Transition Plan


Report #UCR P5308 South Locker Room Concession Stand<br />

Report<br />

Name<br />

Item/Location<br />

Barrier<br />

(noted feature, item or area does not meet the<br />

new construction criteria detailed below)<br />

Action Priority Target<br />

Date<br />

Estimated<br />

Cost<br />

Interim<br />

Solution<br />

Action<br />

Completion<br />

Date<br />

UCR P5308 1-Doors: North Side<br />

South Entrance to the South<br />

Locker Locker Rooms.<br />

Room &<br />

Concession<br />

Stand<br />

The international symbol of accessibility is<br />

posted at all primary entrances.<br />

Post a sign/decal displaying<br />

the "International Symbol of<br />

Accessibility" at the primary<br />

entrance.<br />

1 $24.51<br />

UCR P5308 3-Floors and Levels:<br />

South Ground Level at the<br />

Locker South Locker Rooms.<br />

Room & [Five carpets / mats.]<br />

Concession<br />

Stand<br />

Carpets or carpet tiles are securely attached<br />

and do not exceed 1/2" in height. Carpet's<br />

exposed edges are fastened to floor surfaces<br />

and have trim along entire length.<br />

Secure loose doormat. 1 $1,225.03<br />

UCR P5308 4-Signage: Ground<br />

South Level at the South<br />

Locker Locker Rooms. [No<br />

Room & signage.]<br />

Concession<br />

Stand<br />

Permanent I.D. signs, when provided, are<br />

installed on the wall adjacent to the latch side of<br />

the door NOTE: At double leaf doors, and when<br />

there is no room on the latch side, signs shall<br />

be placed on the nearest adjacent wall,<br />

preferably on the right.<br />

Install permanent ID sign to<br />

latch side of door.<br />

1 $551.26<br />

UCR P5308 5-Visual/Audible Alarms:<br />

South Ground Level at the<br />

Locker South Locker Rooms.<br />

Room & [Three rooms without<br />

Concession fire alarms.]<br />

Stand<br />

The alarm is integrated into the building or<br />

facility alarm system.<br />

Review the entire alarm<br />

system.<br />

1 $7,115.62<br />

UCR P5308 9-Identification Symbols,<br />

South Restrooms: Men's<br />

Locker Restroom Adjacent to<br />

Room & the Gym Door at the<br />

Concession South Locker Rooms.<br />

Stand<br />

Door mounted signage: Men's - Equilateral<br />

triangle with 12" sides, 1/4" thick with the vertex<br />

pointing up. The triangle symbol contrasts with<br />

the door, light on dark background or dark on<br />

light background. Wall mounted signage:<br />

Symbol of accessibility is mounted on wall sign<br />

adjacent to latch side of door [ADAAG 703.6.1 &<br />

CBC 1117B.5.5 Item 4 Pictograms shall have a<br />

field height of 6" ADAAG 703.6.1 Characters<br />

and Braille shall not be located in the pictogram<br />

field].<br />

Install door-mounted sign on<br />

single door. Install wallmounted<br />

sign at single<br />

entrance.<br />

3 $367.51<br />

6/1/2012 Page 1 of 3


Report #UCR P5308 South Locker Room Concession Stand<br />

Report<br />

Name<br />

Item/Location<br />

Barrier<br />

(noted feature, item or area does not meet the<br />

new construction criteria detailed below)<br />

Action Priority Target<br />

Date<br />

Estimated<br />

Cost<br />

Interim<br />

Solution<br />

Action<br />

Completion<br />

Date<br />

UCR P5308 10-Multiple<br />

South Accommodation Toilets:<br />

Locker Men's Restroom<br />

Room & Adjacent to the Gym<br />

Concession Door at the South<br />

Stand Locker Rooms. [No<br />

accessible stall. Provide<br />

an accessible stall.]<br />

60" minimum width of stall [ADAAG 604.8.1.4<br />

toe clearances - The front partition and at least<br />

one side partition shall provide a toe clearance<br />

of 9 inches minimum above the finish floor and<br />

6 inches deep minimum beyond the<br />

compartment side face of the partition exclusive<br />

of partition support members]. 18" betwen<br />

