4 348<br />

<strong>Modulating</strong> <strong>control</strong> <strong>valve</strong> <strong>PN16</strong><br />

<strong>with</strong> <strong>magnetic</strong> <strong>actuator</strong><br />

for HTHW and steam,<br />

<strong>with</strong> positioning <strong>control</strong> and position feedback<br />

<strong>M2H</strong>...<strong>FY</strong>...N<br />

Control <strong>valve</strong> <strong>with</strong> <strong>magnetic</strong> <strong>actuator</strong> for modulating <strong>control</strong> in district heating<br />

systems and HTHW and steam applications<br />

• Fast positioning time (< 1 s)<br />

• High resolution (> 1 : 1000)<br />

• High rangeability<br />

• Closed when de-energised<br />

• With positioning <strong>control</strong> and position feedback<br />

• Low friction, robust and maintenance-free<br />

Use<br />

The <strong>M2H</strong>...<strong>FY</strong>...N <strong>valve</strong> types are through-port <strong>control</strong> <strong>valve</strong>s <strong>with</strong> a fixed <strong>magnetic</strong><br />

<strong>actuator</strong>. The <strong>actuator</strong> is equipped <strong>with</strong> connecting electronics for positioning <strong>control</strong><br />

and position feedback. At zero current the <strong>valve</strong>s are closed.<br />

The short positioning time, high resolution and high rangeability make these <strong>valve</strong>s ideal<br />

for proportional <strong>control</strong> of district heating stations and heating plant using HTHW and<br />

steam.<br />

The low-friction, robust and maintenance-free construction makes regular service<br />

unnecessary.<br />

Type summary<br />

Operating data<br />

q [mm 2 ]<br />

DN kvs PN Pmed 1.5 2.5 4.0<br />

Valve type [mm] [m 3 /h] [VA] [VA] L [m]<br />

<strong>M2H</strong>15<strong>FY</strong>06N 15 0.6 20 5 40 65 110<br />

<strong>M2H</strong>15<strong>FY</strong>15N 15 1.5 20 5 40 65 110<br />

<strong>M2H</strong>15<strong>FY</strong>N 15 3.0 20 5 40 65 110<br />

<strong>M2H</strong>20<strong>FY</strong>N 20 5.0 20 5 40 65 110<br />

<strong>M2H</strong>25<strong>FY</strong>N 25 8.0 20 5 40 65 110<br />

<strong>M2H</strong>32<strong>FY</strong>N 32 12 26 6 30 50 80<br />

<strong>M2H</strong>40<strong>FY</strong>N 40 20 40 10 20 30 50<br />

<strong>M2H</strong>50<strong>FY</strong>N 50 30 40 10 20 30 50<br />

Legend see page 2<br />

Siemens Building Technologies CA1N4348E / 11.1998<br />

Landis & Staefa Division 1/6


Legend :<br />

PN = Nominal power<br />

Pmed = Mean operating power<br />

kvs = Flow rate to VDI/VDE2173, tolerance ±10 %<br />

q = Cross section of AC 24 V or DC 20 V cable (Cu)<br />

L = Max. cable length. With 4-wire connections, the maximum length of a separate 1.5 mm 2 Cu<br />

<strong>control</strong> signal cable may be extended to 200 m.<br />

Ordering<br />

The <strong>valve</strong>s are supplied complete <strong>with</strong> the <strong>magnetic</strong> <strong>actuator</strong> and the terminal housing.<br />

The Z200/... damping device can be ordered on request: see 'Accessories'.<br />

When placing an order, please specify the quantity, product description and type code.<br />

Example:<br />

1 <strong>control</strong> <strong>valve</strong> <strong>M2H</strong>25<strong>FY</strong>N and 1 damping device Z200/32<br />

