The Use and Applicati<strong>on</strong> of CFD in the Air<br />

C<strong>on</strong>diti<strong>on</strong>ing and Fire Protecti<strong>on</strong> Industry<br />

<str<strong>on</strong>g>Case</str<strong>on</strong>g> <str<strong>on</strong>g>Studies</str<strong>on</strong>g> <strong>on</strong> <strong>Displacement</strong><br />

Ventilati<strong>on</strong><br />

By Richard Palmer<br />

Envir<strong>on</strong>mental Design C<strong>on</strong>sultant<br />

Advanced Envir<strong>on</strong>mental Pty Ltd


What does CFD give us?<br />

• Specific passive design soluti<strong>on</strong>s<br />

• Risk management for designs with tight tolerance<br />

requirements <strong>on</strong> internal c<strong>on</strong>diti<strong>on</strong>s<br />

• Air change effectiveness calculati<strong>on</strong>s<br />

• Another design tool that fine tuens the performance<br />

characteristics by giving more accurate predicti<strong>on</strong>s of<br />

how design soluti<strong>on</strong>s will perform


Introducti<strong>on</strong><br />

o Two case studies where CFD<br />

allowed us to go bey<strong>on</strong>d the<br />

ordinary<br />

o Perimeter loads in a retrofitted<br />

displacement soluti<strong>on</strong> in an<br />

office<br />

o Painting z<strong>on</strong>e c<strong>on</strong>diti<strong>on</strong> in a<br />

gallery requiring AAA<br />

c<strong>on</strong>diti<strong>on</strong>s<br />

http://www.travelideas.com.au/uploaded_images/melbourne-cbd-ariel-view-748678.jpg


Bay windows in the GBCA Fit-out<br />

• High solar load in the bay<br />

windows <strong>on</strong> the east<br />

perimeter<br />

• Retrofitted displacement<br />

soluti<strong>on</strong> with a raised floor<br />

• Design soluti<strong>on</strong> to exhaust<br />

the load, not c<strong>on</strong>diti<strong>on</strong> the<br />

load<br />

• Light shelf soluti<strong>on</strong> that<br />

channels hot air into a<br />

perimeter bulk head<br />

passively, from which it is<br />

exhausted


Moorilla Art Gallery<br />

• Private gallery in Tasmania<br />

• Internati<strong>on</strong>al touring gallery<br />

requiring AAA c<strong>on</strong>diti<strong>on</strong>s<br />

– Temp difference 2°C across<br />

the painting z<strong>on</strong>e<br />

– Restricti<strong>on</strong> of air velocities to<br />

less than 0.35 m/s<br />

• <strong>Displacement</strong> Ventilati<strong>on</strong>,<br />

with different supply opti<strong>on</strong>s


Secti<strong>on</strong>


Results<br />

Average<br />

Temperature at<br />

bottom of<br />

painting z<strong>on</strong>e<br />

Average<br />

Temperature at<br />

top of painting<br />

z<strong>on</strong>e<br />

Average<br />

Temperature<br />

across painting<br />

z<strong>on</strong>e<br />

Maximum<br />

Velocity 100mm<br />

above the floor<br />

° C ° C ° C m/s<br />

Opti<strong>on</strong> A-1 20.02 21.62 1.6 0.34<br />

Opti<strong>on</strong> A-2 19.96 21.59 1.63 0.34<br />

Opti<strong>on</strong> A-1-1 20.04 21.77 1.73 0.35


The Use and Applicati<strong>on</strong> of<br />

CFD in the Air C<strong>on</strong>diti<strong>on</strong>ing<br />

and Fire Protecti<strong>on</strong> Industry<br />

AIRAH NSW February 2008