centerline of water closet and side wall or<br />

partition [ADAAG 604.2 16" - 18" to centerline of<br />

water closet].. 32" minimum from side of water<br />

closet to opposite wall or partition. 42" minimum<br />

from centerline of water closet to opposite wall<br />

or partition.<br />

Requires<br />

engineering/architectural<br />

evaluation. Provide major<br />

renovation (including moving<br />

plumbing locations and walls).<br />

3 $41,270.62<br />

UCR P5308 11-Lavatories: Men's<br />

South Restroom Adjacent to<br />

Locker the Gym Door at the<br />

Room & South Locker Rooms.<br />

Concession<br />

Stand<br />

18" minimum from center of fixture to side wall<br />

or partition. 34" max. height to rim or counter<br />

above floor surface. Drain and piping is<br />

insulated or configured to prevent contact.<br />

Relocate existing lavatory.<br />

Insulate pipes under lavatory.<br />

3 $3,091.26<br />

UCR P5308 12-Urinals: Men's<br />

South Restroom Adjacent to<br />

Locker the Gym Door at the<br />

Room & South Locker Rooms.<br />

Concession<br />

Stand<br />

17" maximum urinal rim height above the<br />

finished floor. 14" minimum projection and 17"<br />

maximum projection from the wall. 44"<br />

maximum height to flush valve above finished<br />

floor.<br />

Replace with accessible urinal. 3 $3,185.07<br />

UCR P5308 13-Accessories: Men's<br />

South Restroom Adjacent to<br />

Locker the Gym Door at the<br />

Room & South Locker Rooms.<br />

Concession<br />

Stand<br />

40" max. height to all other fixtures (i.e., soap<br />

dispensers, towels, toilet seat covers, auto<br />

dryers, sanitary napkins, waste recepatacles,<br />

etc.).<br />

Lower the paper towel<br />

dispenser. Lower the soap<br />

dispenser.<br />

3 $245.01<br />

UCR P5308 14-Showers - (roll in<br />

South compartment): Men's<br />

Locker Restroom Adjacent to<br />

Room & the Gym Door at the<br />

Concession South Locker Rooms.<br />

Stand [No accessible stall.]<br />

Shower seat is folding and is on wall adjacent to<br />

controls.<br />

Requires<br />

engineering/architectural<br />

evaluation. Install compliant<br />

seat.<br />

1 $7,483.13<br />

6/1/2012 Page 2 of 3


Report #UCR P5308 South Locker Room Concession Stand<br />

Report<br />

Name<br />

Item/Location<br />

Barrier<br />

(noted feature, item or area does not meet the<br />

new construction criteria detailed below)<br />

Action Priority Target<br />

Date<br />

Estimated<br />

Cost<br />

Interim<br />

Solution<br />

Action<br />

Completion<br />

Date<br />

UCR P5308 17-Clear Space at<br />

South Doors: Lounge Adjacent<br />

Locker to the Gym at the South<br />

Room & Locker Rooms.<br />

Concession<br />

Stand<br />

UCR P5308 18-Controls, Operating<br />

South Mechanisms & Vending<br />

Locker Machines.: Lounge<br />

Room & Adjacent to the Gym at<br />

Concession the South Locker<br />

Stand Rooms. [Lockers.<br />

Replace hardware with<br />

an accessible one.]<br />

Minimum strike side clearance on PULL side of<br />

door: 18" wide x 60" depth at interior doors,<br />

front approach.<br />

Controls and operating mechanisms (handles,<br />

coin slots, openings, buttons, etc.) are operable<br />

with one hand and do not require tight grasping,<br />

pinching or twisting of the wrist to operate.<br />

Relocate furniture to provide<br />

clear space. University staff<br />

shall be instructed to place and<br />

maintain the placement of<br />

furniture to provide a clear<br />

path of travel and avoid the<br />

obstruction of accessible<br />

required clear spaces.<br />

Replace door hardware with<br />

compliant hardware.<br />

1M $61.25<br />

1 $477.76<br />

UCR P5308 20-Sales and Service<br />

South Counters: Concession<br />

Locker Stands at the South<br />

Room & Locker Rooms.<br />

Concession<br />

Stand<br />