Technical /<br />

Mechanical design<br />

The <strong>control</strong> signal is converted in the terminal housing into a phase cut signal which<br />

generates a <strong>magnetic</strong> field in the coil. This causes the only moving part, the armature, to<br />

change its position in accordance <strong>with</strong> the interacting forces (<strong>magnetic</strong> field, counterspring,<br />

hydraulics etc.). The armature responds rapidly to any change in signal, transferring<br />

the corresponding movement directly to the <strong>control</strong> disc, enabling fast changes in<br />

load to be corrected quickly and accurately.<br />

The <strong>valve</strong> position is measured continuously. Any disturbance in the system is rapidly<br />

corrected by the internal positioning <strong>control</strong>ler, which ensures that the <strong>control</strong> signal and<br />

the <strong>valve</strong> stroke are exactly proportional, and also provides a feedback signal indicating<br />

the <strong>valve</strong> position.<br />

Stroke [%]<br />

100<br />

94.0004<br />

80<br />

60<br />

40<br />

20<br />

0<br />

0 2<br />

4<br />

6<br />

8<br />

10<br />

Control signal [V]<br />

If the power is switched off or fails, the <strong>valve</strong> is automatically closed by the force of the<br />

spring.<br />

The <strong>valve</strong> stem is sealed <strong>with</strong> a maintenance-free O-ring gland.<br />

See sheet 4028 for a detailed description of operation.<br />

Manual adjustment<br />

Accessories<br />

The <strong>control</strong> path can be opened mechanically to between 0 and approximately 90 %, by<br />

turning the handwheel clockwise. The manual adjustment facility can also be used as a<br />

mechanical method of low limit <strong>control</strong>, i.e. the <strong>valve</strong> will exercise its normal <strong>control</strong><br />

function between the manually-set position and the 100 % open position. For full-stroke<br />

automatic <strong>control</strong>, the handwheel must be set to 0 (the anticlockwise end-stop).<br />

Z200/... Damping device to extend the closing time from


Sizing<br />

Water flow chart<br />

Flow / pressure differential relationship.<br />

kvs signifies the volume of water V in m 3 /h, which flows through the open <strong>valve</strong> at a<br />

pressure differential ∆pv of 100 kPa (1 bar).<br />

See sheet 4023 for notes on calculating the value of kvs.<br />

[m 3 /h]<br />

.<br />

V<br />

9I666E<br />

[l / s]<br />

100<br />

70<br />

50<br />

40<br />

30<br />

20<br />

10<br />

7<br />

5<br />

4<br />

3<br />

2<br />

1<br />

0,7<br />

0,5<br />

0,4<br />

0,3<br />

0,2<br />

<strong>M2H</strong>..<strong>FY</strong>..N<br />

VS<br />

DN50 k 30<br />

VS DN40 k 20<br />

VS DN32 k 12<br />

VS DN25 k 8<br />

VS DN20 k 5<br />

VS DN15 k 3<br />

VS DN15 k 1 ,5<br />

DN15 VS<br />

k 0 ,6<br />

20<br />

10<br />

5<br />

4<br />

3<br />

2<br />

7<br />

1<br />

0,7<br />

0,5<br />

0,4<br />

0,3<br />

0,2<br />

0,1<br />

0,07<br />

0,05<br />

10<br />

20 30 50 70 100<br />

200 300 500<br />

700<br />

1000<br />

[kPa]<br />

0,1<br />

0,2 0,3 0,5 0,7 1 2 3 5 7<br />

10<br />

[b ar]<br />

p v<br />

Saturated steam flow chart<br />

9I667E<br />

p v<br />

p 100 [ ]<br />

1<br />

<strong>M2H</strong>..<strong>FY</strong>..N<br />

b<br />

a<br />

k VS<br />

0,6<br />

k VS<br />

1 ,5<br />

k VS<br />

3<br />

k VS<br />

5<br />

k VS<br />

8<br />

k VS<br />

1 2<br />

k VS<br />

2 0<br />

k VS<br />

3 0<br />

0,42<br />

0,30<br />

0,20<br />

0,15<br />

0,10<br />

0,05<br />

100 200 300 500 1000 [kPa]<br />

1 2 3 5 7 10 [bar]<br />

p 1<br />

3 4 5 7 10 1<br />

2 3 4 5 7 10 2 2 3 4 5 7 10 3 2 3<br />

[kg/h]<br />

.<br />

m<br />

Mounting notes<br />

Two sets of mounting instructions are enclosed <strong>with</strong> the <strong>valve</strong>: Ref. 35640 (<strong>valve</strong>) and<br />

