW<br />

(Outage of Lar.Rivr Station Generator (Outage of Lar.Rivr-DaveJohn 230-kV line (Outage of Lar.Rivr-DaveJohn 230-kV line<br />

loaded DaveJohn-Lar.Rivr 230-kV line to loaded DaveJohn-Stegall 230-kV line to loaded DaveJohn-Stegall 230-kV line to<br />

its emergency rating) 100 % of 319 MVA rating) 100 % of 319 MVA rating)<br />

LRS 1140 MW (Net) c1 Stress 17 c2 Stress 34 c3 Stress 26<br />

Paw nee 280 MW (Net) TOT3 = 1588 MW TOT3 = 1546 MW TOT3 = 1299 MW<br />

(Outage Sidney-Spck loaded (Outage Lar.Rivr-Story 345-kV line loaded (Outage of Sidney-Stegall 230-kV line<br />

Peetz-Sterling 115-kV to Lar.Rivr-Ault 345-kV line to loaded Gering-McGrew 115-kV to 100%<br />

100% of normal 109 MVA rating) 100% of its 956 MVA rating.) of 109 MVA rating)<br />

LRS 570 MW (Net) d1 Stress 25 d2 Stress 31 d3 Stress 15<br />

Paw nee 280 MW (Net) TOT3 = 1277 MW TOT3 = 1183 MW TOT3 = 846 MW<br />

(Outage Sidney-Spck 230-kV loaded (Outage of Lar.Rivr-DaveJohn 230-kV line (Outage of Lar.Rivr-DaveJohn 230-kV line<br />

Peetz-Sterling 115-kV to loaded DaveJohn-Stegall 230-kV line to loaded DaveJohn-Stegall 230-kV line to<br />

100% of normal 109 MVA rating) 100 % of 319 MVA rating) 100 % of 319 MVA rating)<br />

jgriffit@wapa.gov Case Summary Report Calculate New TOT3 Limits WECC's "Accepted <strong>Rating</strong>" is