A portion of the counter is a minimum of 36" in<br />

length, at a height between 28" - 34" above the<br />

floor and;<br />

Provide an auxiliary counter<br />

with a maximum height of 34".<br />

2 $1,225.03<br />

Grand Total $66,323.06<br />

6/1/2012 Page 3 of 3


Cost Report


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5308 South Locker Room & Concession Stand in Riverside, CA<br />

900 University Avenue Qty Unit<br />

Sub<br />

Contractor<br />

Sub<br />

Total<br />

(10%)<br />

Concealed<br />

Conditions<br />

(12.5%)<br />

Security<br />

Conditions<br />

(15%)<br />

General<br />

Conditions<br />

Total<br />

1. Doors - North Side Entrance to the South Locker Rooms.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Post a sign/decal displaying the ”International Symbol of Accessibility”<br />

at the primary entrance.<br />

1 ea. $17.22 $17.22 $18.94 $21.31 $24.51 $24.51<br />

TOTAL EST: $24.51<br />

3. Floors and Levels - Ground Level at the South Locker Rooms.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Secure loose doormat. 5 ea. $172.16 $860.80 $946.88 $1,065.24 $1,225.03 $1,225.03<br />

TOTAL EST: $1,225.03<br />

4. Signage - Ground Level at the South Locker Rooms.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install permanent ID sign to latch side of door. 3 ea. $129.12 $387.36 $426.10 $479.36 $551.26 $551.26<br />

TOTAL EST: $551.26<br />

5. Visual/Audible Alarms - Ground Level at the South Locker Rooms.<br />

Priority: 0<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62<br />

TOTAL EST: $7,115.62<br />

9. Identification Symbols, Restrooms - Men’s Restroom Adjacent to the Gym Door at the South Locker Rooms.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install door-mounted sign on single door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />

Install wall-mounted sign at single entrance. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />

TOTAL EST: $367.50<br />

Page 1 of 3


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5308 South Locker Room & Concession Stand in Riverside, CA<br />

900 University Avenue Qty Unit<br />

Sub<br />

Contractor<br />

Sub<br />

Total<br />

(10%)<br />

Concealed<br />

Conditions<br />

(12.5%)<br />

Security<br />

Conditions<br />

(15%)<br />

General<br />

Conditions<br />

Total<br />

10. Multiple Accommodation Toilets - Men’s Restroom Adjacent to the Gym Door at the South Locker Rooms.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62<br />

Provide major renovation (including moving plumbing locations 75 s.f. $320.00 $24,000.00 $26,400.00 $29,700.00 $34,155.00 $34,155.00<br />

and walls).<br />

TOTAL EST: $41,270.62<br />

11. Lavatories - Men’s Restroom Adjacent to the Gym Door at the South Locker Rooms.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Relocate existing lavatory. 1 ea. $2,000.00 $2,000.00 $2,200.00 $2,475.00 $2,846.25 $2,846.25<br />

Insulate pipes under lavatory (or sink when applicable). 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />

TOTAL EST: $3,091.26<br />

12. Urinals - Men’s Restroom Adjacent to the Gym Door at the South Locker Rooms.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Replace/Install urinal. 1 ea. $2,238.08 $2,238.08 $2,461.89 $2,769.63 $3,185.07 $3,185.07<br />

TOTAL EST: $3,185.07<br />

13. Accessories - Men’s Restroom Adjacent to the Gym Door at the South Locker Rooms.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Relocate the paper towel dispenser / hand dryer. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />

Relocate the soap dispenser. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />

TOTAL EST: $245.02<br />

14. Showers - (roll in compartment) - Men’s Restroom Adjacent to the Gym Door at the South Locker Rooms.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62<br />

Install compliant seat. 1 ea. $258.24 $258.24 $284.06 $319.57 $367.51 $367.51<br />