Ref. 35677 (terminal housing).<br />

Warning :<br />

Always disconnect the power before fitting or removing the terminal<br />

housing. The terminal housing is calibrated and matched to the <strong>actuator</strong>,<br />

and should be replaced only by qualified personnel.<br />

– A fine mesh strainer installed on the inlet side of the <strong>valve</strong> is essential to prevent the<br />

ingress of grit.<br />

– Vertical to horizontal mounting: Protection standard IP31. The <strong>valve</strong> must not be<br />

suspended below the horizontal.<br />

– The <strong>actuator</strong> must not be lagged.<br />

– For special information on use in steam applications, see sheet 4026.<br />

Siemens Building Technologies CA1N4348E / 11.1998<br />

Landis & Staefa Division 3/6


Recommendation<br />

Water systems should be cleaned, flushed and treated in accordance <strong>with</strong> current good<br />

practice, as described, for example, in BSRIA Application Guides AG 8/91 and AG2/93.<br />

For other relevant information, see also CIBSE Guide B (Section 7).<br />

Technical data<br />

Electrical interface:<br />

Only admissisble <strong>with</strong> low voltage (SELV, PELV)<br />

Supply voltage<br />

AC 24 V, 50/60 Hz<br />

– Max. voltage tolerance +15/–10 %<br />

Nominal power See table 'Operating data' page 1<br />

Control signal<br />

DC 0 ...10 V or DC 4 ... 20 mA<br />

Position feedback (output signal) DC 0 ...10 V = 0 ...100 % stroke<br />

– Max. load 1.5 mA<br />

– Accuracy ± 3 % of full scale<br />

Nominal pressure<br />

<strong>PN16</strong><br />

Operating pressure p e max:<br />

Water up to 120 °C<br />

1.6 MPa (16 bar)<br />

Above 120 °C<br />

1.3 MPa (13 bar)<br />

Saturated steam<br />

0.9 MPa ( 9 bar)<br />

Pressure differential ∆p v max 1.0 MPa (10 bar)<br />

Leakage at ∆p v = 0.1 MPa (1 bar) Max. 0.05 % k vs (to VDE/VDI2174)<br />

Temperature of medium 2 ...180 °C<br />

Valve characteristic (stroke, k v ) Linear, optimised in low opening range<br />

Resolution ∆H / H100 > 1 : 1000 (H = Stroke)<br />

Type of operation<br />

<strong>Modulating</strong><br />

Manual adjustment<br />

Up to max. 90 %, depending on DN<br />

Position when de-energised Closed<br />

Orientation<br />

Upright to horizontal<br />

Positioning time *)<br />

< 1 s<br />

Materials:<br />

Housing<br />

Spheroidal graphite cast iron (GGG40.3)<br />

Seat / inner <strong>valve</strong><br />

CrNi steel<br />

Valve stem seal<br />

EPDM (O ring)<br />

Connection terminals<br />

Screw terminals for 4 mm2 wire<br />

Protection standard<br />

Upright to horizontal mounting IP31 to IEC529<br />

Ambient temperature 2 ... 50 °C<br />

Weight (incl. packaging) See table 'Dimensions' on page 6<br />

Conformity<br />

Meets the requirements for CE marking<br />

*) The <strong>valve</strong> can be fitted <strong>with</strong> a Z200/... damping device to achieve a slower closing time of 10 ... 30 s.<br />

Internal diagram<br />

NS = system ground<br />

LS ~<br />

1<br />

G<br />

+<br />

AC 24 V<br />

2<br />

–<br />

NS<br />

T<br />

M<br />

60365<br />

Block diagram of<br />

signal converter<br />

Input DC 0 ...10 V<br />

Output DC 4 ... 20 mA<br />

3<br />

5<br />

R<br />

T<br />

+<br />

–<br />

V<br />

V<br />

E<br />

Q<br />

Position<br />

transducer<br />

Output DC 0 ...10 V<br />

4<br />

Position-feedback electronics<br />

<strong>with</strong> base/span adjustment<br />

U<br />

Key to block diagram<br />

E Phase cut converter<br />

G Bridge rectifier<br />

M Magnetic <strong>valve</strong><br />

Q Phase cut output<br />

R<br />

T<br />

U<br />

V<br />

Input resistor 50 k ohms<br />

Voltage / current converter<br />

(load on 350 ohms to NS)<br />

Position / voltage converter<br />

Differential amplifier<br />

CA1N4348E / 11.1998<br />

Siemens Building Technologies<br />

4/6 Landis & Staefa Division


Connection<br />

terminals<br />

Warning :<br />

If the <strong>control</strong>ler and the <strong>valve</strong> receive their supply from a separate source,<br />

the <strong>valve</strong> transformer must not be earthed on the secondary side.<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