TOTAL EST: $7,483.13<br />

Page 2 of 3


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5308 South Locker Room & Concession Stand in Riverside, CA<br />

900 University Avenue Qty Unit<br />

Sub<br />

Contractor<br />

Sub<br />

Total<br />

(10%)<br />

Concealed<br />

Conditions<br />

(12.5%)<br />

Security<br />

Conditions<br />

(15%)<br />

General<br />

Conditions<br />

Total<br />

17. Clear Space at Doors - Lounge Adjacent to the Gym at the South Locker Rooms.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Relocate furniture to provide clear space. 1 ea. $43.04 $43.04 $47.34 $53.26 $61.25 $61.25<br />

TOTAL EST: $61.25<br />

18. Controls, Operating Mechanisms & Vending Machines. - Lounge Adjacent to the Gym at the South Locker Rooms.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Replace door hardware with compliant hardware. 1 ea. $335.71 $335.71 $369.28 $415.44 $477.76 $477.76<br />

TOTAL EST: $477.76<br />

20. Sales and Service Counters - Concession Stands at the South Locker Rooms.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Lower 36” wide counter section or provide an auxiliary counter<br />

with a maximum height of 34”.<br />

1 ea. $860.80 $860.80 $946.88 $1,065.24 $1,225.03 $1,225.03<br />

TOTAL EST: $1,225.03<br />

REPORT TOTALS: $46,603.81 $51,264.19 $57,672.21 $66,323.04 $66,323.04<br />

Page 3 of 3


Survey


Americans with Disabilities Act of 1990<br />

Site Assessment Report<br />

Report: UCR P5308 South<br />

Locker Room & Concession<br />

Stand<br />

900 University Avenue<br />

Riverside, CA 92521<br />

Inspection Date: 08/17/2009<br />

Prepared for:<br />

University of California at Riverside<br />

Prepared by:<br />

National Access Consultants, LLC<br />

2321 Abbot Kinney Blvd. Suite 200<br />

Venice, California 90291<br />

(805)497-6116


Contents<br />

1. Doors - North Side Entrance to the South Locker Rooms. . . . . . . . . . . . . . . . . . . . . . . . . 1<br />

2. Clear Space at Doors - North Side Entrance to the South Locker Rooms. . . . . . . . . . . . . . . . 3<br />

3. Floors and Levels - Ground Level at the South Locker Rooms. . . . . . . . . . . . . . . . . . . . . . 5<br />

4. Signage - Ground Level at the South Locker Rooms. . . . . . . . . . . . . . . . . . . . . . . . . . . . 6<br />

5. Visual/Audible Alarms - Ground Level at the South Locker Rooms. . . . . . . . . . . . . . . . . . . 7<br />

6. Electrical Controls & Receptacles/Fire Alarm Boxes - Gym Room (Northeast End) at the South Locker<br />

Rooms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8<br />

7. Doors - Men’s Restroom Adjacent to the Gym Door at the South Locker Rooms. . . . . . . . . . . 10<br />

8. Clear Space at Doors - Men’s Restroom Adjacent to the Gym Door at the South Locker Rooms. . 12<br />

9. Identification Symbols, Restrooms - Men’s Restroom Adjacent to the Gym Door at the South Locker<br />

Rooms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14<br />

10. Multiple Accommodation Toilets - Men’s Restroom Adjacent to the Gym Door at the South Locker<br />

Rooms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15<br />

11. Lavatories - Men’s Restroom Adjacent to the Gym Door at the South Locker Rooms. . . . . . . . . 16<br />

12. Urinals - Men’s Restroom Adjacent to the Gym Door at the South Locker Rooms. . . . . . . . . . . 18<br />

13. Accessories - Men’s Restroom Adjacent to the Gym Door at the South Locker Rooms. . . . . . . . 19<br />

14. Showers - (roll in compartment) - Men’s Restroom Adjacent to the Gym Door at the South Locker<br />

Rooms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20<br />

15. Electrical Controls & Receptacles/Fire Alarm Boxes - Men’s Restroom Adjacent to the Gym Door at<br />

the South Locker Rooms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21<br />

16. Doors - Lounge Adjacent to the Gym at the South Locker Rooms. . . . . . . . . . . . . . . . . . . . 22<br />

17. Clear Space at Doors - Lounge Adjacent to the Gym at the South Locker Rooms. . . . . . . . . . . 24<br />

18. Controls, Operating Mechanisms & Vending Machines. - Lounge Adjacent to the Gym at the South<br />

Locker Rooms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26<br />

19. Electrical Controls & Receptacles/Fire Alarm Boxes - Lounge Adjacent to the Gym at the South<br />

Locker Rooms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27<br />

20. Sales and Service Counters - Concession Stands at the South Locker Rooms. . . . . . . . . . . . . . 28


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5308 South Locker Room & Concession Stand in Riverside, CA<br />

900 University Avenue<br />

1. Doors - North Side Entrance to the South Locker Rooms.<br />

Memo:<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

32” minimum clear width of doorway.<br />

5 lb. maximum pressure to operate exterior doors.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

The international symbol of accessibility is posted at all primary entrances.<br />

Recommendation:<br />

Post a sign/decal displaying the ”International Symbol of Accessibility” at the primary entrance.<br />

Photo #UCR P5308 South Locker Room & Concession Stand-1-1 (originally 0001)<br />

1


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5308 South Locker Room & Concession Stand in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5308 South Locker Room & Concession Stand-1-2 (originally 0002)<br />

2


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5308 South Locker Room & Concession Stand in Riverside, CA<br />

900 University Avenue<br />

2. Clear Space at Doors - North Side Entrance to the South Locker<br />

Rooms.<br />

Memo:<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

60” min. clear space in direction of door swing.<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Minimum strike side clearance on PULL side of door: 24” exterior doors.<br />

Minimum strike side clearance on PUSH side of door: 0”.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5308 South Locker Room & Concession Stand-2-1 (originally 0003)<br />

3


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5308 South Locker Room & Concession Stand in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5308 South Locker Room & Concession Stand-2-2 (originally 0004)<br />

4


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5308 South Locker Room & Concession Stand in Riverside, CA<br />

900 University Avenue<br />

3. Floors and Levels - Ground Level at the South Locker Rooms.<br />

Memo:<br />

Five carpets / mats.<br />

Areas noted in compliance:<br />

Floor surface is slip resistant.<br />

Changes in level do not exceed 1/4” vertical or 1/2” with 1:2 bevel.<br />

Areas not meeting new construction standards:<br />

Carpets or carpet tiles are securely attached and do not exceed 1/2” in height.<br />

Carpet’s exposed edges are fastened to floor surfaces and have trim along entire length.<br />

Recommendation:<br />

Secure loose doormat.<br />

Photo #UCR P5308 South Locker Room & Concession Stand-3-1 (originally 0005)<br />

5


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5308 South Locker Room & Concession Stand in Riverside, CA<br />

900 University Avenue<br />

4. Signage - Ground Level at the South Locker Rooms.<br />

Memo:<br />

No signage.<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />

leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably on<br />

the right.<br />

Recommendation:<br />

Install permanent ID sign to latch side of door.<br />

Photo #UCR P5308 South Locker Room & Concession Stand-4-1 (originally 0006)<br />

6


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5308 South Locker Room & Concession Stand in Riverside, CA<br />

900 University Avenue<br />

5. Visual/Audible Alarms - Ground Level at the South Locker Rooms.<br />

Memo:<br />

Three rooms without fire alarms.<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

The alarm is integrated into the building or facility alarm system.<br />

Recommendation:<br />

Requires engineering/architectural evaluation.<br />

Photo #UCR P5308 South Locker Room & Concession Stand-5-1 (originally 0007)<br />

7


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5308 South Locker Room & Concession Stand in Riverside, CA<br />