40555B<br />

~<br />

⊥<br />

TE<br />

AC 24 V supply<br />

Common<br />

Input DC 0 ...10 V<br />

Output DC 0 ...10 V<br />

Input DC 4 ... 20 mA<br />

Connection<br />

diagrams<br />

• <strong>with</strong> DESIGO 30<br />

• <strong>with</strong> INTEGRAL RS<br />

– refer to manual R21<br />

– refer to manual K21<br />

• <strong>with</strong> MULTIREG<br />

Warning :<br />

The T2 transformer must not be earthed on the secondary side and<br />

should be suitably fused.<br />

T1<br />

T2<br />

AC 24 V<br />

AC 24 V<br />

RPR1<br />

<strong>M2H</strong>...<strong>FY</strong>...N<br />

50243en<br />

AC 24 V<br />

GND<br />

Output DC 0 ...10 V<br />

Input DC 0 ...10 V<br />

1<br />

2<br />

3<br />

15<br />

9<br />

1)<br />

Valve position indication<br />

DC 0 ...10 V = 0 ...10 %<br />

U<br />

1)<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

~ AC 24 V Supply<br />

Common<br />

Input DC 0 ..10 V<br />

Output DC 0 ..10 V<br />

T E<br />

• <strong>with</strong> other <strong>control</strong>lers<br />

(output DC 0 ...10 V)<br />

T2<br />

AC 24 V<br />

<strong>M2H</strong>...<strong>FY</strong>...N<br />

50244en<br />

Output DC 0 ...10 V<br />

Valve position indication<br />

DC 0 ...10 V = 0 ...100 %<br />

1)<br />

U<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

~<br />

T E<br />

AC 24 V Supply<br />

Common<br />

Input DC 0 ...10 V<br />

Output DC 0 ...10 V<br />

• <strong>with</strong> other <strong>control</strong>lers<br />

(output DC 4... 20 mA)<br />

T2<br />

AC 24 V<br />

<strong>M2H</strong>...<strong>FY</strong>...N<br />

50996en<br />

Output DC 4 ... 20 mA<br />

Valve position indication<br />

DC 0 ...10 V = 0 ...100 %<br />

1)<br />

U<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

~ AC 24 V Supply<br />

Common<br />

Output DC 0 ... 10 V<br />

Input DC 4 ... 20 mA<br />

T E<br />

1) only if needed<br />

Siemens Building Technologies CA1N4348E / 11.1998<br />

Landis & Staefa Division 5/6


Application<br />

examples<br />

Examples of installation in straight-through applications (principles only, <strong>with</strong>out<br />

installation-specific details)<br />

9H808 A<br />

9H807 A<br />

D<br />

E<br />

D : District heating (supply heating) system, indirect connection<br />

E : District heating (supply heating) system, directly connected to water-heating system.<br />

Dimensions<br />

All dimensions in mm<br />

940224<br />

min.<br />

100<br />

ø 40<br />

F<br />

ø E<br />

H<br />

Cable connection max. 2 x ø 11,8<br />

b<br />

ø d<br />

1 2<br />

ø k<br />

ø D<br />

Flange dimensions to DIN2533, <strong>PN16</strong><br />

DN<br />

L<br />

Valve type L ø D ø d b ø k H ø E F W<br />

<strong>M2H</strong>15<strong>FY</strong>...N 130 95 4x14 14 65 318 80 84 7.3<br />

<strong>M2H</strong>20<strong>FY</strong>N 150 105 4x14 16 75 320 80 84 8.3<br />

<strong>M2H</strong>25<strong>FY</strong>N 160 115 4x14 16 85 338 80 84 9.3<br />

<strong>M2H</strong>32<strong>FY</strong>N 180 140 4x18 18 100 373 100 94 14.3<br />

<strong>M2H</strong>40<strong>FY</strong>N 200 150 4x18 18 110 434 100 94 16.8<br />

<strong>M2H</strong>50<strong>FY</strong>N 230 165 4x18 20 125 518 125 108 27.0<br />

W = Weight (incl. packaging) in kg<br />

© 1998 Siemens Building Technologies Ltd.<br />

CA1N4348E / 11.1998<br />