900 University Avenue<br />

6. Electrical Controls & Receptacles/Fire Alarm Boxes - Gym Room<br />

(Northeast End) at the South Locker Rooms.<br />

Memo:<br />

Areas noted in compliance:<br />

The center of electrical receptacles or controls, and switches to control lighting, heating, cooling & appliances are 48”<br />

max. above the floor or working platform. (49-3/4”.)<br />

The center of electrical outlets intended to be used by the room occupant are located a min. of 15” above the floor<br />

or working platform.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5308 South Locker Room & Concession Stand-6-1 (originally 0008)<br />

8


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5308 South Locker Room & Concession Stand in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5308 South Locker Room & Concession Stand-6-2 (originally 0009)<br />

9


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5308 South Locker Room & Concession Stand in Riverside, CA<br />

900 University Avenue<br />

7. Doors - Men’s Restroom Adjacent to the Gym Door at the South<br />

Locker Rooms.<br />

Memo:<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

32” minimum clear width of doorway.<br />

5 lb. maximum pressure to operate interior doors.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5308 South Locker Room & Concession Stand-7-1 (originally 0010)<br />

10


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5308 South Locker Room & Concession Stand in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5308 South Locker Room & Concession Stand-7-2 (originally 0011)<br />

11


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5308 South Locker Room & Concession Stand in Riverside, CA<br />

900 University Avenue<br />

8. Clear Space at Doors - Men’s Restroom Adjacent to the Gym Door at<br />

the South Locker Rooms.<br />

Memo:<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

60” min. clear space in direction of door swing.<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />

Minimum strike side clearance on PUSH side of door: 0”.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5308 South Locker Room & Concession Stand-8-1 (originally 0012)<br />

12


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5308 South Locker Room & Concession Stand in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5308 South Locker Room & Concession Stand-8-2 (originally 0013)<br />

13


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5308 South Locker Room & Concession Stand in Riverside, CA<br />

900 University Avenue<br />

9. Identification Symbols, Restrooms - Men’s Restroom Adjacent to the<br />

Gym Door at the South Locker Rooms.<br />

Memo:<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Door mounted signage: Men’s - Equilateral triangle with 12” sides, 1/4” thick with the vertex pointing up. The triangle<br />

symbol contrasts with the door, light on dark background or dark on light background.<br />

Wall mounted signage: Symbol of accessibility is mounted on wall sign adjacent to latch side of door.<br />

Recommendation:<br />

Install door-mounted sign on single door.<br />

Install wall-mounted sign at single entrance.<br />

Photo #UCR P5308 South Locker Room & Concession Stand-9-1 (originally 0014)<br />

14


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5308 South Locker Room & Concession Stand in Riverside, CA<br />

900 University Avenue<br />

10. Multiple Accommodation Toilets - Men’s Restroom Adjacent to the<br />

Gym Door at the South Locker Rooms.<br />

Memo:<br />

No accessible stall. Provide an accessible stall.<br />

Areas noted in compliance:<br />

60” min. diameter turning circle clear of objects from floor height to 27” in room.<br />

44” min. clear path provided throughout facility.<br />

Areas not meeting new construction standards:<br />

60” minimum width of stall.<br />

18” betwen centerline of water closet and side wall or partition.<br />

32” minimum from side of water closet to opposite wall or partition.<br />

42” minimum from centerline of water closet to opposite wall or partition.<br />

Recommendation:<br />

Requires engineering/architectural evaluation.<br />

Provide major renovation (including moving plumbing locations and walls).<br />

Photo #UCR P5308 South Locker Room & Concession Stand-10-1 (originally 0015)<br />

15


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5308 South Locker Room & Concession Stand in Riverside, CA<br />

900 University Avenue<br />

11. Lavatories - Men’s Restroom Adjacent to the Gym Door at the South<br />

Locker Rooms.<br />

Memo:<br />

Areas noted in compliance:<br />

30” x 48” min. clear space provided in front of lavatory that allows forward approach (doors may not encroach into this<br />

space).<br />

Required clear space extends 19” max. underneath the lavatory and adjoins or over laps an accessible route.<br />

29” min. clearance from bottom of apron to floor surface.<br />

27” high x 8” deep knee clearance under front lip.<br />

30” wide x 9” high x 17” deep clearance from front of lavatory.<br />

There are no sharp or abrasive elements under lavatory.<br />

Faucets are lever type, electronically activated or approved self closing valves (10 second open flow).<br />

Faucets are operable with one hand and do not require tight grasping, pinching or twisting of wrist.<br />

5 lb. max. force required to operate controls.<br />

Areas not meeting new construction standards:<br />

18” minimum from center of fixture to side wall or partition. (16-1/2”.)<br />

34” max. height to rim or counter above floor surface. (36”.)<br />

Drain and piping is insulated or configured to prevent contact.<br />

Recommendation:<br />

Relocate existing lavatory.<br />

Insulate pipes under lavatory (or sink when applicable).<br />

16


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5308 South Locker Room & Concession Stand in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5308 South Locker Room & Concession Stand-11-1 (originally 0016)<br />

17


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5308 South Locker Room & Concession Stand in Riverside, CA<br />

900 University Avenue<br />

12. Urinals - Men’s Restroom Adjacent to the Gym Door at the South<br />

Locker Rooms.<br />

Memo:<br />

Areas noted in compliance:<br />

A clear floor space that is a minimum 30” wide by 48” deep is provided in front of the urinal to allow forward approach.<br />

5 lb max. pressure to operate valve.<br />

Walls within 24” of front and sides of urinals are smooth, hard and non-absorbent to 48” height, and are not adversely<br />

affected by moisture.<br />

Areas not meeting new construction standards:<br />

17” maximum urinal rim height above the finished floor. (23-1/2” high.)<br />

14” minimum projection and 17” maximum projection from the wall. (12”.)<br />

44” maximum height to flush valve above finished floor. (52”.)<br />

Recommendation:<br />

Replace/Install urinal.<br />

Photo #UCR P5308 South Locker Room & Concession Stand-12-1 (originally 0017)<br />

18


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5308 South Locker Room & Concession Stand in Riverside, CA<br />

900 University Avenue<br />

13. Accessories - Men’s Restroom Adjacent to the Gym Door at the<br />

South Locker Rooms.<br />

Memo:<br />

Areas noted in compliance:<br />

40” maximum height to bottom of reflective surface of mirror.<br />

Accessories do not require tight grasping, pinching or twisting of the wrist to operate.<br />

A minimum 30” x 48” minimum clear floor or ground space is provided to allow forward or parallel approach to accessories.<br />

A maximum of 5 lbs. force is required to operate mechanisms.<br />

Areas not meeting new construction standards:<br />

40” max. height to all other fixtures (i.e., soap dispensers, towels, toilet seat covers, auto dryers, sanitary napkins, waste<br />

recepatacles, etc.). (Paper towel dispenser - 62” / soap dispenser - 45”.)<br />

Recommendation:<br />

Relocate the paper towel dispenser / hand dryer.<br />

Relocate the soap dispenser.<br />

Photo #UCR P5308 South Locker Room & Concession Stand-13-1 (originally 0018)<br />

19


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5308 South Locker Room & Concession Stand in Riverside, CA<br />

900 University Avenue<br />

14. Showers - (roll in compartment) - Men’s Restroom Adjacent to the<br />

Gym Door at the South Locker Rooms.<br />

Memo:<br />

No accessible stall.<br />

Areas noted in compliance:<br />

36” x 60” min. compartment size.<br />

36” x 60” min. clear floor space adjoining compartment.<br />

2% max. surface slope in any direction (thresholds are not allowed).<br />

Areas not meeting new construction standards:<br />

Shower seat is folding and is on wall adjacent to controls.<br />

Recommendation:<br />

Requires engineering/architectural evaluation.<br />

Install compliant seat.<br />

Photo #UCR P5308 South Locker Room & Concession Stand-14-1 (originally 0019)<br />

20


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5308 South Locker Room & Concession Stand in Riverside, CA<br />

900 University Avenue<br />

15. Electrical Controls & Receptacles/Fire Alarm Boxes - Men’s Restroom<br />

Adjacent to the Gym Door at the South Locker Rooms.<br />

Memo:<br />

Areas noted in compliance:<br />

The center of electrical receptacles or controls, and switches to control lighting, heating, cooling & appliances are 48”<br />

max. above the floor or working platform. (50-1/4”.)<br />

The center of electrical outlets intended to be used by the room occupant are located a min. of 15” above the floor<br />

or working platform.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5308 South Locker Room & Concession Stand-15-1 (originally 0020)<br />

21


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5308 South Locker Room & Concession Stand in Riverside, CA<br />

900 University Avenue<br />

16. Doors - Lounge Adjacent to the Gym at the South Locker Rooms.<br />

Memo:<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

32” minimum clear width of doorway.<br />

5 lb. maximum pressure to operate interior doors.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5308 South Locker Room & Concession Stand-16-1 (originally 0021)<br />

22


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5308 South Locker Room & Concession Stand in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5308 South Locker Room & Concession Stand-16-2 (originally 0022)<br />

23


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5308 South Locker Room & Concession Stand in Riverside, CA<br />

900 University Avenue<br />

17. Clear Space at Doors - Lounge Adjacent to the Gym at the South<br />

Locker Rooms.<br />

Memo:<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

60” min. clear space in direction of door swing.<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Minimum strike side clearance on PUSH side of door: 0”.<br />

Areas not meeting new construction standards:<br />

Minimum strike side clearance on PULL side of door: 18” interior doors, front approach. (2” (table).)<br />

Recommendation:<br />

Relocate furniture to provide clear space.<br />

Photo #UCR P5308 South Locker Room & Concession Stand-17-1 (originally 0023)<br />

24


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5308 South Locker Room & Concession Stand in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5308 South Locker Room & Concession Stand-17-2 (originally 0024)<br />

25


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5308 South Locker Room & Concession Stand in Riverside, CA<br />

900 University Avenue<br />

18. Controls, Operating Mechanisms & Vending Machines. - Lounge<br />

Adjacent to the Gym at the South Locker Rooms.<br />

Memo:<br />

Lockers. Replace hardware with an accessible one.<br />

Areas noted in compliance:<br />

Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />

Forward Reach to Objects: Highest operable part of object is a maximum of 48” above the floor surface.<br />

Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />

Areas not meeting new construction standards:<br />

Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />

require tight grasping, pinching or twisting of the wrist to operate. (Pinching required.)<br />

Recommendation:<br />

Replace door hardware with compliant hardware.<br />

Photo #UCR P5308 South Locker Room & Concession Stand-18-1 (originally 0025)<br />

26


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5308 South Locker Room & Concession Stand in Riverside, CA<br />

900 University Avenue<br />

19. Electrical Controls & Receptacles/Fire Alarm Boxes - Lounge<br />

Adjacent to the Gym at the South Locker Rooms.<br />

Memo:<br />

Areas noted in compliance:<br />

The center of electrical receptacles or controls, and switches to control lighting, heating, cooling & appliances are 48”<br />

max. above the floor or working platform.<br />

The center of electrical outlets intended to be used by the room occupant are located a min. of 15” above the floor<br />

or working platform.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5308 South Locker Room & Concession Stand-19-1 (originally 0026)<br />

27


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5308 South Locker Room & Concession Stand in Riverside, CA<br />

900 University Avenue<br />

20. Sales and Service Counters - Concession Stands at the South Locker<br />

Rooms.<br />

Memo:<br />

Areas noted in compliance:<br />

A minimum 30” x 48” clear floor space is provided at the counter and;<br />

One full unobstructed side of the clear floor space adjoins or overlaps an accessible route.<br />

Areas not meeting new construction standards:<br />

A portion of the counter is a minimum of 36” in length, at a height between 28” - 34” above the floor and; (40-1/2”.)<br />

Recommendation:<br />

Lower 36” wide counter section or provide an auxiliary counter with a maximum height of 34”.<br />

Photo #UCR P5308 South Locker Room & Concession Stand-20-1 (originally 0027)<br />